Tracer® ZN.010
and ZN.510
Table 5. Occupancy Sensor State Table
Sensor Type | Sensor Position | Unit Occupancy Mode |
Normally Open | Open | Occupied |
Normally Open | Closed | Unoccupied |
Normally Closed | Open | Unoccupied |
Normally Closed | Closed | Occupied |
Binary Outputs
Table 6. Binary Outputs
Binary Output | Description | Pin |
BOP1 | Fan high speed | |
BOP2 | Fan medium speed | |
BOP3 | Fan low speed | |
BOP4 | Main valve | |
BOP5 | Auxiliary valve/electric heat | |
BOP6 |
Notes:
1.In a
2.If no valves are ordered with the unit, the factory default for the Tracer® ZN.010 and ZN.510 controller are:
BOP4 configured as normally closed BOP5 configured as normally open
3.If the fresh air damper option is not ordered on the unit, BOP6 will be configured as none.
43 |