Electrical
Grounding
Restrictions
Wall Mounted
Control
Interconnection
Wiring
All sensor and input circuits are normally at or near ground (common) potential. When wiring sensors and other input devices to the Tracer® ZN.010, ZN.510, ZN.520 or TUC, avoid creating ground loops with grounded conductors external to the unit control circuit. Ground loops can affect the measurement accuracy of the controller.
!CAUTION: Unit transformer IT1 provides power to
All input/output circuits (except isolated relay contacts and optically isolated inputs) assume a grounded source, either a ground wire at the supply transformer to control panel chassis, or an installer supplied ground.
Note: Do not connect any sensor or input circuit to an external ground connection.
The installer must provide interconnection wiring to connect wall mounted devices such as a fan mode switch or zone sensor module. Refer to the unit wiring schematic for specific wiring details and point-
Recommendation: Do not bundle or run interconnection wiring in parallel with or in the same conduit with any
Table 3. Maximum Wiring Distances, ft (m)
Device | Wire Size Range |
Max. Wiring Distance |
|
Fan Mode Switch | 14 - 22 AWG |
500 (152.4) |
|
Zone Sensor Module | 16 - 22 AWG |
200 (60.96) |
|
35 |