5. Gateway Initialization and Diagnostics

Bits

Description

13ABC_DU: Modbus exchanges activated

The gateway activates this bit to tell the Profibus-DP master that the Modbus data located in its input memory area have all been updated at least once since the last activation of FB_DU (“ABC_DU” means “ABC – Data Updated”). These Modbus input data include every data in responses from all Modbus slaves, for both periodic commands and aperiodic commands.

This bit is deactivated by the gateway when the FB_DU bit is deactivated, that is to say when the Profibus-DP master demands a shutdown of Modbus exchanges.

N.B. Once it is active, this bit is not deactivated if there are any communication errors with the Modbus slaves. To signal this type of error, the gateway uses bit 12 of its status word.

12Periodicity of Modbus exchanges

The gateway activates this bit provided that it is periodically communicating with all of the Modbus slaves. It deactivates it as soon as it loses communication with one of them.

The “Reconnect time (10ms)”, “Retries” and “Timeout time (10ms)” elements of each of the Modbus queries (see chapter 6.11.2.2 Configuring the Query, page 72) are used to determine whether communication is lost, then restored.

N.B. If a number of periodic exchanges are configured for the same Modbus slave, only one of them needs to remain active for the periodic communications with this slave to be declared active.

8-11EC: Error code associated with the Modbus network

Code of the error detected on the Modbus network by the gateway and transmitted to the Profibus- DP master.

0- 7 ED: Error data item associated with the Modbus network

Data item associated with the EC error code.

The correct use of this status word by the Profibus-DP master, to read a diagnostic generated by the gateway, goes through the following steps:

Checking of (ABC_HS_SEND ≠ FB_HS_CONFIRM).

 Reading of the value of ABC_DU to determine whether all of the Modbus input data are up-to-date.

 Reading of the value of the “Periodicity of Modbus exchanges” bit to determine whether the periodicity of the Modbus communications has been maintained.

 Reading of the values of EC and ED to check for any error detected by the gateway on the Modbus network (see table page 41).

 Copying of the value of the ABC_HS_SEND bit to the FB_HS_CONFIRM bit.

This last step is essential because it allows the gateway to transmit a future diagnostic in order not to “loose” any further error reporting! Even if you do not wish to read the content of the gateway’s status word, it is preferable to automate this step in your Profibus-DP master software.

