Schneider Electric LUFP7 user manual Configuring the Motor Starters, Modbus Cycle Time

Page 25

4. Software Implementation of the Gateway

4.1.2. Configuring the Motor Starters

Each motor starter should be configured as follows:

Protocol:

Modbus RTU slave

Modbus address

1 to 8

Bitrate

19,200 bits/s

Data bits

8

Start bits

1

Parity

None

Parity bit

0

Stop bits

1

When using a TeSys U motor starter with a Modbus communication module (LULC031 module), the configuration parameters for the RS485 connection are automatically detected, only the Modbus address of the motor starter needs to be configured.

4.1.3. Modbus Cycle Time

The LUFP7 gateway’s default configuration sets a cycle time of 300 ms on Modbus commands for each of the 8 TeSys U motor starters.

4.1.4. Managing Degraded Modes

The default management for degraded modes is described below. This description only applies to a Premium PLC fitted with a TSX PBY 100 coupler. Please refer to chapter 6.11.2.1 Managing degraded modes, page 71, if you want to change the degraded mode management of one or several Modbus commands.

Desired

behaviour

Reset

Output

Hold

Inputs

Reset

Event

Premium PLC:

Disconnection

Failure of the

Disconnection of

of the upstream

the downstream

CPU stop or failure

LUFP7 gateway

Profibus-DP network

Modbus network

 

 

“Outputs” option

Yes

 

 

equal to “Reset” (1)

Depending on the configuration of the

 

“Outputs” option

——

TeSys U motor starters (2)

equal to “Hold” (1)

 

 

 

 

 

——

 

Yes

 

(1)The “Outputs” option is described in chapter 4.2.8 Importing the Configuration of the Profibus-DP Network under PL7 PRO, page 31. Under PL7 PRO, it can be accessed from the configuration screen for the TSX PBY 100 board.

(2)The desired behaviour with regard to the outputs should be directly configured on each of the TeSys U motor starters.

You may also refer to chapter 4.2 Degraded application mode of the Implementation manual – TSX PBY 100 – PROFIBUS-DP(ref.: TSX DM PBY 100E) for further details regarding the processing of degraded modes by the TSX PBY 100 board.

