Terminal Unit
Control (TUC)
Troubleshooting
|
| More detailed information about programming and operating the TUC | |
|
| board can be found in Trane publication, | |
|
| tion Operation and Programming Guide. | |
| Table 44. TUC Does Not Communicate | ||
| Probable Cause | Explanation | |
| TUC is not addressed correctly | Verify the ICS address according to Table 21 on page 63. Each TUC | |
|
| on the link requires a unique address in the range of 33 to 96. Set or | |
|
| modify the DIP switches, then short the TUC test input momentarily. | |
| Incorrect comm 4 wiring | Verify that the link is twisted pair Trane part # | |
|
| lent. TUC (comm 4) wiring is polarity sensitive throughout the com- | |
|
| munication link. If possible, isolate the TUC from the rest of the ICS | |
|
| link to determine if the problem exists in the comm wiring or in the | |
|
| TUC board. | |
| Defective TUC board | If the previous solutions do not fix the problem, it may be necessary | |
|
| to replace the TUC board. | |
Table 45. Fan Outputs not Energizing |
| ||
Probable Cause | Explanation |
| |
Random start enabled | When enabled, the random start feature delays the unit | ||
|
| 3 to 32 seconds (configurable) after | |
When enabled, the | |||
|
| startup for two minutes after | |
|
| Tracer® system ample time to communicate its fan control request. | |
Cycling fan operation | When configured to cycle with capacity, the unit fan cycles off when | ||
|
| there is no call for heating or cooling. The heating/cooling sources | |
|
| cycle on or off periodically with the unit fan to match the capacity | |
|
| according to | |
Unoccupied operation | The fan cycles with capacity when the unit is in unoccupied mode. | ||
|
| This occurs even if the unit is configured for continuous fan opera- | |
|
| tion. While unoccupied, the fan cycles on or off with heating/ | |
|
| cooling to match the capacity according to | |
|
| (PWM) logic. The TUC can be placed in unoccupied mode either | |
|
| through a Tracer® system or through BIP3 if it has been configured | |
|
| as occupied/unoccupied. | |
Latching diagnostic present | A specific list of diagnostics effects fan operation. For more informa- | ||
|
| tion, see the “Diagnostics” section on page 73. Latching diagnostics | |
|
| require a manual reset to restore normal unit operation. | |
Unit disabled | The Tracer® system can disable the unit via a shutdown input or | ||
|
| BIP1 can be configured as external interlock. | |
Local fan switch: off | Using the local fan mode switch to determine fan operation, the | ||
|
| “off” position on the switch controls the unit fan to off. |
109 |