Trane LO manual Binary Inputs, BIP1: Low Temperature Detection Option, BIP3: Occupancy Sensor

Models: LO

1 136
Download 136 pages 3.51 Kb
Page 42
Image 42
Binary Inputs

Tracer® ZN.010

and ZN.510

Binary Inputs

BIP1: Low

Temperature

Detection

Option

BIP2: Condensate

Overflow Detection

Option

BIP3: Occupancy Sensor

The factory hard wires the low temperature detection sensor to binary input #1 (BIP1) on the Tracer® ZN.010 and ZN.510. The sensor defaults normally closed (N.C.), and will trip off the unit on a low temperature diagnostic when detecting low temperature. In addition, the Tracer® ZN.010 and ZN.510 control unit devices as listed below:

Fan: Off

Valves: Open

Electric heat: Off

Damper: Closed

Note: See the “Diagnostics” section on page 50 for more information.

The factory hard wires the condensate overflow sensor to binary input #2 (BIP2) on the Tracer® ZN.010 and ZN.510. The sensor defaults normally closed (N.C.), and will trip off the unit on a condensate overflow diagnostic if condensate reaches the trip point. In addition, the Tracer® ZN.010 and ZN.510 control unit devices as listed below:

Fan: Off

Valves: Closed

Electric heat: Of

Reference Table 6 for the Tracer® ZN.010 and ZN.510’s six binary outputs.

Binary input #3 (BIP3) on Tracer® ZN.010 and ZN.510 is available for field- wiring an occupancy sensor, such as a binary switch or a timeclock, to detect occupancy. The sensor can be either normally open or normally closed. Reference Table 5 on page 43.

42

UNT-IOM-6

Page 42
Image 42
Trane LO manual Binary Inputs, BIP1: Low Temperature Detection Option, BIP2: Condensate Overflow Detection Option