Bosch Appliances ICP-CC488 Programming Entry/Exit Timers, Entry Timer, Delay Alarm Reporting Time

Page 78

ICP-CC488 Installation Guide 17.0

System Event Timers

 

 

EN 78

17.1Programming Entry/Exit Timers

There are two programming locations for Entry Timer 1, Entry Timer 2, Exit Time for AWAY Mode, and Entry Guard Time for STAY Mode.

The first location of the timer allows you to set the timer in increments of 1 sec. The sec location allows you to set the timer in increments of 16 sec. Add these two locations together for the total time.

Example

To set the Entry Time to 18 sec, program Location 466 as 2 (2 x 1 sec = 2 sec) and Location 467 as 1 (1 x 16 sec = 16 sec) for a total time of 18 sec (2 + 16 = 18).

17.2Entry Timer 1

Location 466 to 467

 

 

Location

Default

Increments of

1 sec

466

4

(0 sec to 15 sec)

 

 

Increments of

16 sec

467

1

(0 sec to 240 sec)

 

 

You can program Entry Timer 1 from 0 to 255 sec in increments of 1 sec. Entry Timer 1 is the delay time used by the Delay-1 Zones. Refer to Section 14.3.2 Zone Types on page 61 for more information.

17.3Entry Timer 2

Location 468 to 467

 

 

Location

Default

Increments of

1 sec

468

8

(0 sec to 15 sec)

 

 

Increments of

16 sec

467

2

(0 sec to 240 sec)

 

 

You can program Entry Timer 2 from 0 to 255 sec in increments of 1 sec. Entry Timer 2 is the delay time used by Delay-2 Zones. Refer to Section 14.3.2 Zone Types on page 61 for more information.

17.4Exit Timer

Location 470 to 471

 

 

Location

Default

Increments of

1 sec

470

12

(0 sec to 15 sec)

 

 

Increments of

16 sec

471

3

(0 sec to 240 sec)

 

 

You can program the Exit Timer from 0 to 255 sec in increments of 1 sec. When arming the system in AWAY Mode, the remote codepad beeps during Exit Time until the final 10 sec, when the codepad sounds one continuous beep to indicate the end of Exit Time is near.

The remote codepad always sounds one short beep at the end of Exit Time when arming in STAY Mode 1 or STAY Mode 2.

17.5Entry Guard Timer for STAY Mode

Location 472 to 473

 

 

Location

Default

Increments of

1 sec

472

0

(0 sec to 15 sec)

 

 

Increments of

16 sec

473

0

(0 sec to 240 sec)

 

 

Entry Guard Timer for STAY Mode is the delay time used for all zones except 24-Hour Burglary and 24- Hour Fire Zones when the system is armed in STAY Mode 1 or STAY Mode 2. All zones, including Delay Zones, use this timer for the entry delay (for example, the Entry Guard Timer overrides the delay time programmed for a Delay Zone). If the Entry Guard Timer is programmed as 0, each zone acts according to its programmed zone type.

Refer to Section 14.3.7 to program zones to be automatically isolated in STAY Mode 1. Refer to Section 5.2.6 to program zones to be automatically isolated in STAY Mode 2.

17.6Delay Alarm Reporting Time

Location 474 to 475

 

Location

Default

Increments of 1 sec (0 sec to

474

0

15 sec)

 

 

Increments of 16 sec (0 sec to

475

0

240 sec)

 

 

These locations program the time in sec that a delayed report waits dormant in the dial buffer before it is sent to the receiving party. If a User Code holder resets the alarm within this time frame, the control panel clears the dialer buffer and does not report the alarm to the receiving party. Refer to Section 14.3.5 Zone Options 1 on page 61 to program zones for delay alarm reporting.

17.7Sensor Watch Time

Location 476 to 477

 

Location

Default

Increments of days (tens digit)

476

0

Increments of days (units digit)