43

Image 42
Contents LUFP7 Page LUFP9 Page Table of Contents Introduction Introduction to the User GuideIntroduction to the LUFP7 Gateway TerminologyNotational Conventions DPM1Profibus-DP Master Upstream network Profibus-DP Additional DocumentationIntroduction to the Communication System Architecture ModbusPrinciple Used to Configure and Operate the LUFP7 Gateway ABC Configurator Modbus NetworkLUFP7 gateway HilscherProfibus-DP Configuration Modbus RTU Hardware Implementation of the LUFP7 GatewayOn Receipt Powering the Gateway Mounting the Gateway on a DIN RailMounting the gateway Connecting the Gateway to the Modbus Network LU9GC03Examples of Modbus Connection Topologies LUFP7 Gateway TSXCSA00 Pin OutsWiring Recommendations for the Modbus Network 120 ΩHubs, drops, taps, and line terminations Cables Connecting the LUFP7 gateway to the Profibus-DP NetworkNAD 911 04/03 connector Point SUB-D male Pin Outs LUFP7 plug --- 9-point SUB-D femaleWiring Recommendations for the Profibus-DP Network GNDNAD 911 04 or 03 connector Configuring the Profibus-DP Communication Features Encoding the Gateway AddressNo Internal Line Termination Address = Signalling System Architecture Software Implementation of the GatewayIntroduction Profibus-DPConfiguring the Motor Starters Modbus Cycle TimeManaging Degraded Modes Gateway Configuration under PL7 PRO and SyCon Setting Up the Hardware Configuration under PL7 PROCreating a Profibus-DP Network under SyCon Selecting and Adding the Profibus-DP Master StationSetting up the Gateway Description Files Editing and Configuring the Gateway Selecting and Adding the Gateway to the Profibus-DP NetworkSoftware Implementation of the Gateway Optional Saving and Exporting the Profibus-DP Network ConfigurationDiagnostic length Possible valuesConfiguring the Gateway I/O under PL7 PRO IW4.0 Service PLC input DescriptionService PLC output Description IW4.0.1Description of Services Assigned to Gateway Inputs/Outputs Sample reading of a motor starter parameterAllocating Symbols to the Gateway Inputs and Outputs Using and Monitoring the TSX PBY 100 Coupler Configuration Developing a Profibus-DP ApplicationFull Management Gateway Initialization and DiagnosticsDisabled 5.3.2 Profibus-DP Master Control Word Control/Status Byte fieldProfibus-DP Master Control Word Fbdu Modbus exchange startup ED Error data item associated with the Modbus network Bits Description Abchssend New gateway diagnostic11EC Error code associated with the Modbus network Gateway Status WordDiagnostic Only Description of the errorBits Description Abcdu Modbus exchanges activated Simplified Operation Configuring the Gateway Connecting the Gateway to the Configuration PCGND RS-232 Link ProtocolInstalling AbcConf Importing the Gateway ConfigurationTransferring a Configuration to the Gateway Monitoring the Content of the Gateway’s MemoryConfiguring the Gateway Procedure for deleting a Modbus slave Deleting a Modbus SlaveCopying a previously configured Modbus slave Adding a Modbus SlaveAdding a new type of Modbus slave Importing/exporting a Modbus slave configuration Changing the Periodic Data Exchanged with a Modbus Slave Replacing a periodic input data elementReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway Configuring the Gateway IW4.0.18 IW4.0.16IW4.0.17 IW4.0.19Configuring the Gateway Configuring the Gateway Configuring the Gateway Configuring the Gateway Deleting Aperiodic Parameter Data QW4.0.16QW4.0.17 Configuring the Gateway Configuring the Gateway Managing the downstream Changing a Modbus Slave Configuration Changing the name of a Modbus slaveChanging the Address of a Modbus slave Adding and Setting Up a Modbus Command With the TeSys U Motor StartersName of the Modbus command Modbus query Modbus responseWith a Generic Modbus Slave CPU stop/failure LUFP7 gateway Profibus-DP Modbus RTU Configuring the Query Configuration Description ElementConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Configuring the Content of the Query Frame Field Size Description Frame Mode. The default value, CRC, should not be changed Configuring the Content of the Response FrameStart byte fields Adding a Special Modbus Command Modbus Commands Based on Standard CommandsModbus Commands which Can Be Completely Changed by the User Configuring the General Characteristics of the Gateway Fieldbus ElementABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Appendix a Technical Characteristics Communication CharacteristicsEnvironment Communications between other stations Performance Results Inputs General data Identification Number GSD File ContentAppendix B LUFP7 Gateway GSD File Identification number Name of the related GSD fileMaximum response time of the gateway Input Appendix C Default Configuration Configuring Modbus Exchanges 16#1016#06 Content of the Gateway’s Dpram Memory Service Address Size DescriptionInput Data Memory Area Output Data Memory Area Appendix D Sample Use under PL7 PRO Overview of the LUFP7 Tutorial ExampleLUFP7 Gateway Initialization and Diagnostics See note IEC61915 command register Controlling and Supervising the 8 TeSys U Motor StartersTeSys U status register IEC61915 Reading and Writing any TeSys U Motor Starter Parameter Appendix D Sample Use under PL7 PRO Appendix D Sample Use under PL7 PRO Appendix E Profibus-DP Data and Diagnostics Gateway Profibus-DP DiagnosticsBytes Structure Description Gateway Configuration Data Bytes Name DescriptionGeneral Gateway Information Bytes Name Value108 Appendix F Modbus Commands Read Holding Registers Command 16#03 Preset Single Register Command 16#06Frame Field Value or properties Preset Multiple Registers Command 16#10 Modbus Protocol Exception ResponsesCode Name Description of the exception Exception Appendix F Concept and Quantum PLC LUFP7 QuantumLeft intentionally blank 114 Page User’s Manual LUFP7 V1.1 2003-05