26

Image 25
Contents LUFP7 Page LUFP9 Page Table of Contents Introduction to the User Guide IntroductionTerminology Introduction to the LUFP7 GatewayDPM1 Notational ConventionsIntroduction to the Communication System Architecture Additional DocumentationProfibus-DP Master Upstream network Profibus-DP ModbusPrinciple Used to Configure and Operate the LUFP7 Gateway Modbus Network ABC ConfiguratorHilscher LUFP7 gatewayProfibus-DP Hardware Implementation of the LUFP7 Gateway Configuration Modbus RTUOn Receipt Mounting the Gateway on a DIN Rail Powering the GatewayMounting the gateway LU9GC03 Connecting the Gateway to the Modbus NetworkExamples of Modbus Connection Topologies LUFP7 Gateway Pin Outs TSXCSA00120 Ω Wiring Recommendations for the Modbus NetworkHubs, drops, taps, and line terminations NAD 911 04/03 connector Point SUB-D male Connecting the LUFP7 gateway to the Profibus-DP NetworkCables Pin Outs LUFP7 plug --- 9-point SUB-D femaleGND Wiring Recommendations for the Profibus-DP NetworkNAD 911 04 or 03 connector Encoding the Gateway Address Configuring the Profibus-DP Communication FeaturesNo Internal Line Termination Address = Signalling Introduction Software Implementation of the GatewaySystem Architecture Profibus-DPModbus Cycle Time Configuring the Motor StartersManaging Degraded Modes Setting Up the Hardware Configuration under PL7 PRO Gateway Configuration under PL7 PRO and SyConSelecting and Adding the Profibus-DP Master Station Creating a Profibus-DP Network under SyConSetting up the Gateway Description Files Selecting and Adding the Gateway to the Profibus-DP Network Editing and Configuring the GatewaySoftware Implementation of the Gateway Diagnostic length Saving and Exporting the Profibus-DP Network ConfigurationOptional Possible valuesConfiguring the Gateway I/O under PL7 PRO Service PLC output Description Service PLC input DescriptionIW4.0 IW4.0.1Sample reading of a motor starter parameter Description of Services Assigned to Gateway Inputs/OutputsAllocating Symbols to the Gateway Inputs and Outputs Developing a Profibus-DP Application Using and Monitoring the TSX PBY 100 Coupler ConfigurationDisabled 5.3.2 Profibus-DP Master Control Word Gateway Initialization and DiagnosticsFull Management Control/Status Byte fieldProfibus-DP Master Control Word Fbdu Modbus exchange startup 11EC Error code associated with the Modbus network Bits Description Abchssend New gateway diagnosticED Error data item associated with the Modbus network Gateway Status WordDescription of the error Diagnostic OnlyBits Description Abcdu Modbus exchanges activated Simplified Operation Connecting the Gateway to the Configuration PC Configuring the GatewayRS-232 Link Protocol GNDImporting the Gateway Configuration Installing AbcConfMonitoring the Content of the Gateway’s Memory Transferring a Configuration to the GatewayConfiguring the Gateway Deleting a Modbus Slave Procedure for deleting a Modbus slaveAdding a Modbus Slave Copying a previously configured Modbus slaveAdding a new type of Modbus slave Importing/exporting a Modbus slave configuration Replacing a periodic input data element Changing the Periodic Data Exchanged with a Modbus SlaveReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway Configuring the Gateway IW4.0.17 IW4.0.16IW4.0.18 IW4.0.19Configuring the Gateway Configuring the Gateway Configuring the Gateway Configuring the Gateway QW4.0.16 Deleting Aperiodic Parameter DataQW4.0.17 Configuring the Gateway Configuring the Gateway Managing the downstream Changing the name of a Modbus slave Changing a Modbus Slave ConfigurationChanging the Address of a Modbus slave With the TeSys U Motor Starters Adding and Setting Up a Modbus CommandModbus response Name of the Modbus command Modbus queryWith a Generic Modbus Slave CPU stop/failure LUFP7 gateway Profibus-DP Modbus RTU Configuration Description Element Configuring the QueryConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Configuring the Content of the Query Frame Field Size Description Frame Configuring the Content of the Response Frame Mode. The default value, CRC, should not be changedStart byte fields Modbus Commands Based on Standard Commands Adding a Special Modbus CommandModbus Commands which Can Be Completely Changed by the User Fieldbus Element Configuring the General Characteristics of the GatewayABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Communication Characteristics Appendix a Technical CharacteristicsEnvironment Communications between other stations Performance Results Inputs General data Appendix B LUFP7 Gateway GSD File GSD File ContentIdentification Number Identification number Name of the related GSD fileMaximum response time of the gateway Input Appendix C Default Configuration 16#10 Configuring Modbus Exchanges16#06 Service Address Size Description Content of the Gateway’s Dpram MemoryInput Data Memory Area Output Data Memory Area Overview of the LUFP7 Tutorial Example Appendix D Sample Use under PL7 PROLUFP7 Gateway Initialization and Diagnostics See note Controlling and Supervising the 8 TeSys U Motor Starters IEC61915 command registerTeSys U status register IEC61915 Reading and Writing any TeSys U Motor Starter Parameter Appendix D Sample Use under PL7 PRO Appendix D Sample Use under PL7 PRO Gateway Profibus-DP Diagnostics Appendix E Profibus-DP Data and DiagnosticsBytes Structure Description Bytes Name Description Gateway Configuration DataBytes Name Value General Gateway Information108 Appendix F Modbus Commands Preset Single Register Command 16#06 Read Holding Registers Command 16#03Frame Field Value or properties Modbus Protocol Exception Responses Preset Multiple Registers Command 16#10Code Name Description of the exception Exception LUFP7 Quantum Appendix F Concept and Quantum PLCLeft intentionally blank 114 Page User’s Manual LUFP7 V1.1 2003-05