Table 20. Fresh Air Damper Stays Open

Tracer® ZN.010

and ZN.510

Table 20. Fresh Air Damper Stays Open

Probable Cause

Explanation

Normal Operation

The controller opens and closes the fresh air damper based on the controller’s

 

occupancy mode and fan status. Normally, the fresh air damper is open during

 

occupied mode when the fan is running and closed during unoccupied mode.

Manual Output Test

The controller includes a manual output test sequence that verifies analog and

 

binary output operation and associated wiring. However, based on the current

 

step in the test sequence, the fresh air damper may be open. Refer to the

 

“Manual Output Test” section on page 51.

Unit Configuration

The controller must be properly configured based on the actual installed end

 

devices and application. When the unit configuration does not match the actual

 

end device, the damper may not work correctly.

Unit Wiring

The wiring between the controller outputs and the fresh air damper must be

 

present and correct for normal damper operation. Refer to the typical unit wiring

 

diagrams in the Appendix of this manual.