Fan Board
Assembly
Removal
Replacing the Motor
Follow the procedure below when replacing the coil or making repairs to the fan or motor.
!WARNING: Allow rotating fan to stop before servicing equipment. Failure to do so may cause severe personal injury or death.
Vertical Units
1.Remove the front panel of cabinet and recessed units.
2.Pull the main and overflow drain hoses of the main drain pan into the inside of the
3.Remove the two fanboard mounting screws shown in Figure 35.
4.Slide the fanboard out horizon- tally to remove.
Horizontal Units |
|
1. Open the bottom panel of |
|
cabinet and recessed models. | Figure 35. Remove the two |
2. Remove the main drain pan | mounting screws located |
under the fanboard to slide it | |
following the instructions given | out. |
under the drain pan section above for horizontal
3.While supporting the fanboard in place, remove the two fanboard mounting screws which secure the fanboard to the unit.
!CAUTION: Support the fanboard when removing it from the unit. Failure to do so may cause personal injury.
The capacitor for all unit motors can be replaced should it fail. Contact the local Trane service department to replace the motor capacitor in the event it fails. However, the motor itself cannot be repaired or rewound. If the motor fails, record the model number from the unit nameplate and present to the local Trane Service Parts Center to purchase a replacement. The motor bearings are perma- nently lubricated and do not require any further oiling.