Condensate
Overflow
Detection Device
inch inside diameter flexible plastic tube over the nipple and secure with a field supplied hose clamp.
Note: The installer is responsible for adequately insulating field piping. See the “External Insulating Requirements section on page 20 for more information.
The condensate overflow detection device is an option on
Figure 12. Condensate overflow switch installed in a vertical auxiliary drain pan.
Figure 13. Condensate overflow switch installed in a horizontal auxiliary drain pan.
Automatic
Changeover
Sensor
If the unit does not have a factory piping package, the factory at- taches the sensor and coiled lead wires to the piping side end panel. The installer should attach the sensor parallel to and in direct contact with the supply water pipe.
Note: The installer is responsible to ensure the changeover sensor is installed in a location that can sense active water temperature. Otherwise, the unit may fail to sense the correct operating mode and disable temperature control.
26 |