Tracer® ZN.010
and ZN.510
Table 17. Valves Stay Open
Probable Cause | Explanation |
Normal operation | The controller opens and closes the valves to meet the unit capacity require- |
| ments. |
Valve override | The controller can communicate a valve override request to affect the |
| valve operation. |
Manual output test | The controller includes a manual output test sequence that verifies analog and |
| binary output operation and the associated wiring. However, based on the |
| current step in the test sequence, the valves may be open. Refer to the “Manual |
| Output Test” section on page 51. |
Diagnostic present | A specific list of diagnostics affects valve operation. For more information, see |
| the “Diagnostics” section on page 50. |
Sampling logic | The controller includes entering water temperature sampling logic that automati |
| cally invokes during |
| entering water temperature is correct for the unit operating mode. Refer to the |
| “Entering Water Temperature Sampling” section on page 41. |
Unit configuration | The controller must be properly configured based on the actual installed end |
| devices and application. When the unit configuration does not match the actual |
| end device, the valves may not work correctly. |
Unit wiring | The wiring between the controller outputs and the valve(s) must be present and |
| correct for normal valve operation. Refer to the typical unit wiring diagrams in |
| the Appendix of this manual. |
55 |