Bosch Appliances ICP-CC488 manual User Code Priority, Priority Levels, Arm/Disarm, Arm Only

Page 55

ICP-CC488 Installation Guide 13.0

Access Codes

 

 

EN 55

Location 185 to 264

 

Location

Default

User Code 1

185

2

 

186

5

 

187

8

 

188

0

Priority Level

189

10

User Code 2

190 to 193

15

Priority Level

194

2

User Code 3

195 to 198

15

Priority Level

199

2

User Code 4

200 to 203

15

Priority Level

204

2

User Code 5

205 to 208

15

Priority Level

209

2

User Code6

210 to 213

15

Priority Level

214

2

User Code 7

215 to 218

15

Priority Level

219

2

User Code 8

220

0

 

221 to 223

15

Priority Level

224

3

User Code 9

225 to 228

15

Priority Level

229

2

User Code 10

230 to 233

15

Priority Level

234

2

User Code 11

235 to 238

15

Priority Level

239

2

User Code 12

240 to 243

15

Priority Level

244

2

User Code 13

245 to 248

15

Priority Level

249

2

User Code 14

250 to 253

15

Priority Level

254

2

User Code 15

255 to 258

15

Priority Level

259

2

User Code 16

260 to 263

15

Priority Level

264

2

13.3User Code Priority

The installer can assign one of ten different priority levels to a User Code. Each priority level allows or restricts a user from performing specific functions.

Table 47: Priority Levels

Priority

Description

Level

 

0

Arm/disarm

1

Arm only

2

Arm/disarm and Open/Close Reports

3

Arm only and Close Report

4

Arm/disarm and code to isolate

6

Arm/disarm, code to isolate, and Open/Close

 

Reports

8

Arm/disarm and Master Code functions

10

Arm/disarm, Master Code functions, and

 

Open/Close Reports

12

Arm/disarm, Master Code functions, and code

 

to isolate

14

Arm/disarm, Master Code functions, code to

 

isolate, and Open/Close Reports

Arm/Disarm

The user can arm and disarm the system. A Closing Report is sent only after a previous code with the ability to send an Opening Report disarms the system.

Arm Only

The user can arm the system but cannot disarm the system. A Closing Report is sent only after a previous code with the ability to send an Opening Report disarms the system.

Open/Close Reports

Open and Close Reports are sent to the monitoring station when the user disarms and arms the system, but only if Open/Close Reports is enabled in Locations 401 and 402 (refer to Section 15.13 Open/Close Reports on page 67).

Code To Isolate

If one or more User Codes include this option, the method of standard isolating is disabled and only a User Code with this option in its priority level can isolate zones before arming the system using the Code to Isolate method. Refer to Section 3.11 Isolating Zones on page 17 for more information.

