ICP-CC488 Installation Guide 16.0

Programmable Outputs

 

 

EN 70

When programming Test Report options, specify the hour and minute of the day the report is required, and how often to send the report. Test reports are reported on a daily basis from every day to every fifteen days. Refer to Section 5.1.2 Set the Number of Days until the First Test Report to set the first test report.

If Test Reports are not required, program the repeat interval in Location 434 as 0.

Program the Test Report Time as 24:00 to send reports every 30 min.

Example

If you want to send Test Reports once every seven days at 11:35 PM, program Locations 428 to 429 as:

[2 3 3 5 7 1 7]

15.29 Test Reporting Dialer Options

Location 435

0No report allowed

1 Report to Receiver 1

2 Report to Receiver 2

4Report to both Receiver 1 and Receiver 2

8 Report to Receiver 2 only if Receiver 1 fails

Location 435 is set by default to report only to Receiver 1. You can select whether Test Reports are sent to Receiver 1, Receiver 2, or both, Receiver 2 only when Receiver 1 fails, or no reporting.

16.0 Programmable Outputs

The ICP-CC488 Control Panel has four fully- programmable outputs on the main printed circuit board and one programmable output that operates the codepad buzzer. The four outputs are set by default to operate as horn speaker, fire alarm verification, strobe, and internal screamer.

Programmable outputs require four parameters to operate correctly.

Table 54:

Output Parameters

 

 

 

 

 

 

 

 

 

 

Parameter

Description

 

 

Event Type

The Event Type specifies when an output

 

is activated. The Output Event Types are

 

listed in Section 16.2 on page 71 . Enter

 

the code for the Output Event Type into

 

the two corresponding locations for the

 

output.

 

 

Polarity

Polarity determines whether the output

 

operates for the duration of the event,

 

pulses for the duration, operates only

 

once (one shot), or latches on. The

 

Polarity options are listed in Table 56 on

 

page 76.

 

 

Time Base/

The Time Base and Time Multiplier

Time

parameters determine how long and how

Multiplier

often the output operates. Refer to

 

Section 16.4 Output Timing.

 

 

 

 

 

 

 

 

 

Location

436 to 465

 

 

 

 

Location

Default

Output 1 (Default – Horn

 

 

Speaker)

 

 

 

 

Event Code

436

1

 

Event Code

437

14

 

Polarity

438

0

 

Time Base

439

0

 

Time Base Multiplier

440

0

 

Time Base Multiplier

441

0

Output 2 (Default – Fire Alarm With Verification)

 

 

Event Code

442

2

 

Event Code

443

7

 

Polarity

444

10

 

Time Base

445

2

 

Time Base Multiplier

446

1

 

Time Base Multiplier

447

5

Strobe Output (Default – Strobe – Reset After 8 hrs.)

 

Event Code

448

2

 

Event Code

449

0

 

Polarity

450

6

 

Time Base

451

4

 

Time Base Multiplier

452

0

 

Time Base Multiplier

453

8

Relay Output (Default – Sirens Running)

 

 

Event Code

454

1

 

Event Code

455

15

 

Polarity

456

1

 

Time Base

457

0

 

Time Base Multiplier

458

0

 

Time Base Multiplier

459

0

Codepad Buzzer (Default – Entry/Exit Warning and Day

Alarm)

 

 

 

 

Event Code

460

0

 

Event Code

461

13

 

Polarity

462

2

 

Time Base

463

1

 

Time Base Multiplier

464

0

 

Time Base Multiplier

465

1

 

 

 

 

