Bosch Appliances ICP-CC488 Codepad Panic Report, Codepad Fire Report, Codepad Medical Report

Page 106

ICP-CC488 Installation Guide 25.0

Programming Sheets

 

 

EN 106

Codepad Panic Report

Location

405 to 406

Refer to page 67

Default

7 15

 

 

 

Codepad Fire Report

Location

407 to 408

Refer to page 68

Default

7 14

Codepad Medical Report

Location

409 to 410

Refer to page 68

Default

7 13

 

 

 

Codepad Reporting Options

Location

411

Refer to page 68

0

No report required

 

 

 

 

1

Receiver 1

 

2

Receiver 2

 

4

Receiver 1 and 2

 

8

Receiver 2 only when Receiver 1 fails

System Status – AUX Power Supply Fail Report

Location

412 to 413

Refer to page 68

Default

10 3

System Status – AUX Power Supply Fail Restore Report

Location

414 to 415

Refer to page 68

Default

10 8

System Status – AC Fail Report

Location

416 to 417

Refer to page 68

Default

10 2

 

 

 

System Status – AC Fail Restore Report

Location

418 to 419

Refer to page 68

Default

10 7

System Status – Low Battery Report

Location

420 to 421

Refer to page 69

Default

10 1

 

 

 

System Status – Low Battery Restore Report

Location

422 to 423

Refer to page 69

Default

10 6

System Status – Access Denied

Location

424 to 426

Refer to page 69

Default

 

6 7 12

Location 424

Code retries

 

Location 425

Reporting code – tens digit

Location 426

Reporting code – units digit

System Status Reporting Options

Location

427

Refer to page 69

0

No report required

 

1

Receiver 1

 

2

Receiver 2

 

4

Receiver 1 and 2

 

8

Receiver 2 only when Receiver 1 fails

Test Reporting Time

Location

 

428 to 434

 

Refer to page 69

Default

 

0

0 0

0 7 1 0

Location 428

Hour of the day – tens digit

 

Location 429

Hour of the day – units digit

 

Location 430

Minute of the day – tens digit

Location 431

Minute of the day – units digit

Location 432

Test Report code – tens digit

Location 433

Test Report code – units digit

Location 434

Repeat interval in days

 

 

Test Reporting Dialer Options

Location

 

435

 

Refer to page 70

0No report required

1 Receiver 1

2 Receiver 2

4 Receiver 1 and 2

8 Receiver 2 only when Receiver 1 fails

Output Configurations

Location

 

436 to 465

 

 

Refer to page 70

Output 1

 

Locations 436 to 441

Default for horn speaker

 

 

1

14

0

0

0

0

Output 2

 

Locations 442 to 447

Default for Fire Alarm

 

 

2

7 10

2

1

5

verification

 

 

 

 

 

 

 

 

Strobe

 

Locations 444 to 453

Default for strobe (reset in 8 hr)

 

2 0

6

4

0

8

Relay

 

Locations 454 to 459

Default for sirens running

 

 

1

15

1

0

0

0

Codepad

 

Locations 460 to 465

Default for entry/Exit Warning

0 13

2

1

0 1

and Delay Alarm

 

 

 

 

 

 

 

 

Outputs are programmed with four parameters in six locations:

Event Type

Polarity

Time Base

Time Multiplier

 

 

 

 

 

 

Entry Time 1

Location

 

466 to 467

 

Refer to page 78

Default

 

4 1

Location 466

Increments of 1 sec (0 to 15 sec)

Location 467

Increments of 16 sec (0 to 240 sec)

 

 

 

 

 

 

Entry Time 2

Location

 

468 to 469

 

Refer to page 78

Default

 

8 2

Location 468

Increments of 1 sec (0 to 15 sec)

Location 469

Increments of 16 sec (0 to 240 sec)

Exit Time

Location

 

470 to 471

 

Refer to page 78

Default

 

12 3

Location 470

Increments of 1 sec (0 to 15 sec)

Location 471

Increments of 16 sec (0 to 240 sec)

 

 

 

 

 

 