When priority level 4, 6, 12, or 14 is assigned to any User Codes, the Standard Isolating method no longer operates. Only User Codes with a priority level of 4, 6, 12, or 14 can isolate zones using the Code to Isolate method.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 55
Contents ICP-CC488 Installation GuideCopyright Notice ICP-CC488 Installation Guide NoticesBosch Security Systems, Inc /08 F01U089457-02 Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Tables FiguresUser Code Allocations Hexadecimal Values for Zone Nos ICP-CC488 Installation Guide Introduction ICP-CC488 FeaturesIntroduction Set the Date and Time ICP-CC488 Zone DefaultsZone Defaults for the ICP-CC488 Quick StartICP-CC488 Installation Guide Codepad Indicators Codepad IndicatorsICP-CP508W Eight Zone LED Codepad ICP-CP508LW Eight Zone LCD Codepad Mains IndicatorFault indicator Audible IndicatorsICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads ICP-CC488 Installation Guide System Operations Arming the System in Away ModeDisarming the System from Away Mode Arming the System in Stay ModeDisarming the System from Stay Mode Codepad Panic Alarm Codepad Duress AlarmStandard Isolating Codepad Fire AlarmCodepad Medical Alarm Isolating ZonesFault Descriptions Fault Analysis ModeAC Mains Failure System Fault indicatorsRemote Radio Transmitter Operations Fault Analysis ConditionsRemote Radio User Code Priority Levels Indications from Remote Radio Transmitter OperationsChanging or Deleting Remote Radio User Codes Add or Delete RF Wireless Devices Installer Code FunctionsICP-CC488 Installation Guide System Functions Installer Code FunctionsChange Domestic Phone Numbers Set the Number of Days until the First Test ReportDomestic Dialing Digits Telco Arm Sequence Codepad Indicators When Changing Phone NumbersExamples provided for this feature apply only to Australia Change Telco Arm/Disarm SequenceSatellite Siren Service Mode Setting Stay Mode 2 ZonesTurning Telephone Monitor Mode On and Off Event Memory Playback Telephone Monitor Mode IndicationsEvent Memory Recall Mode Event SequenceChanging and Deleting User Codes Master Code FunctionsMaster Code Functions Arm or Disarm Both Areas at the Same TimeChanging and Deleting Remote Radio User Codes User Numbers Displayed by the Codepad IndicatorsChanging Domestic Phone Numbers Codepad Indicators When Changing Domestic Telephone Numbers Turning Outputs On/Off When you program a # in the telco arm sequence, enter STAY2Event Non-volatile Memory Recall Mode Setting the Date and TimeHold-Down Functions Arm the System in Away ModeArm the System in Stay Mode User Code FunctionsHorn Speaker Test Turning Day Alarm On and OffFault Analysis Mode Reset Latching OutputsProgramming with the Remote Codepad ICP-CC488 Installation Guide Remote Arming by TelephoneRemote Arming by Telephone ProgrammingCodepad Indicators ICP-CC488 Installation Guide ProgrammingProgramming with the Programming Key Programming Option Bits Installer’s Programming CommandsInstaller’s Programming Mode Commands Command 959 Test the Programming KeyCommand 963 Copy the Programming Key to the Control Panel Command 960 Exit from Installers Programming ModeCommand 965 Set Up Domestic Dialing Format Command 964 Erase the Programming KeyCommand 965 Defaults Disable Factory DefaultsExample Auto Step Enabled Example Auto Step DisabledRemote Connection with Customer Control Alarm Link SoftwareICP-CC488 Installation Guide Alarm Link Software Remote ConnectAlarm Link Options Domestic Dialing ICP-CC488 Installation Guide Domestic DialingEnable Alarm Link Call Back Terminate Alarm Link Connection on AlarmTransmission Formats Setting Up and Programming Domestic ReportingICP-CC488 Installation Guide Dialer Reporting Formats Dialer Reporting FormatsExample Reporting in 4 + 2 Format + 2 Reporting Format Contact ID Format BreakdownPoint ID Codes 10.1.4 4 + 2 Reporting FormatBasic Pager Reporting Format + 2 Transmission Code Descriptions14.3.2 Basic Pager Display Dialer Information ICP-CC488 Installation Guide Dialer InformationBasic Pager Display Information Dialing Digits Primary Telephone Number for Receiver 1 and ReceiverSecondary Telephone Number for Receiver 1 and Receiver Handshake Tone for Receiver 1 and ReceiverTelco Arming Sequence Transmission Format for Receiver 1 and ReceiverSubscriber ID Number for Receiver 1 and Receiver Dialing FormatAnswering Machine Bypass Telco Disarming SequenceCall Back Telephone Number Ring CountDialer Options Telephone Line Fault OptionsICP-CC488 Installation Guide Dialer Options Dialer OptionsOpen/Close Reports for Stay Mode 1 and Stay Mode Answering Machine Bypass Only When ArmedUse Bell 103 for FSK Format Disabled=CCITT V21 Open/Close Reports Only if Previous AlarmUser Codes Access CodesInstaller Code ICP-CC488 Installation Guide Access CodesArm Only User Code