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 70
Contents Installation Guide ICP-CC488Copyright Notice ICP-CC488 Installation Guide NoticesBosch Security Systems, Inc /08 F01U089457-02 Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Figures TablesUser Code Allocations Hexadecimal Values for Zone Nos ICP-CC488 Installation Guide Introduction ICP-CC488 FeaturesIntroduction Quick Start ICP-CC488 Zone DefaultsZone Defaults for the ICP-CC488 Set the Date and TimeICP-CC488 Installation Guide Codepad Indicators Codepad IndicatorsICP-CP508W Eight Zone LED Codepad Audible Indicators Mains IndicatorFault indicator ICP-CP508LW Eight Zone LCD CodepadICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads Arming the System in Stay Mode Arming the System in Away ModeDisarming the System from Away Mode ICP-CC488 Installation Guide System OperationsDisarming the System from Stay Mode Codepad Duress Alarm Codepad Panic AlarmIsolating Zones Codepad Fire AlarmCodepad Medical Alarm Standard IsolatingFault Analysis Mode Fault DescriptionsSystem Fault indicators AC Mains FailureFault Analysis Conditions Remote Radio Transmitter OperationsRemote Radio User Code Priority Levels Indications from Remote Radio Transmitter OperationsChanging or Deleting Remote Radio User Codes Installer Code Functions Installer Code FunctionsICP-CC488 Installation Guide System Functions Add or Delete RF Wireless DevicesChange Domestic Phone Numbers Set the Number of Days until the First Test ReportDomestic Dialing Digits Change Telco Arm/Disarm Sequence Codepad Indicators When Changing Phone NumbersExamples provided for this feature apply only to Australia Telco Arm SequenceSatellite Siren Service Mode Setting Stay Mode 2 ZonesTurning Telephone Monitor Mode On and Off Event Sequence Telephone Monitor Mode IndicationsEvent Memory Recall Mode Event Memory PlaybackArm or Disarm Both Areas at the Same Time Master Code FunctionsMaster Code Functions Changing and Deleting User CodesChanging and Deleting Remote Radio User Codes User Numbers Displayed by the Codepad IndicatorsChanging Domestic Phone Numbers Codepad Indicators When Changing Domestic Telephone Numbers When you program a # in the telco arm sequence, enter STAY2 Turning Outputs On/OffSetting the Date and Time Event Non-volatile Memory Recall ModeUser Code Functions Arm the System in Away ModeArm the System in Stay Mode Hold-Down FunctionsReset Latching Outputs Turning Day Alarm On and OffFault Analysis Mode Horn Speaker TestProgramming ICP-CC488 Installation Guide Remote Arming by TelephoneRemote Arming by Telephone Programming with the Remote CodepadCodepad Indicators ICP-CC488 Installation Guide ProgrammingProgramming with the Programming Key Command 959 Test the Programming Key Installer’s Programming CommandsInstaller’s Programming Mode Commands Programming Option BitsCommand 960 Exit from Installers Programming Mode Command 963 Copy the Programming Key to the Control PanelCommand 964 Erase the Programming Key Command 965 Set Up Domestic Dialing FormatExample Auto Step Disabled Disable Factory DefaultsExample Auto Step Enabled Command 965 DefaultsRemote Connect Alarm Link SoftwareICP-CC488 Installation Guide Alarm Link Software Remote Connection with Customer ControlAlarm Link Options Terminate Alarm Link Connection on Alarm ICP-CC488 Installation Guide Domestic DialingEnable Alarm Link Call Back Domestic DialingDialer Reporting Formats Setting Up and Programming Domestic ReportingICP-CC488 Installation Guide Dialer Reporting Formats Transmission Formats10.1.4 4 + 2 Reporting Format Contact ID Format BreakdownPoint ID Codes Example Reporting in 4 + 2 Format + 2 Reporting Format+ 2 Transmission Code Descriptions Basic Pager Reporting Format14.3.2 Basic Pager Display Dialer Information ICP-CC488 Installation Guide Dialer InformationBasic Pager Display Information Handshake Tone for Receiver 1 and Receiver Primary Telephone Number for Receiver 1 and ReceiverSecondary Telephone Number for Receiver 1 and Receiver Dialing DigitsDialing Format Transmission Format for Receiver 1 and ReceiverSubscriber ID Number for Receiver 1 and Receiver Telco Arming SequenceRing Count Telco Disarming SequenceCall Back Telephone Number Answering Machine BypassDialer Options Telephone Line Fault OptionsICP-CC488 Installation Guide Dialer Options Dialer OptionsOpen/Close Reports Only if Previous Alarm Answering Machine Bypass Only When ArmedUse Bell 103 for FSK Format Disabled=CCITT V21 Open/Close Reports for Stay Mode 1 and Stay ModeICP-CC488 Installation Guide Access Codes Access CodesInstaller Code User CodesArm/Disarm User Code PriorityPriority Levels Arm OnlyZone Information Day Alarm InformationICP-CC488 Installation Guide Zone Information EOL Resistor