13. Appendix F: Modbus Commands

Code

Name of the

Description of the exception

exception

 

 

16#01

ILLEGAL FUNCTION

The query’s “Function” command code is not implemented in the Modbus slave

 

 

software, or it is unable to process it for the moment.

16#02

ILLEGAL DATA

The combination of the query’s “Starting Address” and “No. of Registers” fields

 

ADDRESS

(or assimilated fields) gives access to one or more addresses which are not

 

 

accessible on the Modbus slave.

16#03

ILLEGAL DATA

The value of one of the Modbus query’s fields is outside the authorized limits.

 

VALUE

This error does not affect the content of the “Data” (or assimilated) fields, as this

 

 

error only takes account of the fields used for managing the Modbus protocol.

16#04

SLAVE DEVICE

An unrecoverable failure has occurred when processin the command.

 

FAILURE

 

 

16#05

ACKNOWLEDGE

The Modbus slave informs the gateway that it has accepted the command

(1)

 

(acknowledgement), but that it will take too long to process it and it cannot afford

 

 

to wait for the completion of this process before sending a response.

 

 

The gateway should transmit subsequent queries in order to determine whether

 

 

the command has finished or not.

16#06

SLAVE DEVICE

The Modbus slave informs the gateway that it is already in the process of

(1)

BUSY

running a command and therefore it cannot run the one transmitted to it.

 

 

So the gateway should re-transmit the query subsequently.

16#07

NEGATIVE

The Modbus slave informs the gateway that it cannot process the requested

(1)

ACKNOWLEDGE

command. This exception only affects commands 13 and 14 (16#0D and

 

 

16#0E). These functions are not part of the standard Modbus commands and are

 

 

not described in this document.

16#08

MEMORY PARITY

The Modbus slave informs the gateway that it has detected a parity error on the

(1)

ERROR

access to its own memory. This exception only affects standard commands 20

 

 

and 21 (16#14 and 16#15) which are not supported by the gateway.

(1) Please see the standard Modbus documentation for further information about these various scenarios.

