Trane LO TUC Sequence of Operation, Cooling and Heating Operation, Setpoint Control, Occupied

Models: LO

1 136
Download 136 pages 3.51 Kb
Page 92
Image 92
TUC Sequence of Operation

Terminal Unit

Control (TUC)

TUC Sequence of Operation

Cooling and Heating Operation

Setpoint Control

·Occupied

·Unoccupied

·Tracer® with supply fan control

Occupied

In the occupied mode, the factory configures the TUC for continuous occupied fan cycle. With the fan control set to auto, the fan operates at the required speed to meet the cooling or heating capacity.

However, the fan will run at one set speed continuously if set in the high, medium, or low position.

Unoccupied

In the unoccupied mode, the TUC cycles the fan between off and high speed to satisfy the unoccupied setpoint. However, if the occupied preheat damper position is closed and the room setpoint is 3° F above (cool down) or 3° F below (warm-up) setpoint, the fan runs at high speed when exiting the unoccupied mode to occupied mode. Also, if the occupied preheat damper position is configured as closed, the fan will run in high speed any time the room temperature falls 3° F or below room setpoint in occupied heating mode.

Tracer® with supply fan control

If the unit is communicating with Tracer® and the supply fan control programming point is configured for Tracer® (the factory configures as local), then Tracer® will control the fan regardless of the fan mode switch position.

All TUC lockouts (latching diagnostics) are manually reset whenever the fan mode switch is set to the off position or when power is restored to the unit. The last diagnostic to occur is retained until the unit power is disconnected. Refer to Trane publication, EMTX-IOP-1TUC Installation Operation and Programming Guide, for specific instructions regarding the procedure for running the TUC.

Adjust the cooling setpoint by using either the setpoint adjustment knob, resetting the TUC default values, or Tracer® downloaded values. The factory configures the occupied heat or cool setpoint source for local mode. The local mode allows the local setpoint knob to deter- mine the cooling setpoint If using Tracer® to define the heat or cool setpoint source, the TUC uses the Tracer® setpoints. If Tracer® is not communicating, the TUC will attempt to obtain the heating and cooling setpoint from a local source. If there is no input from a local source, the TUC will resort to its default values.

The TUC limits the parameters of the cooling setpoint input (adjust- able from either the setpoint knob or Tracer® ) to prevent excessively

92

UNT-IOM-6

Page 92
Image 92
Trane LO TUC Sequence of Operation, Cooling and Heating Operation, Setpoint Control, Terminal Unit Control TUC, Occupied