Tracer® ZN.520
Table 36. Valves Stay Closed
Probable Cause | Explanation |
Requested mode off | You can communicate a desired operating mode (such as off, heat, and |
| cool) to the controller. When off is communicated to the controller, the |
| unit controls the fan off. There is no heating or cooling (valves are |
| closed). |
Power up control wait | When power up control wait is enabled |
| remains off until one of two conditions occurs:The controller exits power |
| up control wait once it receives communicated information.The controller |
| exits power up control wait once the power up control wait time expires. |
Manual output test | The controller includes a manual output test sequence you can use to |
| verify output operation and associated output wiring. However, based on |
| the current step in the test sequence, the valve(s) may not be open. |
| Refer to the Manual Output Test section. |
Fan mode off | When a local fan mode switch (provided on the Trane zone sensor) |
| determines the fan operation, the off position controls the unit off and |
| valves to close. |
Sampling logic | The controller includes entering water temperature sampling logic which |
| is automatically invoked during |
| entering water temperature is either too cool or too hot for the desired |
| heating or cooling.Refer to the Entering Water Temperature Sampling |
| section. |
Diagnostic present | A specific list of diagnostic affects valve operation. For more information, |
| see the Diagnostics section. |
Unit configuration | The controller must be properly configured based on the actual installed |
| end devices and application. When the unit configuration does not match |
| the actual end devices, the valves may not work correctly.Example: A 2- |
| pipe heat/cool changeover unit will not cool if the entering water tempera |
| ture is too warm for cooling or if the entering water sensor is not present. |
| The unit will not heat if the entering water temperature is too cool for |
| heating. |
Unit wiring | The wiring between the controller outputs and the valve(s) must be |
| present and correct for normal valve operation. |
Random start observed | After power up, the controller always observes a random start from 0 to |
| 25 seconds. The controller remains off until the random start time |
| expires. |
86 |