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 106
Contents Installation Guide ICP-CC488Copyright Notice ICP-CC488 Installation Guide NoticesBosch Security Systems, Inc /08 F01U089457-02 Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Figures TablesUser Code Allocations Hexadecimal Values for Zone Nos ICP-CC488 Installation Guide Introduction ICP-CC488 FeaturesIntroduction Quick Start ICP-CC488 Zone DefaultsZone Defaults for the ICP-CC488 Set the Date and TimeICP-CC488 Installation Guide Codepad Indicators Codepad IndicatorsICP-CP508W Eight Zone LED Codepad Audible Indicators Mains IndicatorFault indicator ICP-CP508LW Eight Zone LCD CodepadICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads Arming the System in Stay Mode Arming the System in Away ModeDisarming the System from Away Mode ICP-CC488 Installation Guide System OperationsDisarming the System from Stay Mode Codepad Duress Alarm Codepad Panic AlarmIsolating Zones Codepad Fire AlarmCodepad Medical Alarm Standard IsolatingFault Analysis Mode Fault DescriptionsSystem Fault indicators AC Mains FailureFault Analysis Conditions Remote Radio Transmitter OperationsRemote Radio User Code Priority Levels Indications from Remote Radio Transmitter OperationsChanging or Deleting Remote Radio User Codes Installer Code Functions Installer Code FunctionsICP-CC488 Installation Guide System Functions Add or Delete RF Wireless DevicesChange Domestic Phone Numbers Set the Number of Days until the First Test ReportDomestic Dialing Digits Change Telco Arm/Disarm Sequence Codepad Indicators When Changing Phone NumbersExamples provided for this feature apply only to Australia Telco Arm SequenceSatellite Siren Service Mode Setting Stay Mode 2 ZonesTurning Telephone Monitor Mode On and Off Event Sequence Telephone Monitor Mode IndicationsEvent Memory Recall Mode Event Memory PlaybackArm or Disarm Both Areas at the Same Time Master Code FunctionsMaster Code Functions Changing and Deleting User CodesChanging and Deleting Remote Radio User Codes User Numbers Displayed by the Codepad IndicatorsChanging Domestic Phone Numbers Codepad Indicators When Changing Domestic Telephone Numbers When you program a # in the telco arm sequence, enter STAY2 Turning Outputs On/OffSetting the Date and Time Event Non-volatile Memory Recall ModeUser Code Functions Arm the System in Away ModeArm the System in Stay Mode Hold-Down FunctionsReset Latching Outputs Turning Day Alarm On and OffFault Analysis Mode Horn Speaker TestProgramming ICP-CC488 Installation Guide Remote Arming by TelephoneRemote Arming by Telephone Programming with the Remote CodepadCodepad Indicators ICP-CC488 Installation Guide ProgrammingProgramming with the Programming Key Command 959 Test the Programming Key Installer’s Programming CommandsInstaller’s Programming Mode Commands Programming Option BitsCommand 960 Exit from Installers Programming Mode Command 963 Copy the Programming Key to the Control PanelCommand 964 Erase the Programming Key Command 965 Set Up Domestic Dialing FormatExample Auto Step Disabled Disable Factory DefaultsExample Auto Step Enabled Command 965 DefaultsRemote Connect Alarm Link SoftwareICP-CC488 Installation Guide Alarm Link Software Remote Connection with Customer ControlAlarm Link Options Terminate Alarm Link Connection on Alarm ICP-CC488 Installation Guide Domestic DialingEnable Alarm Link Call Back Domestic DialingDialer Reporting Formats Setting Up and Programming Domestic ReportingICP-CC488 Installation Guide Dialer Reporting Formats Transmission Formats10.1.4 4 + 2 Reporting Format Contact ID Format BreakdownPoint ID Codes Example Reporting in 4 + 2 Format + 2 Reporting Format+ 2 Transmission Code Descriptions Basic Pager Reporting Format14.3.2 Basic Pager Display Dialer Information ICP-CC488 Installation Guide Dialer InformationBasic Pager Display Information Handshake Tone for Receiver 1 and Receiver Primary Telephone Number for Receiver 1 and ReceiverSecondary Telephone Number for Receiver 1 and Receiver Dialing DigitsDialing Format Transmission Format for Receiver 1 and ReceiverSubscriber ID Number for Receiver 1 and Receiver Telco Arming SequenceRing Count Telco Disarming SequenceCall Back Telephone Number Answering Machine BypassDialer Options Telephone Line Fault OptionsICP-CC488 Installation Guide Dialer Options Dialer OptionsOpen/Close Reports Only if Previous Alarm Answering Machine Bypass Only When ArmedUse Bell 103 for FSK Format Disabled=CCITT V21 Open/Close Reports for Stay Mode 1 and Stay ModeICP-CC488 Installation Guide Access Codes Access CodesInstaller Code User CodesArm/Disarm User Code PriorityPriority Levels Arm OnlyZone Information Day Alarm InformationICP-CC488 Installation Guide Zone Information EOL Resistor