ValueTamper Zone 1 3K3 Zone 5 6K8 Zone Options Zone ProgrammingZone Operating Information Zone Reporting InformationYou can program Zones 1 to 16 as any zone type Keyswitch Zone Delay-1 ZoneDelay-2 Zone Instant ZoneZone Not Used 13 24-Hour Fire ZoneChime Zone Zone Pulse CountKeyswitch Zone Options Delay Alarm ReportingSilent Alarm Latching Arm and Disarm in Away ModeMomentary Arm and Disarm in Away Mode Latching Arm in Stay ModeLatching Disarm from Stay Mode 1 or Stay Mode Momentary Arm in Away ModeSwinger Shutdown Count for Siren Swinger Shutdown Count for DialerZone Status Walk Test Report System Reporting InformationZone Status Zone Tamper Report Zone Status Bypass ReportsZone Status Sensor Watch Reports Zone Status Alarm Restore CodeRF Low Battery Report Zone Status Reporting OptionsOpen/Close Reports RF Receiver Trouble Restore ReportRF Dialer Options Open/Close Reporting OptionsSystem Status AC Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report Codepad Fire ReportSystem Status Access Denied System Status Low Battery ReportSystem Status Low Battery Restore Report System Status Reporting OptionsProgrammable Outputs ICP-CC488 Installation Guide Programmable OutputsTest Reporting Dialer Options Redirecting Outputs to the Codepad Buzzer Output Event TypesDay Alarm Enabled Entry Warning + Day Alarm ResettingExit Warning + Entry Warning + Day Alarm Resetting AUX Power Supply FailCodepad Fire Alarm Sensor Watch AlarmCodepad Medical Alarm Codepad Panic AlarmRadio Control Output 1 Not in Away Mode Fire Alarm VerificationRemote Control Radio Control Output 2 Not in Away ModeGlobal Chime Area 1 in Alarm Area 2 in AlarmMimic Zone Zone Not SealedOutput Polarity Output Timing System Event TimersICP-CC488 Installation Guide System Event Timers Pulsing PolaritiesExit Timer Programming Entry/Exit TimersEntry Timer Entry Guard Timer for Stay ModeSiren Run Time Auto Arming Pre-Alert TimerCodepad Lockout Time Siren Sound RateSystem and Consumer Options Strobe Indications for Radio Arm/Disarm Assign Button 4 To Operate Stay ModeAccess Denied Code Retries To Be Silent Codepad Panic To Be SilentConsumer Options Radio Input Options Partitioning Using Codepads in a Partitioned SystemICP-CC488 Installation Guide Partitioning 19.1 CP500 Master Partitioned LED CodepadZone Allocations Zone Allocations for Areas 1 Setting Up and Programming Codepads for PartitioningUser Code Allocations Detailed ExampleSetting Up an Area 2 Codepad Setting Up an Area 1 Codepad as the Main CodepadSetting Up an Area 1 Codepad Codepad Connections For Partitioning ExamplesRF Information ICP-CC488 Installation Guide RF InformationRF Option Bit Using Hexadecimal Values for RF Device Mapping Default RF Device Mapping Devices 1 toDefault RF Device Mapping Devices 9 to Enable RF Jamming MonitorICP-CC488 Installation Guide Optional Equipment RF Device Signal Strength Devices 1 to 8 Read OnlyRF Device Signal Strength Devices 9 to 16 Read Only Optional Equipment21.4 CC891 Programming Key 21.5 CC816 Alarm Link Software21.3 SS914 Edmsat Satellite Siren ICP-CP500AW Eight Zone Area Addressable CodepadTerminals and Descriptions ICP-CC488 Installation Guide Terminals and DescriptionsTerminal Descriptions Glossary Of Terms Stay Mode Domestic alarm reportsThat an alarm was sent out This mode. Only the installer can program these zonesDiagrams ICP-CC488 Wiring DiagramICP-CC488 Installation Guide Terminals and Descriptions Wiring and Power Up Operation Telecom Connection Diagram for AustraliaYellow wire Green wire Appendices Appendix B Test Reports Only When ArmedICP-CC488 Installation Guide Appendices Appendix a Telephone Anti JammingSpecifications SpecificationsWarranty Statement Software Version NumberTick ICP-CC488 Installation Guide Programming SheetsProgramming Sheets ICP-CC488 Programming SheetsDialing Format Telephone Line Fault OptionsAlarm Link Options ReservedUser Code Priority Levels Installer CodeDay Alarm Zones EOL Resistor ValueZone Pulse Count Settings ZonesZone Descriptions RF Low Battery ReportRF Receiver Trouble Restore Report Swinger Shutdown Count for SirenSystem Status AC Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status Low Battery ReportSpeaker Beep Volume Entry Guard Time for Stay ModeDelay Alarm Reporting Time Sensor Watch TimeZone Allocations for Area 1 and Area Zone Allocations Enabled for Area 1 and AreaRadio Input Options Domestic Telephone NumbersRF Options RF Device Signal Strength Devices 1 toRF Device Signal Strength Devices 9 to RF Device Mapping OptionSystem Time Disable Factory DefaultCountry Codes System DateICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Index Remote Connect Without Call Back Verification41Telephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02