Trane LO manual Tracer ZN.010 and ZN.510, Valves Stay Open, Probable Cause, Explanation

Models: LO

1 136
Download 136 pages 3.51 Kb
Page 55
Image 55
Table 17. Valves Stay Open

Tracer® ZN.010

and ZN.510

Table 17. Valves Stay Open

Probable Cause

Explanation

Normal operation

The controller opens and closes the valves to meet the unit capacity require-

 

ments.

Valve override

The controller can communicate a valve override request to affect the

 

valve operation.

Manual output test

The controller includes a manual output test sequence that verifies analog and

 

binary output operation and the associated wiring. However, based on the

 

current step in the test sequence, the valves may be open. Refer to the “Manual

 

Output Test” section on page 51.

Diagnostic present

A specific list of diagnostics affects valve operation. For more information, see

 

the “Diagnostics” section on page 50.

Sampling logic

The controller includes entering water temperature sampling logic that automati

 

cally invokes during 2-pipe or 4-pipe changeover to determine if the

 

entering water temperature is correct for the unit operating mode. Refer to the

 

“Entering Water Temperature Sampling” section on page 41.

Unit configuration

The controller must be properly configured based on the actual installed end

 

devices and application. When the unit configuration does not match the actual

 

end device, the valves may not work correctly.

Unit wiring

The wiring between the controller outputs and the valve(s) must be present and

 

correct for normal valve operation. Refer to the typical unit wiring diagrams in

 

the Appendix of this manual.

UNT-IOM-6

55

Page 55
Image 55
Trane LO manual Tracer ZN.010 and ZN.510, Valves Stay Open, Probable Cause, Explanation