ICP-CC488 Installation Guide 5.0

System Functions

 

 

EN 31

Example

If Output 2 is programmed as 291000 in Locations 443 to 448, the Master Code holder can turn on this output by entering:

[2 5 8 0 5][AWAY][2][AWAY][AWAY]

To turn an output off from the remote codepad:

1.Enter your Master Code and press [5][AWAY]. Three beeps sound and the STAY and AWAY indicators flash.

2.Enter the number of the output (1 to 3) and press [STAY].

Two beeps sound and the output turns off.

3.Repeat Step 2 to turn off another output.

4.Press [AWAY] button to exit from this function. Two beeps sound and the STAY and AWAY indicators are extinguished.

Example

If Output 2 is programmed as 291000 in Locations 442 to 447, the Master Code holder can turn off this output by entering:

[2 5 8 0 5][AWAY][2][STAY][AWAY]

5.2.8Setting the Date and Time

Use this function when the date and time must be changed or if the system was powered down.

If the date and time is not set, the date and time fault appears only when the Auto Arming Time is programmed in Locations 482 to 485 (refer to Section

17.12Auto Arming Time on page 79), or when you enter Fault Analysis Mode by holding down [5].

To set the new date and time:

1.Enter your Master Code and press [6][AWAY]. Three beeps sound and the STAY and AWAY indicators flash.

2.Enter the day, month, year, hour, and minute in DD, MM, YY, HH, MM format (where DD is the day of the month, MM is the month of the year, YY is the year, HH is the hour of the day, and MM is the minute of the day) and press [AWAY].

Use 24:00 hour format when programming the hour of the day.

Two beeps sound and the STAY and AWAY indicators are extinguished. If a long beep sounds, an error occurred when you entered the date and time.

Example

To set the date and time for 1st January 2009 at 10:30 PM, enter:

[2 5 8 0 6][AWAY][0 1 0 1 0 9 2 2 3 0][AWAY]

5.2.9Walk Test Mode

Walk Test Mode allows you to test detection devices to ensure that they are functioning correctly. Before activating Walk Test Mode, isolate any zones that are not required for testing. Refer to Section 3.11 Isolating Zones for more information. Use Locations 383 and 384 to enable Walk Test Mode Reports (refer to Section 15.2).

To enter Walk Test Mode:

1.Enter your Master Code and press [7][AWAY]. Three beeps sound and the STAY and AWAY indicators flash. The codepad beeps once per sec when Walk Test Mode is active.

2.Unseal and seal the zones to be tested.

The codepad sounds one long beep and the horn speaker sounds one short beep each time a zone is sealed or unsealed.

3.Press [AWAY] to exit from this function. Two beeps sound and the STAY and AWAY indicators are extinguished. The system returns to the disarmed state.

5.2.10Event Non-volatile Memory Recall Mode

This function allows you to play back the last 40 system events that occurred. Event Non-volatile Memory Recall Mode reports all alarms and each arming or disarming of the system and helps with troubleshooting system faults. The events are shown using the codepad indicators. The event memory is not lost even with the power supply off.

To enter Event Memory Recall Mode:

Enter your Master Code and press [8][AWAY]. Three beeps sound. The events are played back by the codepad indicators in reverse chronological order.

Example

If the events occurred in the following order:

Table 32: Event Sequence

Sequence Event

1System armed in AWAY Mode

2Alarm in Zone 3

3Alarm in Zone 4

4System disarmed

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 31
Contents ICP-CC488 Installation GuideCopyright Notice ICP-CC488 Installation Guide NoticesBosch Security Systems, Inc /08 F01U089457-02 Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Tables FiguresUser Code Allocations Hexadecimal Values for Zone Nos ICP-CC488 Installation Guide Introduction ICP-CC488 FeaturesIntroduction Set the Date and Time ICP-CC488 Zone DefaultsZone Defaults for the ICP-CC488 Quick StartICP-CC488 Installation Guide Codepad Indicators Codepad IndicatorsICP-CP508W Eight Zone LED Codepad ICP-CP508LW Eight Zone LCD Codepad Mains IndicatorFault indicator Audible IndicatorsICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads ICP-CC488 Installation Guide System Operations Arming the System in Away ModeDisarming the System from Away Mode Arming the System in Stay ModeDisarming the System from Stay Mode Codepad Panic Alarm Codepad Duress AlarmStandard Isolating Codepad Fire AlarmCodepad Medical Alarm Isolating ZonesFault Descriptions Fault Analysis ModeAC Mains Failure System Fault indicatorsRemote Radio Transmitter Operations Fault Analysis ConditionsRemote Radio User Code Priority Levels Indications from Remote Radio Transmitter OperationsChanging or Deleting Remote Radio User Codes Add or Delete RF Wireless Devices Installer Code FunctionsICP-CC488 Installation Guide System Functions Installer Code FunctionsChange Domestic Phone Numbers Set the Number of Days until the First Test ReportDomestic Dialing Digits Telco Arm Sequence Codepad Indicators When Changing Phone NumbersExamples provided for this feature apply only to Australia Change Telco Arm/Disarm SequenceSatellite Siren Service Mode Setting Stay Mode 2 ZonesTurning Telephone Monitor Mode On and Off Event Memory Playback Telephone Monitor Mode IndicationsEvent Memory Recall Mode Event SequenceChanging and Deleting User Codes Master Code FunctionsMaster Code Functions Arm or Disarm Both Areas at the Same TimeChanging and Deleting Remote Radio User Codes User Numbers Displayed by the Codepad IndicatorsChanging Domestic Phone Numbers Codepad Indicators When Changing Domestic Telephone Numbers Turning Outputs On/Off When you program a # in the telco arm sequence, enter STAY2Event Non-volatile Memory Recall Mode Setting the Date and TimeHold-Down Functions Arm the System in Away ModeArm the System in Stay Mode User Code FunctionsHorn Speaker Test Turning Day Alarm On and OffFault Analysis Mode Reset Latching OutputsProgramming with the Remote Codepad ICP-CC488 Installation Guide Remote Arming by TelephoneRemote Arming by Telephone ProgrammingCodepad Indicators ICP-CC488 Installation Guide ProgrammingProgramming with the Programming Key Programming Option Bits Installer’s Programming CommandsInstaller’s Programming Mode Commands Command 959 Test the Programming KeyCommand 963 Copy the Programming Key to the Control Panel Command 960 Exit from Installers Programming ModeCommand 965 Set Up Domestic Dialing Format Command 964 Erase the Programming KeyCommand 965 Defaults Disable Factory DefaultsExample Auto Step Enabled Example Auto Step DisabledRemote Connection with Customer Control Alarm Link SoftwareICP-CC488 Installation Guide Alarm Link Software Remote ConnectAlarm Link Options Domestic Dialing ICP-CC488 Installation Guide Domestic DialingEnable Alarm Link Call Back Terminate Alarm Link Connection on AlarmTransmission Formats Setting Up and Programming Domestic ReportingICP-CC488 Installation Guide Dialer Reporting Formats Dialer Reporting FormatsExample Reporting in 4 + 2 Format + 2 Reporting Format Contact ID Format BreakdownPoint ID Codes 10.1.4 4 + 2 Reporting FormatBasic Pager Reporting Format + 2 Transmission Code Descriptions14.3.2 Basic Pager Display Dialer Information ICP-CC488 Installation Guide Dialer InformationBasic Pager Display Information Dialing Digits Primary Telephone Number for Receiver 1 and ReceiverSecondary Telephone Number for Receiver 1 and Receiver Handshake Tone for Receiver 1 and ReceiverTelco Arming Sequence Transmission Format for Receiver 1 and ReceiverSubscriber ID Number for Receiver 1 and Receiver Dialing FormatAnswering Machine Bypass Telco Disarming SequenceCall Back Telephone Number Ring CountDialer Options Telephone Line Fault OptionsICP-CC488 Installation Guide Dialer Options Dialer OptionsOpen/Close Reports for Stay Mode 1 and Stay Mode Answering Machine Bypass Only When ArmedUse Bell 103 for FSK Format Disabled=CCITT V21 Open/Close Reports Only if Previous AlarmUser Codes Access CodesInstaller Code ICP-CC488 Installation Guide Access CodesArm Only User Code PriorityPriority Levels Arm/DisarmEOL Resistor Value