Tracer® ZN.010
and ZN.510
Table 13. Test Sequence for
Steps | Fan | Cool Output | Heat Output | Damper |
|
| BOP4 (1) | BOP5 | BOP6 |
1. Off | Off | Off | Off | Closed |
2. Fan High | High | Off | Off | Closed |
3. Fan Medium | Medium | Off | Off | Closed |
4. Fan Low | Low | Off | Off | Closed |
5. Cool | High | On | Off | Closed |
6. Heat | High | Off | On | Closed |
7. Fresh Air | High | Off | Off | Open |
Damper (3) |
|
|
|
|
8. Exit | (2) |
|
|
|
|
|
|
|
|
Notes:
(1)At the beginning of step 2, the controller attempts to clear all diagnostics.
(2)For all
(2)After the Fresh Air Damper step, the test sequence performs the Exit step.This initiates a reset and attempts to return the controller to normal operation.
(3)The fresh air damper (BOP6) only energizes during this step if binary output 6 has been configured as a fresh air damper.