Tracer® ZN.520
Unit diagnostics can affect the Tracer® ZN.520 controller operation, causing unit operation to be defined as abnormal. Refer to the Troubleshooting section for more information about abnormal unit operation.
The heating output is controlled based on the heating capacity. At 0% capacity, the heating output is off continuously. Between 0 and 100% capacity, the heating output is controlled according to modulating valve logic (modulating valves) or cycled on
The Tracer® ZN.520 fan output(s) normally run continuously during the occupied and occupied standby modes, but cycle between high and off speeds with heating/cooling during the unoccupied mode. When in the occupied mode or occupied standby mode and the fan speed is set at the high, medium, or low position, the fan runs continuously at the selected speed. Refer to the Troubleshooting section for more information on abnormal fan operation.
When the unit’s supply fan is set to auto, the controller’s configura- tion determines the fan speed when in the occupied mode or occu- pied standby mode. The fan runs continuously at the configured heating fan speed or cooling fan speed. For all fan speed selections except off, the fan cycles off during unoccupied mode.
The economizer outdoor air damper is never used as a source of heating. Instead, the economizer damper (when present) is only used for ventilation; therefore, the damper is at the occupied minimum position in the occupied mode. The damper control is primarily associated with occupied fan operation.
Fan Mode Operation | For multiple fan speed applications, the Tracer® ZN.520 controller |
| offers additional fan configuration flexibility. Separate default fan |
| speeds for heating and cooling modes can be configured. The fan |
| runs continuously for requested speeds (off, high, medium, or low). |
| When the fan mode switch is in the Auto position or a hardwired fan |
| mode input does not exist, the fan operates at the default configured |
| speed. See Table 21 on page 67 for default fan configuration for heat |
| and cool mode. During unoccupied mode, the fan cycles between |
| high speed and off with heating and cooling fan modes. If the re- |
| quested speed is off, the fan always remains off. |
| During dehumidification, when the fan is on Auto, the fan speed can |
66 |