112

Image 111
Contents LUFP7 Page LUFP9 Page Table of Contents Introduction to the User Guide IntroductionTerminology Introduction to the LUFP7 GatewayDPM1 Notational ConventionsModbus Additional DocumentationIntroduction to the Communication System Architecture Profibus-DP Master Upstream network Profibus-DPPrinciple Used to Configure and Operate the LUFP7 Gateway Modbus Network ABC ConfiguratorLUFP7 gateway HilscherProfibus-DP Configuration Modbus RTU Hardware Implementation of the LUFP7 GatewayOn Receipt Powering the Gateway Mounting the Gateway on a DIN RailMounting the gateway Connecting the Gateway to the Modbus Network LU9GC03Examples of Modbus Connection Topologies LUFP7 Gateway Pin Outs TSXCSA00Wiring Recommendations for the Modbus Network 120 ΩHubs, drops, taps, and line terminations Pin Outs LUFP7 plug --- 9-point SUB-D female Connecting the LUFP7 gateway to the Profibus-DP NetworkNAD 911 04/03 connector Point SUB-D male CablesGND Wiring Recommendations for the Profibus-DP NetworkNAD 911 04 or 03 connector Configuring the Profibus-DP Communication Features Encoding the Gateway AddressNo Internal Line Termination Address = Signalling Profibus-DP Software Implementation of the GatewayIntroduction System ArchitectureConfiguring the Motor Starters Modbus Cycle TimeManaging Degraded Modes Setting Up the Hardware Configuration under PL7 PRO Gateway Configuration under PL7 PRO and SyConSelecting and Adding the Profibus-DP Master Station Creating a Profibus-DP Network under SyConSetting up the Gateway Description Files Selecting and Adding the Gateway to the Profibus-DP Network Editing and Configuring the GatewaySoftware Implementation of the Gateway Possible values Saving and Exporting the Profibus-DP Network ConfigurationDiagnostic length OptionalConfiguring the Gateway I/O under PL7 PRO IW4.0.1 Service PLC input DescriptionService PLC output Description IW4.0Sample reading of a motor starter parameter Description of Services Assigned to Gateway Inputs/OutputsAllocating Symbols to the Gateway Inputs and Outputs Developing a Profibus-DP Application Using and Monitoring the TSX PBY 100 Coupler ConfigurationControl/Status Byte field Gateway Initialization and DiagnosticsDisabled 5.3.2 Profibus-DP Master Control Word Full ManagementProfibus-DP Master Control Word Fbdu Modbus exchange startup Gateway Status Word Bits Description Abchssend New gateway diagnostic11EC Error code associated with the Modbus network ED Error data item associated with the Modbus networkDescription of the error Diagnostic OnlyBits Description Abcdu Modbus exchanges activated Simplified Operation Connecting the Gateway to the Configuration PC Configuring the GatewayRS-232 Link Protocol GNDImporting the Gateway Configuration Installing AbcConfMonitoring the Content of the Gateway’s Memory Transferring a Configuration to the GatewayConfiguring the Gateway Deleting a Modbus Slave Procedure for deleting a Modbus slaveCopying a previously configured Modbus slave Adding a Modbus SlaveAdding a new type of Modbus slave Importing/exporting a Modbus slave configuration Replacing a periodic input data element Changing the Periodic Data Exchanged with a Modbus SlaveReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway Configuring the Gateway IW4.0.19 IW4.0.16IW4.0.17 IW4.0.18Configuring the Gateway Configuring the Gateway Configuring the Gateway Configuring the Gateway Deleting Aperiodic Parameter Data QW4.0.16QW4.0.17 Configuring the Gateway Configuring the Gateway Managing the downstream Changing a Modbus Slave Configuration Changing the name of a Modbus slaveChanging the Address of a Modbus slave With the TeSys U Motor Starters Adding and Setting Up a Modbus CommandModbus response Name of the Modbus command Modbus queryWith a Generic Modbus Slave CPU stop/failure LUFP7 gateway Profibus-DP Modbus RTU Configuration Description Element Configuring the QueryConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Configuring the Content of the Query Frame Field Size Description Frame Configuring the Content of the Response Frame Mode. The default value, CRC, should not be changedStart byte fields Adding a Special Modbus Command Modbus Commands Based on Standard CommandsModbus Commands which Can Be Completely Changed by the User Fieldbus Element Configuring the General Characteristics of the GatewayABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Appendix a Technical Characteristics Communication CharacteristicsEnvironment Communications between other stations Performance Results Inputs General data Identification number Name of the related GSD file GSD File ContentAppendix B LUFP7 Gateway GSD File Identification NumberMaximum response time of the gateway Input Appendix C Default Configuration Configuring Modbus Exchanges 16#1016#06 Content of the Gateway’s Dpram Memory Service Address Size DescriptionInput Data Memory Area Output Data Memory Area Overview of the LUFP7 Tutorial Example Appendix D Sample Use under PL7 PROLUFP7 Gateway Initialization and Diagnostics See note IEC61915 command register Controlling and Supervising the 8 TeSys U Motor StartersTeSys U status register IEC61915 Reading and Writing any TeSys U Motor Starter Parameter Appendix D Sample Use under PL7 PRO Appendix D Sample Use under PL7 PRO Appendix E Profibus-DP Data and Diagnostics Gateway Profibus-DP DiagnosticsBytes Structure Description Bytes Name Description Gateway Configuration DataBytes Name Value General Gateway Information108 Appendix F Modbus Commands Read Holding Registers Command 16#03 Preset Single Register Command 16#06Frame Field Value or properties Modbus Protocol Exception Responses Preset Multiple Registers Command 16#10Code Name Description of the exception Exception LUFP7 Quantum Appendix F Concept and Quantum PLCLeft intentionally blank 114 Page User’s Manual LUFP7 V1.1 2003-05