Schneider Electric LUFP7 user manual Replacing an Output Periodic Data Element

Page 53

6. Configuring the Gateway

6.8.2. Replacing an Output Periodic Data Element

E.g. “TeSys U n°6” motor starter. We are trying to replace the control of the “Command Register” (address 704 = 16#02C0) with the control of the “2nd Command Register” (address 705 = 16#02C1).

The operation consists of changing the value of the “Starting Address” in the “Query” and in the “Response” for the “Preset Multiple Registers” command (Modbus command for writing values of a number of registers).

Select “Starting Address” from the “Query”, then change its value as shown below. You can enter the address of the parameter in decimal format. AbcConf will automatically convert it to hexadecimal. Do the same for the “Starting Address” element of the “Response” because the gateway checks the value of this field when it receives each Modbus response. If the value does not correspond to that of the query, the gateway will ignore the response.

This operation in no way changes the content of the gateway’s memory, because we do not need to change the values of the “Data length” and “Data location” fields of the “Data” element of the “Query”. So no additional operations will be necessary, either in AbcConf, or in SyCon.

On the other hand, the Profibus-DP master PLC software will have to take account of the change in the nature of the corresponding output. In chapter 10.2.2 Output Data Memory Area, page 96, the description of the word located at address 16#020C becomes “value of the motor starter h 2nd command register”. This word corresponds to PLC output word %QW4.0.6 (see chapter 4.2.9 Configuring the Gateway I/O under PL7 PRO, page 32).

54

Image 53
Contents LUFP7 Page LUFP9 Page Table of Contents Introduction to the User Guide IntroductionTerminology Introduction to the LUFP7 GatewayDPM1 Notational ConventionsIntroduction to the Communication System Architecture Additional DocumentationProfibus-DP Master Upstream network Profibus-DP ModbusPrinciple Used to Configure and Operate the LUFP7 Gateway Modbus Network ABC ConfiguratorProfibus-DP LUFP7 gatewayHilscher On Receipt Configuration Modbus RTUHardware Implementation of the LUFP7 Gateway Mounting the gateway Powering the GatewayMounting the Gateway on a DIN Rail Examples of Modbus Connection Topologies Connecting the Gateway to the Modbus NetworkLU9GC03 LUFP7 Gateway Pin Outs TSXCSA00Hubs, drops, taps, and line terminations Wiring Recommendations for the Modbus Network120 Ω NAD 911 04/03 connector Point SUB-D male Connecting the LUFP7 gateway to the Profibus-DP NetworkCables Pin Outs LUFP7 plug --- 9-point SUB-D femaleGND Wiring Recommendations for the Profibus-DP NetworkNAD 911 04 or 03 connector No Internal Line Termination Address = Configuring the Profibus-DP Communication FeaturesEncoding the Gateway Address Signalling Introduction Software Implementation of the GatewaySystem Architecture Profibus-DPManaging Degraded Modes Configuring the Motor StartersModbus Cycle Time Setting Up the Hardware Configuration under PL7 PRO Gateway Configuration under PL7 PRO and SyConSelecting and Adding the Profibus-DP Master Station Creating a Profibus-DP Network under SyConSetting up the Gateway Description Files Selecting and Adding the Gateway to the Profibus-DP Network Editing and Configuring the GatewaySoftware Implementation of the Gateway Diagnostic length Saving and Exporting the Profibus-DP Network ConfigurationOptional Possible valuesConfiguring the Gateway I/O under PL7 PRO Service PLC output Description Service PLC input DescriptionIW4.0 IW4.0.1Sample reading of a motor starter parameter Description of Services Assigned to Gateway Inputs/OutputsAllocating Symbols to the Gateway Inputs and Outputs Developing a Profibus-DP Application Using and Monitoring the TSX PBY 100 Coupler ConfigurationDisabled 5.3.2 Profibus-DP Master Control Word Gateway Initialization and DiagnosticsFull Management Control/Status Byte fieldProfibus-DP Master Control Word Fbdu Modbus exchange startup 11EC Error code associated with the Modbus network Bits Description Abchssend New gateway diagnosticED Error data item associated with the Modbus network Gateway Status WordDescription of the error Diagnostic OnlyBits Description Abcdu Modbus exchanges activated Simplified Operation Connecting the Gateway to the Configuration PC Configuring the GatewayRS-232 Link Protocol GNDImporting the Gateway Configuration Installing AbcConfMonitoring the Content of the Gateway’s Memory Transferring a Configuration to the GatewayConfiguring the Gateway Deleting a Modbus Slave Procedure for deleting a Modbus slave Adding a new type of Modbus slave Copying a previously configured Modbus slave Adding a Modbus Slave Importing/exporting a Modbus slave configuration Replacing a periodic input data element Changing the Periodic Data Exchanged with a Modbus SlaveReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway Configuring the Gateway IW4.0.17 IW4.0.16IW4.0.18 IW4.0.19Configuring the Gateway Configuring the Gateway Configuring the Gateway Configuring the Gateway QW4.0.17 Deleting Aperiodic Parameter DataQW4.0.16 Configuring the Gateway Configuring the Gateway Managing the downstream Changing the Address of a Modbus slave Changing a Modbus Slave ConfigurationChanging the name of a Modbus slave With the TeSys U Motor Starters Adding and Setting Up a Modbus CommandModbus response Name of the Modbus command Modbus queryWith a Generic Modbus Slave CPU stop/failure LUFP7 gateway Profibus-DP Modbus RTU Configuration Description Element Configuring the QueryConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Configuring the Content of the Query Frame Field Size Description Frame Configuring the Content of the Response Frame Mode. The default value, CRC, should not be changedStart byte fields Modbus Commands which Can Be Completely Changed by the User Adding a Special Modbus CommandModbus Commands Based on Standard Commands Fieldbus Element Configuring the General Characteristics of the GatewayABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Environment Appendix a Technical CharacteristicsCommunication Characteristics Communications between other stations Performance Results Inputs General data Appendix B LUFP7 Gateway GSD File GSD File ContentIdentification Number Identification number Name of the related GSD fileMaximum response time of the gateway Input Appendix C Default Configuration 16#06 Configuring Modbus Exchanges16#10 Input Data Memory Area Content of the Gateway’s Dpram MemoryService Address Size Description Output Data Memory Area Overview of the LUFP7 Tutorial Example Appendix D Sample Use under PL7 PROLUFP7 Gateway Initialization and Diagnostics See note TeSys U status register IEC61915 IEC61915 command registerControlling and Supervising the 8 TeSys U Motor Starters Reading and Writing any TeSys U Motor Starter Parameter Appendix D Sample Use under PL7 PRO Appendix D Sample Use under PL7 PRO Bytes Structure Description Appendix E Profibus-DP Data and DiagnosticsGateway Profibus-DP Diagnostics Bytes Name Description Gateway Configuration DataBytes Name Value General Gateway Information108 Appendix F Modbus Commands Frame Field Value or properties Read Holding Registers Command 16#03Preset Single Register Command 16#06 Modbus Protocol Exception Responses Preset Multiple Registers Command 16#10Code Name Description of the exception Exception LUFP7 Quantum Appendix F Concept and Quantum PLCLeft intentionally blank 114 Page User’s Manual LUFP7 V1.1 2003-05