| Codepad Indicators |
|
|
EN 11
MAINS Indicator
The MAINS indicator displays whether the system’s AC MAINS supply is normal or failed.
When programming in Installer’s Programming Mode or using a Master Code function, the MAINS indicator lights to indicate a location value from 10 to
15.The MAINS indicator represents the 10 digit, which is added to the value of the lit zone indicator (for example, if the value programmed in a location is 12, the MAINS and Zone 2 indicators light).
Table 6: MAINS Indicator
Indicator | Definition |
On | The AC MAINS power is normal. |
Flashing | The AC MAINS supply failed. |
FAULT indicator
The FAULT indicator lights when the system detects a system fault. Refer to Section 3.12 Fault Analysis Mode on page 18 for more information on system faults.
Each time a new system fault is detected (the FAULT indicator flashes), the codepad beeps once per min.
Press [AWAY] to stop the beeping and to acknowledge the fault.
Table 7: FAULT indicator
Indicator | Definition |
On | A system fault must be corrected. |
Off | The system is normal (no faults). |
Flashing | A system fault must be acknowledged. |
Audible Indicators
The codepad provides these audible indications:
Table 8: Audible Indicators
Audible Indicator | Definition |
One short beep | A button was pressed on the |
| codepad, or Exit Time ended when |
| arming in STAY Mode 1 or STAY |
| Mode 2. |
Two short beeps | The system accepted your code. |
Three short beeps | The system executed the requested |
| function. |
One long beep | Exit Time ended when arming in |
| AWAY Mode, or the requested |
| operation was denied or aborted. |
One short beep | Walk Test Mode is currently active, |
every sec | or warning before automatic arming |
| takes place. |
One short beep | Telephone Monitor Mode is active. |
every 2 sec |
|
One short beep | There is a system fault to be |
every min | acknowledged. |
2.2ICP-CP508LW Eight Zone LCD Codepad
Figure 2: ICP-CP508LW Eight Zone LCD Codepad
The codepad is the communications interface between you and the alarm system. The codepad allows you to issue commands and offers visual and audible indications to guide you through general operation.
The codepad incorporates a number of indicators: eight zone indicators show the condition of each zone and seven other indicators show general status. These indicators are described in the tables throughout this section.
Zone Indicators
1 2 3 … The zone indicators (1 to 8) display the status of the zones listed in Table 3 on page 10.
AWAY Indicator
The AWAY indicator lights when the system is armed in AWAY Mode. The ON indicator also lights when the system is armed in AWAY Mode (refer to Table 5 on page 10).
The AWAY indicator flashes with the STAY indicator when you are in Installer’s Programming Mode or you are using a Master Code function.
Refer to Section 3.1 Arming the System in AWAY Mode for more information.
STAY Indicator
The STAY indicator lights when the system is armed in STAY Mode 1 or STAY Mode 2 (refer to Table 4).
The STAY indicator also flashes with the AWAY indicator when you are in Installer’s Programming Mode or you are using a Master Code function.
The ON indicator also lights when the system is armed in STAY Mode 1 or STAY Mode 2.
For more information, refer to:
•Section 3.3 to arm the system in STAY Mode 1.
•Section 14.3.5 to set zones to be automatically isolated in STAY Mode 1.