Page 57

6. Configuring the Gateway

Under SyCon, all the configured modules start from an even address (word-aligned). When you change a configuration that includes a one-byte module, you must remove it (“Remove module” button or double-click on the module in the list of configured modules, see page 65) before adding “IN/OUT”, “INPUT” and “OUTPUT” modules to the list of configured modules. This type of module should therefore only be at the end of the list.

N.B. removing the 2 input bytes located at addresses 16#0004 and 16#0005 in the gateway memory has no impact on the overall size of the input data transmitted to the Profibus-DP coupler. These bytes become "Free memory locations", like the byte at address 16#0012.

In this example, the modules configured for the gateway are listed on the right.

Then you should save and export the configuration of the Profibus-DP network, as described in chapter 4.2.7 Saving and Exporting the Profibus-DP Network Configuration, page 31.

7)Configuring the Profibus-DP master PLC inputs: under PL7 PRO, import the new configuration of the Profibus-DP network (see chapter 4.2.8 Importing the Configuration of the Profibus-DP Network under PL7 PRO and following chapters, from page 31). Words %IW4.0.16 to %IW4.0.23 are now displayed in the "PROFIBUS-DP slave data” frame of the TSX PBY 100 coupler configuration window, providing that the address 2 station is selected in the list of the “PROFIBUS-DP slave configuration” frame.

We get the correspondence represented on the next page, derived from the one used for the gateway default configuration. The changes in relation to the default configuration are shown by a greyed-out background, like the “free memory locations”.

58

Image 57
Contents LUFP7 Page LUFP9 Page Table of Contents Introduction to the User Guide IntroductionTerminology Introduction to the LUFP7 GatewayDPM1 Notational ConventionsIntroduction to the Communication System Architecture Additional DocumentationProfibus-DP Master Upstream network Profibus-DP ModbusPrinciple Used to Configure and Operate the LUFP7 Gateway Modbus Network ABC ConfiguratorLUFP7 gateway HilscherProfibus-DP Configuration Modbus RTU Hardware Implementation of the LUFP7 GatewayOn Receipt Powering the Gateway Mounting the Gateway on a DIN RailMounting the gateway Connecting the Gateway to the Modbus Network LU9GC03Examples of Modbus Connection Topologies LUFP7 Gateway Pin Outs TSXCSA00Wiring Recommendations for the Modbus Network 120 ΩHubs, drops, taps, and line terminations NAD 911 04/03 connector Point SUB-D male Connecting the LUFP7 gateway to the Profibus-DP NetworkCables Pin Outs LUFP7 plug --- 9-point SUB-D femaleGND Wiring Recommendations for the Profibus-DP NetworkNAD 911 04 or 03 connector Configuring the Profibus-DP Communication Features Encoding the Gateway AddressNo Internal Line Termination Address = Signalling Introduction Software Implementation of the GatewaySystem Architecture Profibus-DPConfiguring the Motor Starters Modbus Cycle TimeManaging Degraded Modes Setting Up the Hardware Configuration under PL7 PRO Gateway Configuration under PL7 PRO and SyConSelecting and Adding the Profibus-DP Master Station Creating a Profibus-DP Network under SyConSetting up the Gateway Description Files Selecting and Adding the Gateway to the Profibus-DP Network Editing and Configuring the GatewaySoftware Implementation of the Gateway Diagnostic length Saving and Exporting the Profibus-DP Network ConfigurationOptional Possible valuesConfiguring the Gateway I/O under PL7 PRO Service PLC output Description Service PLC input DescriptionIW4.0 IW4.0.1Sample reading of a motor starter parameter Description of Services Assigned to Gateway Inputs/OutputsAllocating Symbols to the Gateway Inputs and Outputs Developing a Profibus-DP Application Using and Monitoring the TSX PBY 100 Coupler ConfigurationDisabled 5.3.2 Profibus-DP Master Control Word Gateway Initialization and DiagnosticsFull Management Control/Status Byte fieldProfibus-DP Master Control Word Fbdu Modbus exchange startup 11EC Error code associated with the Modbus network Bits Description Abchssend New gateway diagnosticED Error data item associated with the Modbus network Gateway Status WordDescription of the error Diagnostic OnlyBits Description Abcdu Modbus exchanges activated Simplified Operation Connecting the Gateway to the Configuration PC Configuring the GatewayRS-232 Link Protocol GNDImporting the Gateway Configuration Installing AbcConfMonitoring the Content of the Gateway’s Memory Transferring a Configuration to the GatewayConfiguring the Gateway Deleting a Modbus Slave Procedure for deleting a Modbus slaveCopying a previously configured Modbus slave Adding a Modbus SlaveAdding a new type of Modbus slave Importing/exporting a Modbus slave configuration Replacing a periodic input data element Changing the Periodic Data Exchanged with a Modbus SlaveReplacing an Output Periodic Data Element Increasing the Amount of Periodic Input Data Configuring the Gateway Configuring the Gateway Configuring the Gateway IW4.0.17 IW4.0.16IW4.0.18 IW4.0.19Configuring the Gateway Configuring the Gateway Configuring the Gateway Configuring the Gateway Deleting Aperiodic Parameter Data QW4.0.16QW4.0.17 Configuring the Gateway Configuring the Gateway Managing the downstream Changing a Modbus Slave Configuration Changing the name of a Modbus slaveChanging the Address of a Modbus slave With the TeSys U Motor Starters Adding and Setting Up a Modbus CommandModbus response Name of the Modbus command Modbus queryWith a Generic Modbus Slave CPU stop/failure LUFP7 gateway Profibus-DP Modbus RTU Configuration Description Element Configuring the QueryConfiguring the Gateway Default communication mode. The query is transmitted Configuring the Response Configuring the Content of the Query Frame Field Size Description Frame Configuring the Content of the Response Frame Mode. The default value, CRC, should not be changedStart byte fields Adding a Special Modbus Command Modbus Commands Based on Standard CommandsModbus Commands which Can Be Completely Changed by the User Fieldbus Element Configuring the General Characteristics of the GatewayABC Element Sub-Network Element Configuring the Gateway Adding a Broadcaster Node Appendix a Technical Characteristics Communication CharacteristicsEnvironment Communications between other stations Performance Results Inputs General data Appendix B LUFP7 Gateway GSD File GSD File ContentIdentification Number Identification number Name of the related GSD fileMaximum response time of the gateway Input Appendix C Default Configuration Configuring Modbus Exchanges 16#1016#06 Content of the Gateway’s Dpram Memory Service Address Size DescriptionInput Data Memory Area Output Data Memory Area Overview of the LUFP7 Tutorial Example Appendix D Sample Use under PL7 PROLUFP7 Gateway Initialization and Diagnostics See note IEC61915 command register Controlling and Supervising the 8 TeSys U Motor StartersTeSys U status register IEC61915 Reading and Writing any TeSys U Motor Starter Parameter Appendix D Sample Use under PL7 PRO Appendix D Sample Use under PL7 PRO Appendix E Profibus-DP Data and Diagnostics Gateway Profibus-DP DiagnosticsBytes Structure Description Bytes Name Description Gateway Configuration DataBytes Name Value General Gateway Information108 Appendix F Modbus Commands Read Holding Registers Command 16#03 Preset Single Register Command 16#06Frame Field Value or properties Modbus Protocol Exception Responses Preset Multiple Registers Command 16#10Code Name Description of the exception Exception LUFP7 Quantum Appendix F Concept and Quantum PLCLeft intentionally blank 114 Page User’s Manual LUFP7 V1.1 2003-05