6. Configuring the Gateway

In this case, all you have to do is add an “INPUT: 4 Byte (2 word)” module after the module configured for the gateway, as the number of input bytes in the default configuration is even (word-aligned).

Under SyCon, all the configured modules start from an even address (word-aligned). When you change a configuration that includes a one-byte module, you must remove it (“Remove module” button or double-click on the module in the list of configured modules, see page 65) before adding “IN/OUT”, “INPUT” and “OUTPUT” modules to the list of configured modules. This type of module should therefore only be at the end of the list.

N.B. Removing the 2 output bytes located at addresses 16#0208 and 16#0209 in the gateway memory has no impact on the overall size of the input data transmitted to the Profibus-DP coupler. These bytes become "Free memory locations", like the byte at address 16#0012.

In this example, the modules configured for the gateway are listed on the right.

Then you should save and export the configuration of the Profibus-DP network, as described in chapter 4.2.7 Saving and Exporting the Profibus-DP Network Configuration, page 31.

7)Configuring the Profibus-DP master PLC outputs: under PL7 PRO, import the new configuration of the Profibus-DP network (see chapter 4.2.8 Importing the Configuration of the Profibus-DP Network under PL7 PRO and following chapters, from page 31). Words %QW4.0.16 and %QW4.0.17 are now displayed in the "PROFIBUS-DP slave data” frame of the TSX PBY 100 coupler configuration window, providing that the address 2 station is selected in the list of the “PROFIBUS-DP slave configuration” frame.

We get the correspondence represented on the next page, derived from the one used for the gateway default configuration. The changes in relation to the default configuration are shown by a greyed-out background, like the “free memory locations”.

63

Image 62
Contents LUFP7 Page LUFP9 Page Table of Contents Introduction Introduction to the User GuideIntroduction to the LUFP7 Gateway TerminologyNotational Conventions DPM1Profibus-DP Master Upstream network Profibus-DP Additional DocumentationIntroduction to the Communication System Architecture ModbusPrinciple Used to Configure and Operate the LUFP7 Gateway ABC Configurator Modbus NetworkProfibus-DP LUFP7 gatewayHilscher On Receipt Configuration Modbus RTUHardware Implementation of the LUFP7 Gateway Mounting the gateway Powering the GatewayMounting the Gateway on a DIN Rail Examples of Modbus Connection Topologies Connecting the Gateway to the Modbus NetworkLU9GC03 LUFP7 Gateway TSXCSA00 Pin OutsHubs, drops, taps, and line terminations Wiring Recommendations for the Modbus Network120 Ω Cables Connecting the LUFP7 gateway to the Profibus-DP NetworkNAD 911 04/03 connector Point SUB-D male Pin Outs LUFP7 plug --- 9-point SUB-D femaleWiring Recommendations for the Profibus-DP Network GNDNAD 911 04 or 03 connector No Internal Line Termination Address = Configuring the Profibus-DP Communication FeaturesEncoding the Gateway Address Signalling System Architecture Software Implementation of the GatewayIntroduction Profibus-DPManaging Degraded Modes Configuring the Motor StartersModbus Cycle Time Gateway Configuration under PL7 PRO and SyCon Setting Up the Hardware Configuration under PL7 PROCreating a Profibus-DP Network under SyCon Selecting and Adding the Profibus-DP Master StationSetting up the Gateway Description Files Editing and Configuring the Gateway Selecting and Adding the Gateway to the Profibus-DP NetworkSoftware Implementation of the Gateway Optional Saving and Exporting the Profibus-DP Network ConfigurationDiagnostic length Possible valuesConfiguring the Gateway I/O under PL7 PRO IW4.0 Service PLC input DescriptionService PLC output Description IW4.0.1Description of Services Assigned to Gateway Inputs/Outputs Sample reading of a motor starter parameterAllocating Symbols to the Gateway Inputs and Outputs Using and Monitoring the TSX PBY 100 Coupler Configuration Developing a Profibus-DP ApplicationFull Management Gateway Initialization and DiagnosticsDisabled 5.3.2 Profibus-DP Master Control Word Control/Status Byte fieldProfibus-DP Master Control Word Fbdu Modbus exchange startup ED Error data item associated with the Modbus network Bits Description Abchssend New gateway diagnostic11EC Error code associated with the Modbus network Gateway Status WordDiagnostic Only Description of the errorBits Description Abcdu Modbus exchanges activated Simplified Operation Configuring the Gateway Connecting the Gateway to the Configuration PCGND RS-232 Link ProtocolInstalling AbcConf Importing the Gateway ConfigurationTransferring a Configuration to the Gateway Monitoring the Content of the Gateway’s MemoryConfiguring the Gateway Procedure for deleting a Modbus slave Deleting a Modbus SlaveAdding a new type of Modbus slave Copying a previously configured Modbus slaveAdding a Modbus Slave Importing/exporting a Modbus slave configuration Changing the Periodic Data Exchanged with a Modbus Slave Replacing a periodic input data elementReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway Configuring the Gateway IW4.0.18 IW4.0.16IW4.0.17 IW4.0.19 Configuring the Gateway Configuring the Gateway Configuring the Gateway Configuring the Gateway QW4.0.17 Deleting Aperiodic Parameter DataQW4.0.16 Configuring the Gateway Configuring the Gateway Managing the downstream Changing the Address of a Modbus slave Changing a Modbus Slave ConfigurationChanging the name of a Modbus slave Adding and Setting Up a Modbus Command With the TeSys U Motor StartersName of the Modbus command Modbus query Modbus responseWith a Generic Modbus Slave CPU stop/failure LUFP7 gateway Profibus-DP Modbus RTU Configuring the Query Configuration Description ElementConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Configuring the Content of the Query Frame Field Size Description Frame Mode. The default value, CRC, should not be changed Configuring the Content of the Response FrameStart byte fields Modbus Commands which Can Be Completely Changed by the User Adding a Special Modbus CommandModbus Commands Based on Standard Commands Configuring the General Characteristics of the Gateway Fieldbus ElementABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Environment Appendix a Technical CharacteristicsCommunication Characteristics Communications between other stations Performance Results Inputs General data Identification Number GSD File ContentAppendix B LUFP7 Gateway GSD File Identification number Name of the related GSD fileMaximum response time of the gateway Input Appendix C Default Configuration 16#06 Configuring Modbus Exchanges16#10 Input Data Memory Area Content of the Gateway’s Dpram MemoryService Address Size Description Output Data Memory Area Appendix D Sample Use under PL7 PRO Overview of the LUFP7 Tutorial ExampleLUFP7 Gateway Initialization and Diagnostics See note TeSys U status register IEC61915 IEC61915 command registerControlling and Supervising the 8 TeSys U Motor Starters Reading and Writing any TeSys U Motor Starter Parameter Appendix D Sample Use under PL7 PRO Appendix D Sample Use under PL7 PRO Bytes Structure Description Appendix E Profibus-DP Data and DiagnosticsGateway Profibus-DP Diagnostics Gateway Configuration Data Bytes Name DescriptionGeneral Gateway Information Bytes Name Value108 Appendix F Modbus Commands Frame Field Value or properties Read Holding Registers Command 16#03Preset Single Register Command 16#06 Preset Multiple Registers Command 16#10 Modbus Protocol Exception ResponsesCode Name Description of the exception Exception Appendix F Concept and Quantum PLC LUFP7 QuantumLeft intentionally blank 114 Page User’s Manual LUFP7 V1.1 2003-05