Schneider Electric LUFP7 Gateway Initialization and Diagnostics, Full Management, Summary

Page 37

5. Gateway Initialization and Diagnostics

Each of the three sub-chapters 5.2, 5.3 and 5.3.2 describes the principle used to initialize and carry out diagnostics on the gateway using each of the three options offered by the gateway. These options can be configured via AbcConf, by changing the assignment of the “Control/Status Byte” field for the “ABC” element (see chapter 6.12.2 “ABC” Element, page 82). The links between these sub-chapters and these options are as follows:

“Control/Status Byte” field

Sub-chapter

Page

Enabled

5.2 Full Management

37

Enabled but no startup lock

5.3 Diagnostic Only

41

5.1.1. Disabled 5.3.2 Profibus-DP Master Control Word

 

The output word located at addresses 16#0200 (MSB) and 16#0201 (LSB) in the gateway’s output memory constitutes the Profibus-DP master command word. Its structure is described below:

Bits

Description

15FB_HS_CONFIRM: Acknowledgement bit of a gateway diagnostic

The Profibus-DP master must compare the value of the FB_HS_CONFIRM bit to the value of the ABC_HS_SEND bit (bit 15 in the gateway’s status word). If these two values are different, this means that the gateway has transmitted a new diagnostic to the Profibus-DP master.

To tell the gateway that it has read a diagnostic, the Profibus-DP master must copy the value of the ABC_HS_SEND bit to the FB_HS_CONFIRM bit. This allows the gateway to issue a new diagnostic.

Summary:

If ( FB_HS_CONFIRM = ABC_HS_SEND ) Æ The gateway’s status word contains a diagnostic which has already been acknowledged by the Profibus-DP master. So the gateway is free to use this status word to place another diagnostic there.

Else Æ A new diagnostic is available in the gateway’s status word. The Profibus-DP master can read this diagnostic, but must also copy the value of ABC_HS_SEND to FB_HS_CONFIRM in order to allow the gateway to generate new diagnostics.

0-14 Reserved.

 

Simplified Operation

43

The option chosen in the default configuration is “Enabled but no startup lock.”

5.2. Full Management

Until it receive an order to start up the Modbus exchanges from the Profibus-DP master, the LUFP7 gateway does not transmit any queries on the Modbus network. The Profibus-DP master can then deactivate these exchanges by inverting this startup order. Subsequently these two orders may be reiterated by the Profibus-DP master.

The Modbus exchange startup order is located in a 16-bit register occupying the addresses 16#0200 and 16#0201 in the gateway’s memory (outputs). A second 16-bit register, located at the addresses 16#0000 and 16#0001 (inputs), allows the gateway to send diagnostics to the Profibus-DP master.

So you must configure your Profibus-DP master so that it has access to the first two bytes of the gateway’s output data area, as well as to the first two bytes of the gateway’s input data area (see chapter 4.2 Gateway Configuration under PL7 PRO and SyCon, page 26).