477

0

The time set in these two locations determines the number of days (0 to 99) a zone can remain sealed before registering as a fault. This feature is active only when the system is disarmed. If a zone programmed for Sensor Watch is not unsealed and reset during this time, the FAULT indicator lights. Refer to Section 3.13 Fault Descriptions on page 18 for more information on Sensor Watch Faults. Refer to Section 14.3.5 Zone Options 1 on page 61 for programming zones for Sensor Watch.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 78
Contents Installation Guide ICP-CC488ICP-CC488 Installation Guide Notices Copyright NoticeBosch Security Systems, Inc /08 F01U089457-02 Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Figures TablesUser Code Allocations Hexadecimal Values for Zone Nos ICP-CC488 Features ICP-CC488 Installation Guide IntroductionIntroduction Quick Start ICP-CC488 Zone DefaultsZone Defaults for the ICP-CC488 Set the Date and TimeCodepad Indicators ICP-CC488 Installation Guide Codepad IndicatorsICP-CP508W Eight Zone LED Codepad Audible Indicators Mains IndicatorFault indicator ICP-CP508LW Eight Zone LCD CodepadICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads Arming the System in Stay Mode Arming the System in Away ModeDisarming the System from Away Mode ICP-CC488 Installation Guide System OperationsDisarming the System from Stay Mode Codepad Duress Alarm Codepad Panic AlarmIsolating Zones Codepad Fire AlarmCodepad Medical Alarm Standard IsolatingFault Analysis Mode Fault DescriptionsSystem Fault indicators AC Mains FailureFault Analysis Conditions Remote Radio Transmitter OperationsIndications from Remote Radio Transmitter Operations Remote Radio User Code Priority LevelsChanging or Deleting Remote Radio User Codes Installer Code Functions Installer Code FunctionsICP-CC488 Installation Guide System Functions Add or Delete RF Wireless DevicesSet the Number of Days until the First Test Report Change Domestic Phone NumbersDomestic Dialing Digits Change Telco Arm/Disarm Sequence Codepad Indicators When Changing Phone NumbersExamples provided for this feature apply only to Australia Telco Arm SequenceSetting Stay Mode 2 Zones Satellite Siren Service ModeTurning Telephone Monitor Mode On and Off Event Sequence Telephone Monitor Mode IndicationsEvent Memory Recall Mode Event Memory PlaybackArm or Disarm Both Areas at the Same Time Master Code FunctionsMaster Code Functions Changing and Deleting User CodesUser Numbers Displayed by the Codepad Indicators Changing and Deleting Remote Radio User CodesChanging Domestic Phone Numbers Codepad Indicators When Changing Domestic Telephone Numbers When you program a # in the telco arm sequence, enter STAY2 Turning Outputs On/OffSetting the Date and Time Event Non-volatile Memory Recall ModeUser Code Functions Arm the System in Away ModeArm the System in Stay Mode Hold-Down FunctionsReset Latching Outputs Turning Day Alarm On and OffFault Analysis Mode Horn Speaker TestProgramming ICP-CC488 Installation Guide Remote Arming by TelephoneRemote Arming by Telephone Programming with the Remote CodepadICP-CC488 Installation Guide Programming Codepad IndicatorsProgramming with the Programming Key Command 959 Test the Programming Key Installer’s Programming CommandsInstaller’s Programming Mode Commands Programming Option BitsCommand 960 Exit from Installers Programming Mode Command 963 Copy the Programming Key to the Control PanelCommand 964 Erase the Programming Key Command 965 Set Up Domestic Dialing FormatExample Auto Step Disabled Disable Factory DefaultsExample Auto Step Enabled Command 965 DefaultsRemote Connect Alarm Link SoftwareICP-CC488 Installation Guide Alarm Link Software Remote Connection with Customer ControlAlarm Link Options Terminate Alarm Link Connection on Alarm ICP-CC488 Installation Guide Domestic DialingEnable Alarm Link Call Back Domestic DialingDialer Reporting Formats Setting Up and Programming Domestic ReportingICP-CC488 Installation Guide Dialer Reporting Formats Transmission Formats10.1.4 4 + 2 Reporting Format Contact ID Format BreakdownPoint ID Codes Example Reporting in 4 + 2 Format + 2 Reporting Format+ 2 Transmission Code Descriptions Basic Pager Reporting Format14.3.2 Basic Pager Display ICP-CC488 Installation Guide Dialer Information Dialer InformationBasic Pager Display Information Handshake Tone for Receiver 1 and Receiver Primary Telephone Number for Receiver 1 and ReceiverSecondary Telephone Number for Receiver 1 and Receiver Dialing DigitsDialing Format Transmission Format for Receiver 1 and ReceiverSubscriber ID Number for Receiver 1 and Receiver Telco Arming SequenceRing Count Telco Disarming SequenceCall Back Telephone Number Answering Machine BypassDialer Options Telephone Line Fault OptionsICP-CC488 Installation Guide Dialer Options Dialer OptionsOpen/Close Reports Only if Previous Alarm Answering Machine Bypass Only When ArmedUse Bell 103 for FSK Format Disabled=CCITT V21 Open/Close Reports for Stay Mode 