| Zone Information |
|
|
EN 64
When isolating
If you do not want the system to report Zone Bypass Reports, program Locations 385 and 386 to 0 (refer to Section 15.3 Zone Status – Bypass Reports on page 65).
4 – Forced Arming Allowed
If this option is selected, the system can be armed with the zone unsealed. If this option is not selected, the system does not allow the User Code holder to arm the system until the zone is sealed or manually isolated. Refer to Section 3.11 Isolating Zones on page 17 for more information.
8 – Zone Restore Report
If this option is selected, the zone sends Restore Reports when the zone is restored. If this option is not selected, the zone does not send Restore Reports when the zone is restored.
If a
14.3.8Zone Report Code
If you want the control panel to transmit Zone Alarm Reports, program this location as 1. If not, program this location as 0.
14.3.9Zone Dialer Options
By default, a zone reports only to Receiver 1. Table
53 on page 64 lists the reporting options for the zone.
Table 53: Zone Dialer Options
Option Description
0No report required
1 | Receiver 1 |
2 | Receiver 2 |
4Receiver 1 and Receiver 2
8Receiver 2 only when Receiver 1 fails
14.4Swinger Shutdown Count for Siren
Location 379
Default 3
1 to 15 Number of times siren operates until lockout
Location 379 determines the number of times the sirens can be activated before lockout options take effect. This location has no effect unless you program at least one zone for lockout siren. Refer to Section
14.3.5Zone Options 1 on page 61 to program zones for lockout siren.
Only alarms activated from zone inputs can decrement the Swinger Shutdown Counter. Alarms such as Codepad Panic, Access Denied, and other system alarms do not affect the Swinger Shutdown Count.
When the sirens are operating, the Swinger Shutdown Counter is decremented only by the first zone that activated the alarm. Any other zones activated during Siren Run Time do not affect the counter.
When the Swinger Shutdown Count is reached, all zones that were activated are locked out according to their individual lockout settings.
Example
All eight zones are programmed for lockout siren with a Swinger Shutdown Count of 3. If Zone 1 activates an alarm, the Swinger Shutdown Count is decremented by one after the end of Siren Run Time to a swinger shutdown count of 2.
After the Siren Run Time is reset from the previous alarm, Zone 2 activates an alarm and activates the sirens. After the sirens are reset, the swinger shutdown count is decremented again to 1.
If Zone 3 also activates an alarm after the sirens are reset from Zone 2, the Swinger Shutdown Count is decremented to 0, which locks out all three zones from sounding the sirens until the system is reset.
At this point, the Swinger Shutdown Count for Sirens is reset to 3 and the process of swinger shutdown for remaining zones begins again until all zones are locked out.
If the
14.5Swinger Shutdown Count for Dialer
Location 380
Default 6
1 to 15 Number of times dialer operates until lockout
Location 380 determines the number of times the dialer can be activated before lockout options take effect. This location has no effect unless you program at least one zone for lockout dialer. Refer to Section
14.3.5Zone Options 1 on page 61 to program zones for lockout dialer.
Only alarms activated from zone inputs can decrement the Swinger Shutdown Counter. Alarms such as Codepad Panic, Code Retries, and other system alarms do not affect the Swinger Shutdown Count.
When the dialer is online, its counter is decremented only by the first zone that activated the alarm. Any other zones activated while the dialer is online do not affect the counter.