Trane LO Tracer ZN.010 and ZN.510, Controller Diagnostics, Latching, Valves, Elect. Heat

Models: LO

1 136
Download 136 pages 3.51 Kb
Page 50
Image 50
Diagnostics

Tracer® ZN.010

and ZN.510

Diagnostics

Table 14. Controller Diagnostics

Diagnostic

Latching

Fan

Valves

Elect. Heat

Damper

 

Yes/No

 

 

 

 

Auxiliary

No

Enabled

No action

No action

No action

temp. failure

 

 

 

 

 

Condensate

Yes

Off

Closed

Off

Closed

overflow

 

 

 

 

 

detection

 

 

 

 

 

Entering

No

Enabled

Enabled

Enabled

Enabled

water temp.

 

 

 

 

 

failure

 

 

 

 

 

Fan mode

No

Enabled

Enabled

Enabled

Enabled

failure

 

 

 

 

 

Invalid unit

Yes

Disabled

Disabled

Disabled

Disabled

configuration

 

 

 

 

 

failure

 

 

 

 

 

Low temp.

Yes

Off

Open

Off

Closed

detection

 

 

 

 

 

Maintenance

Yes

Enabled

No action

No action

No action

required

 

 

 

 

 

Setpoint

No

Enabled

No action

No action

No action

Zone temp.

No

Off

Closed

Off

Closed

failure

 

 

 

 

 

Notes:

Priority Level: Diagnostics are listed in order from highest to lowest priority. The controller senses and records each diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The diagnostics affect unit operation according to priority level.

Latching: A latching diagnostic requires a manual reset of the controller; while a non-latching diagnostic automatically resets when the input is present and valid.

Enabled: End device is allowed to run if there is a call for it to run.

Disabled: End device is not allowed to run even if there is a call for it to run.

No Action: The diagnostic has no affect on the end device.

50

UNT-IOM-6

Page 50
Image 50
Trane LO manual Tracer ZN.010 and ZN.510, Controller Diagnostics, Latching, Valves, Elect. Heat, Damper, Yes/No, Notes