1 and Stay ModeICP-CC488 Installation Guide Access Codes Access CodesInstaller Code User CodesArm/Disarm User Code PriorityPriority Levels Arm OnlyZone Information Day Alarm InformationICP-CC488 Installation Guide Zone Information EOL Resistor ValueTamper Zone 1 3K3 Zone 5 6K8 Zone Options Zone ProgrammingZone Operating Information Zone Reporting InformationYou can program Zones 1 to 16 as any zone type Keyswitch Zone Delay-1 ZoneDelay-2 Zone Instant ZoneZone Not Used 13 24-Hour Fire ZoneChime Zone Zone Pulse CountKeyswitch Zone Options Delay Alarm ReportingSilent Alarm Latching Arm and Disarm in Away ModeMomentary Arm and Disarm in Away Mode Latching Arm in Stay ModeLatching Disarm from Stay Mode 1 or Stay Mode Momentary Arm in Away ModeSwinger Shutdown Count for Siren Swinger Shutdown Count for DialerZone Status Walk Test Report System Reporting InformationZone Status Zone Tamper Report Zone Status Bypass ReportsZone Status Sensor Watch Reports Zone Status Alarm Restore CodeRF Low Battery Report Zone Status Reporting OptionsOpen/Close Reports RF Receiver Trouble Restore ReportRF Dialer Options Open/Close Reporting OptionsSystem Status AC Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report Codepad Fire ReportSystem Status Access Denied System Status Low Battery ReportSystem Status Low Battery Restore Report System Status Reporting OptionsICP-CC488 Installation Guide Programmable Outputs Programmable OutputsTest Reporting Dialer Options Redirecting Outputs to the Codepad Buzzer Output Event TypesDay Alarm Enabled Entry Warning + Day Alarm ResettingExit Warning + Entry Warning + Day Alarm Resetting AUX Power Supply FailCodepad Fire Alarm Sensor Watch AlarmCodepad Medical Alarm Codepad Panic AlarmRadio Control Output 1 Not in Away Mode Fire Alarm VerificationRemote Control Radio Control Output 2 Not in Away ModeGlobal Chime Area 1 in Alarm Area 2 in AlarmMimic Zone Zone Not SealedOutput Polarity Output Timing System Event TimersICP-CC488 Installation Guide System Event Timers Pulsing PolaritiesExit Timer Programming Entry/Exit TimersEntry Timer Entry Guard Timer for Stay ModeSiren Run Time Auto Arming Pre-Alert TimerCodepad Lockout Time Siren Sound RateSystem and Consumer Options Strobe Indications for Radio Arm/Disarm Assign Button 4 To Operate Stay ModeAccess Denied Code Retries To Be Silent Codepad Panic To Be SilentConsumer Options Radio Input Options Partitioning Using Codepads in a Partitioned SystemICP-CC488 Installation Guide Partitioning 19.1 CP500 Master Partitioned LED CodepadZone Allocations Zone Allocations for Areas 1 Setting Up and Programming Codepads for PartitioningUser Code Allocations Detailed ExampleSetting Up an Area 2 Codepad Setting Up an Area 1 Codepad as the Main CodepadSetting Up an Area 1 Codepad Codepad Connections For Partitioning ExamplesICP-CC488 Installation Guide RF Information RF InformationRF Option Bit Using Hexadecimal Values for RF Device Mapping Default RF Device Mapping Devices 1 toDefault RF Device Mapping Devices 9 to Enable RF Jamming MonitorICP-CC488 Installation Guide Optional Equipment RF Device Signal Strength Devices 1 to 8 Read OnlyRF Device Signal Strength Devices 9 to 16 Read Only Optional Equipment21.4 CC891 Programming Key 21.5 CC816 Alarm Link Software21.3 SS914 Edmsat Satellite Siren ICP-CP500AW Eight Zone Area Addressable CodepadICP-CC488 Installation Guide Terminals and Descriptions Terminals and DescriptionsTerminal Descriptions Glossary Of Terms Stay Mode Domestic alarm reportsThat an alarm was sent out This mode. Only the installer can program these zonesDiagrams ICP-CC488 Wiring DiagramICP-CC488 Installation Guide Terminals and Descriptions Wiring and Power Up Operation Telecom Connection Diagram for AustraliaYellow wire Green wire Appendices Appendix B Test Reports Only When ArmedICP-CC488 Installation Guide Appendices Appendix a Telephone Anti JammingSpecifications SpecificationsWarranty Statement Software Version NumberTick ICP-CC488 Installation Guide Programming SheetsProgramming Sheets ICP-CC488 Programming SheetsDialing Format Telephone Line Fault OptionsAlarm Link Options ReservedUser Code Priority Levels Installer CodeDay Alarm Zones EOL Resistor ValueZone Pulse Count Settings ZonesZone Descriptions RF Low Battery ReportRF Receiver Trouble Restore Report Swinger Shutdown Count for SirenSystem Status AC Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status Low Battery ReportSpeaker Beep Volume Entry Guard Time for Stay ModeDelay Alarm Reporting Time Sensor Watch TimeZone Allocations for Area 1 and Area Zone Allocations Enabled for Area 1 and AreaRadio Input Options Domestic Telephone NumbersRF Options RF Device Signal Strength Devices 1 toRF Device Signal Strength Devices 9 to RF Device Mapping OptionSystem Time Disable Factory DefaultCountry Codes System DateICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Index Remote Connect Without Call Back Verification41Telephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02