Day Alarm InformationICP-CC488 Installation Guide Zone Information Zone InformationTamper Zone 1 3K3 Zone 5 6K8 Zone Reporting Information Zone ProgrammingZone Operating Information Zone OptionsYou can program Zones 1 to 16 as any zone type Instant Zone Delay-1 ZoneDelay-2 Zone Keyswitch ZoneZone Pulse Count 13 24-Hour Fire ZoneChime Zone Zone Not UsedLatching Arm and Disarm in Away Mode Delay Alarm ReportingSilent Alarm Keyswitch Zone OptionsMomentary Arm in Away Mode Latching Arm in Stay ModeLatching Disarm from Stay Mode 1 or Stay Mode Momentary Arm and Disarm in Away ModeSwinger Shutdown Count for Dialer Swinger Shutdown Count for SirenZone Status Bypass Reports System Reporting InformationZone Status Zone Tamper Report Zone Status Walk Test ReportZone Status Reporting Options Zone Status Alarm Restore CodeRF Low Battery Report Zone Status Sensor Watch ReportsOpen/Close Reporting Options RF Receiver Trouble Restore ReportRF Dialer Options Open/Close ReportsCodepad Fire Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportSystem Status Reporting Options System Status Low Battery ReportSystem Status Low Battery Restore Report System Status Access DeniedProgrammable Outputs ICP-CC488 Installation Guide Programmable OutputsTest Reporting Dialer Options Output Event Types Redirecting Outputs to the Codepad BuzzerAUX Power Supply Fail Entry Warning + Day Alarm ResettingExit Warning + Entry Warning + Day Alarm Resetting Day Alarm EnabledCodepad Panic Alarm Sensor Watch AlarmCodepad Medical Alarm Codepad Fire AlarmRadio Control Output 2 Not in Away Mode Fire Alarm VerificationRemote Control Radio Control Output 1 Not in Away ModeZone Not Sealed Area 1 in Alarm Area 2 in AlarmMimic Zone Global ChimeOutput Polarity Pulsing Polarities System Event TimersICP-CC488 Installation Guide System Event Timers Output TimingEntry Guard Timer for Stay Mode Programming Entry/Exit TimersEntry Timer Exit TimerSiren Sound Rate Auto Arming Pre-Alert TimerCodepad Lockout Time Siren Run TimeSystem and Consumer Options Codepad Panic To Be Silent Assign Button 4 To Operate Stay ModeAccess Denied Code Retries To Be Silent Strobe Indications for Radio Arm/DisarmConsumer Options Radio Input Options 19.1 CP500 Master Partitioned LED Codepad Using Codepads in a Partitioned SystemICP-CC488 Installation Guide Partitioning PartitioningZone Allocations Detailed Example Setting Up and Programming Codepads for PartitioningUser Code Allocations Zone Allocations for Areas 1Codepad Connections For Partitioning Examples Setting Up an Area 1 Codepad as the Main CodepadSetting Up an Area 1 Codepad Setting Up an Area 2 CodepadRF Information ICP-CC488 Installation Guide RF InformationRF Option Bit Enable RF Jamming Monitor Default RF Device Mapping Devices 1 toDefault RF Device Mapping Devices 9 to Using Hexadecimal Values for RF Device MappingOptional Equipment RF Device Signal Strength Devices 1 to 8 Read OnlyRF Device Signal Strength Devices 9 to 16 Read Only ICP-CC488 Installation Guide Optional EquipmentICP-CP500AW Eight Zone Area Addressable Codepad 21.5 CC816 Alarm Link Software21.3 SS914 Edmsat Satellite Siren 21.4 CC891 Programming KeyTerminals and Descriptions ICP-CC488 Installation Guide Terminals and DescriptionsTerminal Descriptions Glossary Of Terms This mode. Only the installer can program these zones Domestic alarm reportsThat an alarm was sent out Stay ModeICP-CC488 Wiring Diagram DiagramsICP-CC488 Installation Guide Terminals and Descriptions Telecom Connection Diagram for Australia Wiring and Power Up OperationYellow wire Green wire Appendix a Telephone Anti Jamming Appendix B Test Reports Only When ArmedICP-CC488 Installation Guide Appendices AppendicesSoftware Version Number SpecificationsWarranty Statement SpecificationsICP-CC488 Programming Sheets ICP-CC488 Installation Guide Programming SheetsProgramming Sheets TickReserved Telephone Line Fault OptionsAlarm Link Options Dialing FormatEOL Resistor Value Installer CodeDay Alarm Zones User Code Priority LevelsZones Zone Pulse Count SettingsSwinger Shutdown Count for Siren RF Low Battery ReportRF Receiver Trouble Restore Report Zone DescriptionsSystem Status Low Battery Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportSensor Watch Time Entry Guard Time for Stay ModeDelay Alarm Reporting Time Speaker Beep VolumeDomestic Telephone Numbers Zone Allocations Enabled for Area 1 and AreaRadio Input Options Zone Allocations for Area 1 and AreaRF Device Mapping Option RF Device Signal Strength Devices 1 toRF Device Signal Strength Devices 9 to RF OptionsSystem Date Disable Factory DefaultCountry Codes System TimeICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Remote Connect Without Call Back Verification41 IndexTelephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02