PriorityPriority Levels Arm/DisarmEOL Resistor Value Day Alarm InformationICP-CC488 Installation Guide Zone Information Zone InformationTamper Zone 1 3K3 Zone 5 6K8 Zone Reporting Information Zone ProgrammingZone Operating Information Zone OptionsYou can program Zones 1 to 16 as any zone type Instant Zone Delay-1 ZoneDelay-2 Zone Keyswitch ZoneZone Pulse Count 13 24-Hour Fire ZoneChime Zone Zone Not UsedLatching Arm and Disarm in Away Mode Delay Alarm ReportingSilent Alarm Keyswitch Zone OptionsMomentary Arm in Away Mode Latching Arm in Stay ModeLatching Disarm from Stay Mode 1 or Stay Mode Momentary Arm and Disarm in Away ModeSwinger Shutdown Count for Dialer Swinger Shutdown Count for SirenZone Status Bypass Reports System Reporting InformationZone Status Zone Tamper Report Zone Status Walk Test ReportZone Status Reporting Options Zone Status Alarm Restore CodeRF Low Battery Report Zone Status Sensor Watch ReportsOpen/Close Reporting Options RF Receiver Trouble Restore ReportRF Dialer Options Open/Close ReportsCodepad Fire Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportSystem Status Reporting Options System Status Low Battery ReportSystem Status Low Battery Restore Report System Status Access DeniedProgrammable Outputs ICP-CC488 Installation Guide Programmable OutputsTest Reporting Dialer Options Output Event Types Redirecting Outputs to the Codepad BuzzerAUX Power Supply Fail Entry Warning + Day Alarm ResettingExit Warning + Entry Warning + Day Alarm Resetting Day Alarm EnabledCodepad Panic Alarm Sensor Watch AlarmCodepad Medical Alarm Codepad Fire AlarmRadio Control Output 2 Not in Away Mode Fire Alarm VerificationRemote Control Radio Control Output 1 Not in Away ModeZone Not Sealed Area 1 in Alarm Area 2 in AlarmMimic Zone Global ChimeOutput Polarity Pulsing Polarities System Event TimersICP-CC488 Installation Guide System Event Timers Output TimingEntry Guard Timer for Stay Mode Programming Entry/Exit TimersEntry Timer Exit TimerSiren Sound Rate Auto Arming Pre-Alert TimerCodepad Lockout Time Siren Run TimeSystem and Consumer Options Codepad Panic To Be Silent Assign Button 4 To Operate Stay ModeAccess Denied Code Retries To Be Silent Strobe Indications for Radio Arm/DisarmConsumer Options Radio Input Options 19.1 CP500 Master Partitioned LED Codepad Using Codepads in a Partitioned SystemICP-CC488 Installation Guide Partitioning PartitioningZone Allocations Detailed Example Setting Up and Programming Codepads for PartitioningUser Code Allocations Zone Allocations for Areas 1Codepad Connections For Partitioning Examples Setting Up an Area 1 Codepad as the Main CodepadSetting Up an Area 1 Codepad Setting Up an Area 2 CodepadRF Information ICP-CC488 Installation Guide RF InformationRF Option Bit Enable RF Jamming Monitor Default RF Device Mapping Devices 1 toDefault RF Device Mapping Devices 9 to Using Hexadecimal Values for RF Device MappingOptional Equipment RF Device Signal Strength Devices 1 to 8 Read OnlyRF Device Signal Strength Devices 9 to 16 Read Only ICP-CC488 Installation Guide Optional EquipmentICP-CP500AW Eight Zone Area Addressable Codepad 21.5 CC816 Alarm Link Software21.3 SS914 Edmsat Satellite Siren 21.4 CC891 Programming KeyTerminals and Descriptions ICP-CC488 Installation Guide Terminals and DescriptionsTerminal Descriptions Glossary Of Terms This mode. Only the installer can program these zones Domestic alarm reportsThat an alarm was sent out Stay ModeICP-CC488 Wiring Diagram DiagramsICP-CC488 Installation Guide Terminals and Descriptions Telecom Connection Diagram for Australia Wiring and Power Up OperationYellow wire Green wire Appendix a Telephone Anti Jamming Appendix B Test Reports Only When ArmedICP-CC488 Installation Guide Appendices AppendicesSoftware Version Number SpecificationsWarranty Statement SpecificationsICP-CC488 Programming Sheets ICP-CC488 Installation Guide Programming SheetsProgramming Sheets TickReserved Telephone Line Fault OptionsAlarm Link Options Dialing FormatEOL Resistor Value Installer CodeDay Alarm Zones User Code Priority LevelsZones Zone Pulse Count SettingsSwinger Shutdown Count for Siren RF Low Battery ReportRF Receiver Trouble Restore Report Zone DescriptionsSystem Status Low Battery Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportSensor Watch Time Entry Guard Time for Stay ModeDelay Alarm Reporting Time Speaker Beep VolumeDomestic Telephone Numbers Zone Allocations Enabled for Area 1 and AreaRadio Input Options Zone Allocations for Area 1 and AreaRF Device Mapping Option RF Device Signal Strength Devices 1 toRF Device Signal Strength Devices 9 to RF OptionsSystem Date Disable Factory DefaultCountry Codes System TimeICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Remote Connect Without Call Back Verification41 IndexTelephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02