Trane LO manual Venting the Hydronic Coil, UNT-IOM-6

Models: LO

1 136
Download 136 pages 3.51 Kb
Page 28
Image 28
Venting the Hydronic Coil

Venting the Hydronic Coil

The hydronic coil contains a vent, either manual or automatic, to release air from the unit. This vent is not sufficient for venting the water piping system in the building.

Locate the coil air vent on the piping side, above the coil connections on the unit. Perform the following steps to vent the coil after installing the unit. See Figure 16.

1.Pressurize the building piping system with water and vent any trapped air at system vents.

2.For units with manual air vents, back the set screw out to expel air from the unit and then re-tighten the set screw.

The automatic air vent should require no adjustment for the coil to vent. However, if the coil does not vent immediately, unscrew the outer portion of the fitting to expel air from the port.

If debris has become trapped in the vent, completely remove the outer portion of the fitting and clean.

Figure 16. The hydronic coil air vent is above the coil connections. A horizontal unit is on the left and a vertical on the right.

28

UNT-IOM-6

Page 28
Image 28