5. Gateway Initialization and Diagnostics
The values of the EC and ED fields are described in the table below:
EC | Description of the error | ED | Notes |
2#0000 | Number of re- | Total number of | |
| Modbus network | transmissions (1) | on the |
2#0001 | A Modbus slave is missing | Address of the missing | — |
|
| Modbus slave |
|
2#0010 | Several Modbus slaves | — | — |
| are missing |
|
|
2#0011 | Excessive data in a | Address of the Modbus | This error occurs when the gateway receives too |
| Modbus response | slave involved | much data in the response sent by one of its |
|
|
| Modbus slaves. |
2#0100 | Unknown Modbus error | Address of the Modbus | — |
|
| slave involved |
|
(1)The
In the case of
5.3. Diagnostic Only
The gateway uses a
So you must configure your
5.3.1. Gateway Status Word
The input word located at addresses 16#0000 (MSB) and 16#0001 (LSB) in the gateway’s input memory constitutes the gateway’s status word. Its structure is described below:
Bits Description
15ABC_HS_SEND: New gateway diagnostic
(See description of bit 15 of the
14 | Reserved. |
42