Trane LO Binary Outputs, Tracer ZN.010 and ZN.510, Occupancy Sensor State Table, Sensor Type

Models: LO

1 136
Download 136 pages 3.51 Kb
Page 43
Image 43
Table 5. Occupancy Sensor State Table

Tracer® ZN.010

and ZN.510

Table 5. Occupancy Sensor State Table

Sensor Type

Sensor Position

Unit Occupancy Mode

Normally Open

Open

Occupied

Normally Open

Closed

Unoccupied

Normally Closed

Open

Unoccupied

Normally Closed

Closed

Occupied

Binary Outputs

Table 6. Binary Outputs

Binary Output

Description

Pin

BOP1

Fan high speed

J1-1

BOP2

Fan medium speed

J1-2

BOP3

Fan low speed

J1-4

BOP4

Main valve

J1-5

BOP5

Auxiliary valve/electric heat

J1-6

BOP6

2-position fresh air damper

J1-7

Notes:

1.In a four-pipe application, BOP4 is used for cooling and BOP5 is used for heating.

2.If no valves are ordered with the unit, the factory default for the Tracer® ZN.010 and ZN.510 controller are:

BOP4 configured as normally closed BOP5 configured as normally open

3.If the fresh air damper option is not ordered on the unit, BOP6 will be configured as none.

UNT-IOM-6

43

Page 43
Image 43