38

Image 37
Contents LUFP7 Page LUFP9 Page Table of Contents Introduction to the User Guide IntroductionTerminology Introduction to the LUFP7 GatewayDPM1 Notational ConventionsIntroduction to the Communication System Architecture Additional DocumentationProfibus-DP Master Upstream network Profibus-DP ModbusPrinciple Used to Configure and Operate the LUFP7 Gateway Modbus Network ABC ConfiguratorHilscher LUFP7 gatewayProfibus-DP Hardware Implementation of the LUFP7 Gateway Configuration Modbus RTUOn Receipt Mounting the Gateway on a DIN Rail Powering the GatewayMounting the gateway LU9GC03 Connecting the Gateway to the Modbus NetworkExamples of Modbus Connection Topologies LUFP7 Gateway Pin Outs TSXCSA00120 Ω Wiring Recommendations for the Modbus NetworkHubs, drops, taps, and line terminations NAD 911 04/03 connector Point SUB-D male Connecting the LUFP7 gateway to the Profibus-DP NetworkCables Pin Outs LUFP7 plug --- 9-point SUB-D femaleGND Wiring Recommendations for the Profibus-DP NetworkNAD 911 04 or 03 connector Encoding the Gateway Address Configuring the Profibus-DP Communication FeaturesNo Internal Line Termination Address = Signalling Introduction Software Implementation of the GatewaySystem Architecture Profibus-DPModbus Cycle Time Configuring the Motor StartersManaging Degraded Modes Setting Up the Hardware Configuration under PL7 PRO Gateway Configuration under PL7 PRO and SyConSelecting and Adding the Profibus-DP Master Station Creating a Profibus-DP Network under SyConSetting up the Gateway Description Files Selecting and Adding the Gateway to the Profibus-DP Network Editing and Configuring the GatewaySoftware Implementation of the Gateway Diagnostic length Saving and Exporting the Profibus-DP Network ConfigurationOptional Possible valuesConfiguring the Gateway I/O under PL7 PRO Service PLC output Description Service PLC input DescriptionIW4.0 IW4.0.1Sample reading of a motor starter parameter Description of Services Assigned to Gateway Inputs/OutputsAllocating Symbols to the Gateway Inputs and Outputs Developing a Profibus-DP Application Using and Monitoring the TSX PBY 100 Coupler ConfigurationDisabled 5.3.2 Profibus-DP Master Control Word Gateway Initialization and DiagnosticsFull Management Control/Status Byte fieldProfibus-DP Master Control Word Fbdu Modbus exchange startup 11EC Error code associated with the Modbus network Bits Description Abchssend New gateway diagnosticED Error data item associated with the Modbus network Gateway Status WordDescription of the error Diagnostic OnlyBits Description Abcdu Modbus exchanges activated Simplified Operation Connecting the Gateway to the Configuration PC Configuring the GatewayRS-232 Link Protocol GNDImporting the Gateway Configuration Installing AbcConfMonitoring the Content of the Gateway’s Memory Transferring a Configuration to the GatewayConfiguring the Gateway Deleting a Modbus Slave Procedure for deleting a Modbus slaveAdding a Modbus Slave Copying a previously configured Modbus slaveAdding a new type of Modbus slave Importing/exporting a Modbus slave configuration Replacing a periodic input data element Changing the Periodic Data Exchanged with a Modbus SlaveReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway Configuring the Gateway IW4.0.17 IW4.0.16IW4.0.18 IW4.0.19Configuring the Gateway Configuring the Gateway Configuring the Gateway Configuring the Gateway QW4.0.16 Deleting Aperiodic Parameter DataQW4.0.17 Configuring the Gateway Configuring the Gateway Managing the downstream Changing the name of a Modbus slave Changing a Modbus Slave ConfigurationChanging the Address of a Modbus slave With the TeSys U Motor Starters Adding and Setting Up a Modbus CommandModbus response Name of the Modbus command Modbus queryWith a Generic Modbus Slave CPU stop/failure LUFP7 gateway Profibus-DP Modbus RTU Configuration Description Element Configuring the QueryConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Configuring the Content of the Query Frame Field Size Description Frame Configuring the Content of the Response Frame Mode. The default value, CRC, should not be changedStart byte fields Modbus Commands Based on Standard Commands Adding a Special Modbus CommandModbus Commands which Can Be Completely Changed by the User Fieldbus Element Configuring the General Characteristics of the GatewayABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Communication Characteristics Appendix a Technical CharacteristicsEnvironment Communications between other stations Performance Results Inputs General data Appendix B LUFP7 Gateway GSD File GSD File ContentIdentification Number Identification number Name of the related GSD fileMaximum response time of the gateway Input Appendix C Default Configuration 16#10 Configuring Modbus Exchanges16#06 Service Address Size Description Content of the Gateway’s Dpram MemoryInput Data Memory Area Output Data Memory Area Overview of the LUFP7 Tutorial Example Appendix D Sample Use under PL7 PROLUFP7 Gateway Initialization and Diagnostics See note Controlling and Supervising the 8 TeSys U Motor Starters IEC61915 command registerTeSys U status register IEC61915 Reading and Writing any TeSys U Motor Starter Parameter Appendix D Sample Use under PL7 PRO Appendix D Sample Use under PL7 PRO Gateway Profibus-DP Diagnostics Appendix E Profibus-DP Data and DiagnosticsBytes Structure Description Bytes Name Description Gateway Configuration DataBytes Name Value General Gateway Information108 Appendix F Modbus Commands Preset Single Register Command 16#06 Read Holding Registers Command 16#03Frame Field Value or properties Modbus Protocol Exception Responses Preset Multiple Registers Command 16#10Code Name Description of the exception Exception LUFP7 Quantum Appendix F Concept and Quantum PLCLeft intentionally blank 114 Page User’s Manual LUFP7 V1.1 2003-05