Tracer® ZN.520
Analog Inputs
Table 28. Analog Inputs
Description | Terminals | Function | Range |
Zone | Space temperature input | 5° to 122°F | |
|
|
|
|
Ground | Analog ground | NA | |
|
|
|
|
Set | Setpoint input | 40° to 115°F (4.4° to 46.1°C) | |
|
|
|
|
Fan | Fan switch input | 4821 to 4919 W (Off) | |
|
|
| 2297 to 2342 W (Auto) |
|
|
| 10593 to 10807 W (Low) |
|
|
| 13177 to 13443 W (Medium) |
|
|
| 15137 to 16463 W (High) |
|
|
|
|
Ground | Analog ground | NA | |
|
|
|
|
Analog Input 1 | Entering water temperature | ||
| Analog ground | NA | |
Analog Input 2 | Discharge air temperature | ||
| Analog ground | NA | |
Analog Input 3 | Fresh air temp/Generic temp | ||
| Analog ground | NA | |
Analog Input 4 | Universal Input | 0 – 100% | |
|
| Generic | 0 – 100% |
|
| Humidity | 0 – 2000ppm |
|
| CO2 |
|
| Analog ground | NA | |
|
|
|
|
Ground | Analog ground | NA |
Notes:
1)The zone sensor, entering water temperature sensor, discharge air sensor, and the outside air tempera- ture sensor are 10KW thermistors.
2)Zone sensor:
Wall mounted sensors include a thermistor soldered to the sensor’s circuit board. Unit mounted sensors include a return air sensor in the units return air stream.
3) Changeover units include an entering water temperature sensor.
75 |