ValueTamper Zone 1 3K3 Zone 5 6K8 Zone Options Zone ProgrammingZone Operating Information Zone Reporting InformationYou can program Zones 1 to 16 as any zone type Keyswitch Zone Delay-1 ZoneDelay-2 Zone Instant ZoneZone Not Used 13 24-Hour Fire ZoneChime Zone Zone Pulse CountKeyswitch Zone Options Delay Alarm ReportingSilent Alarm Latching Arm and Disarm in Away ModeMomentary Arm and Disarm in Away Mode Latching Arm in Stay ModeLatching Disarm from Stay Mode 1 or Stay Mode Momentary Arm in Away ModeSwinger Shutdown Count for Siren Swinger Shutdown Count for DialerZone Status Walk Test Report System Reporting InformationZone Status Zone Tamper Report Zone Status Bypass ReportsZone Status Sensor Watch Reports Zone Status Alarm Restore CodeRF Low Battery Report Zone Status Reporting OptionsOpen/Close Reports RF Receiver Trouble Restore ReportRF Dialer Options Open/Close Reporting OptionsSystem Status AC Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report Codepad Fire ReportSystem Status Access Denied System Status Low Battery ReportSystem Status Low Battery Restore Report System Status Reporting OptionsProgrammable Outputs ICP-CC488 Installation Guide Programmable OutputsTest Reporting Dialer Options Redirecting Outputs to the Codepad Buzzer Output Event TypesDay Alarm Enabled Entry Warning + Day Alarm ResettingExit Warning + Entry Warning + Day Alarm Resetting AUX Power Supply FailCodepad Fire Alarm Sensor Watch AlarmCodepad Medical Alarm Codepad Panic AlarmRadio Control Output 1 Not in Away Mode Fire Alarm VerificationRemote Control Radio Control Output 2 Not in Away ModeGlobal Chime Area 1 in Alarm Area 2 in AlarmMimic Zone Zone Not SealedOutput Polarity Output Timing System Event TimersICP-CC488 Installation Guide System Event Timers Pulsing PolaritiesExit Timer Programming Entry/Exit TimersEntry Timer Entry Guard Timer for Stay ModeSiren Run Time Auto Arming Pre-Alert TimerCodepad Lockout Time Siren Sound RateSystem and Consumer Options Strobe Indications for Radio Arm/Disarm Assign Button 4 To Operate Stay ModeAccess Denied Code Retries To Be Silent Codepad Panic To Be SilentConsumer Options Radio Input Options Partitioning Using Codepads in a Partitioned SystemICP-CC488 Installation Guide Partitioning 19.1 CP500 Master Partitioned LED CodepadZone Allocations Zone Allocations for Areas 1 Setting Up and Programming Codepads for PartitioningUser Code Allocations Detailed ExampleSetting Up an Area 2 Codepad Setting Up an Area 1 Codepad as the Main CodepadSetting Up an Area 1 Codepad Codepad Connections For Partitioning ExamplesRF Information ICP-CC488 Installation Guide RF InformationRF Option Bit Using Hexadecimal Values for RF Device Mapping Default RF Device Mapping Devices 1 toDefault RF Device Mapping Devices 9 to Enable RF Jamming MonitorICP-CC488 Installation Guide Optional Equipment RF Device Signal Strength Devices 1 to 8 Read OnlyRF Device Signal Strength Devices 9 to 16 Read Only Optional Equipment21.4 CC891 Programming Key 21.5 CC816 Alarm Link Software21.3 SS914 Edmsat Satellite Siren ICP-CP500AW Eight Zone Area Addressable CodepadTerminals and Descriptions ICP-CC488 Installation Guide Terminals and DescriptionsTerminal Descriptions Glossary Of Terms Stay Mode Domestic alarm reportsThat an alarm was sent out This mode. Only the installer can program these zonesDiagrams ICP-CC488 Wiring DiagramICP-CC488 Installation Guide Terminals and Descriptions Wiring and Power Up Operation Telecom Connection Diagram for AustraliaYellow wire Green wire Appendices Appendix B Test Reports Only When ArmedICP-CC488 Installation Guide Appendices Appendix a Telephone Anti JammingSpecifications SpecificationsWarranty Statement Software Version NumberTick ICP-CC488 Installation Guide Programming SheetsProgramming Sheets ICP-CC488 Programming SheetsDialing Format Telephone Line Fault OptionsAlarm Link Options ReservedUser Code Priority Levels Installer CodeDay Alarm Zones EOL Resistor ValueZone Pulse Count Settings ZonesZone Descriptions RF Low Battery ReportRF Receiver Trouble Restore Report Swinger Shutdown Count for SirenSystem Status AC Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status Low Battery ReportSpeaker Beep Volume Entry Guard Time for Stay ModeDelay Alarm Reporting Time Sensor Watch TimeZone Allocations for Area 1 and Area Zone Allocations Enabled for Area 1 and AreaRadio Input Options Domestic Telephone NumbersRF Options RF Device Signal Strength Devices 1 toRF Device Signal Strength Devices 9 to RF Device Mapping OptionSystem Time Disable Factory DefaultCountry Codes System DateICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Index Remote Connect Without Call Back Verification41Telephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02