Trane LO manual Installing the Unit, Vertical Units

Models: LO

1 136
Download 136 pages 3.51 Kb
Page 15
Image 15
Installing the Unit

Installing the Unit

Vertical Units

Cabinet & Concealed Units

Size

 

L (in.)

02

21 1/4

03

21 1/4

04

26 1/4

06

35 3/4

08

44 1/4

10

63 1/4

12

63 1/4

Before beginning installation, refer to Table 1 on page 17 for unit weights and Figure 3 on page 12 for service and operating clearances. In addition, refer to the unit submittal for installation details.

!CAUTION: Do not allow electrical wire to fall between the unit and installation surface. Failure to comply may cause electrical shorts or difficulty in access- ing wires.

Install vertical units in an upright position using the 5/8 inch diameter double key slot hanger holes, located on the back of unit. The hanger holes allow a maximum shank size of 5/16 inch diameter threaded rods or lag screws (installer provides). Follow the installation proce- dure below.

1.Prepare wall openings for recessed units. Reference unit submittal for each unit size dimensions.

2.If the unit has leveling legs, adjust them correctly to level unit.

3.Mark the position of the keyslot hanger holes on the wall according to the dimensions given in Figure 4 for each unit size. Align the hole locations evenly.

L

 

 

 

 

 

 

Low Vertical Cabinet & Concealed

 

 

 

 

 

 

 

 

 

 

 

Size

 

 

L (in.)

 

 

 

 

 

 

 

 

 

03

 

 

26 1/4

 

 

 

 

04

 

 

35 3/4

 

 

 

 

06

 

 

44 1/4

 

 

 

 

 

15.5 in.

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12.19 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5 in.

Floor Level

Floor Level

Figure 4. Keyslot Hanger Hole Locations

UNT-IOM-6

15

Page 15
Image 15