ICP-CC488 Installation Guide 7.0

Programming

 

 

EN 35

When you enter Installer’s Programming Mode, you are automatically positioned at Location 000, the first digit of the Primary Telephone Number for Receiver 1. The codepad indicators show the current data stored in this location.

Table 34: Codepad Indicators

Data

 

 

Zone Indicators

 

 

 

Value

1

2

3

4

5

6

7

8

MAINS

0

1X

2

 

X

3

 

X

4

 

X

 

 

 

5

 

X

 

 

 

6

 

X

7

 

X

 

 

 

8

 

X

9

X

X

10

 

 

X

11

X

 

X

12

X

 

X

13

X

 

X

 

 

 

 

14

X

 

X

15

 

X

X

To move to a different programming location:

Enter the location number and press [AWAY]. For example, press [3 4][AWAY] to automatically step you to the beginning of the Subscriber ID Number for Receiver 1. The data stored in the new location appears.

To move to the next location:

Press [AWAY].

For example, if you are currently positioned at Location 034, press [AWAY] to step to Location 035.

To move to the previous location:

Press [STAY].

For example, if you are positioned at Location 035, press [STAY] to step back to Location 034.

To change data in the current location:

Enter the new value (0 to 15) and press [STAY]. The data is stored and you remain positioned at the same location. The new value is displayed using the codepad indicators (for example, if you enter [1 4] and press [STAY], the Zone 4 and MAINS indicators are lit).

To exit from Installer’s Programming Mode:

Enter command [9 6 0] and press [AWAY]. Two beeps sound and the STAY and AWAY indicators are extinguished. The system returns to the disarmed state and is now ready for use.

Refer to Section 7.4 Installer’s Programming Commands on page 36 for more information about using Installer’s Programming Mode.

7.2Programming with the Programming Key

The CC891 Programming Key allows you to store or copy programming information from your control panel. After storing information in the programming key, you can easily program other ICP-CC488 Control Panels with the same programming data. You can also use the programming key to back up existing information.

If you connect the programming key to the control panel when it is disarmed, the key automatically initiates a data transfer to the control panel’s memory.

If you have a new programming key, enter Installer’s Programming Mode, program the system as required, and then connect the programming key to the control panel.

To connect the programming key:

Locate the socket labeled PROGRAMMING KEY at the top of the printed circuit board (PCB) next to the Auxiliary Module socket (refer to Figure 24 on page 96). Observe the triangular markings on the PCB and align them with the markings on the programming key.

To copy data from the control panel data to the programming key:

1.Enter the Installer Code (the default is 1234) and press [#] to enter Installer’s Programming Mode.

2.Enter [9 6 2 #].

Refer to Section 7.4.4 Command 962 – Copy the Control Panel Memory to the Programming Key on page 37 for more information.

3.Enter [9 6 0 #] to exit from Installer’s Programming Mode.

Two beeps sound and the system returns to the disarmed state. Before removing the programming key, wait 2 sec for the activity LED to return to its normal state. The programming key becomes your standard data pattern for future control panel programming.

If you enter Installer’s Programming Mode, insert a programming key, and then change the data in any location, the data for both the programming key and the control panel is changed at the same time.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 35
Contents ICP-CC488 Installation GuideBosch Security Systems, Inc /08 F01U089457-02 ICP-CC488 Installation Guide NoticesCopyright Notice Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Tables FiguresUser Code Allocations Hexadecimal Values for Zone Nos Introduction ICP-CC488 FeaturesICP-CC488 Installation Guide Introduction Set the Date and Time ICP-CC488 Zone DefaultsZone Defaults for the ICP-CC488 Quick StartICP-CP508W Eight Zone LED Codepad Codepad IndicatorsICP-CC488 Installation Guide Codepad Indicators ICP-CP508LW Eight Zone LCD Codepad Mains IndicatorFault indicator Audible IndicatorsICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads ICP-CC488 Installation Guide System Operations Arming the System in Away ModeDisarming the System from Away Mode Arming the System in Stay ModeDisarming the System from Stay Mode Codepad Panic Alarm Codepad Duress AlarmStandard Isolating Codepad Fire AlarmCodepad Medical Alarm Isolating ZonesFault Descriptions Fault Analysis ModeAC Mains Failure System Fault indicatorsRemote Radio Transmitter Operations Fault Analysis ConditionsChanging or Deleting Remote Radio User Codes Indications from Remote Radio Transmitter OperationsRemote Radio User Code Priority Levels Add or Delete RF Wireless Devices Installer Code FunctionsICP-CC488 Installation Guide System Functions Installer Code FunctionsDomestic Dialing Digits Set the Number of Days until the First Test ReportChange Domestic Phone Numbers Telco Arm Sequence Codepad Indicators When Changing Phone NumbersExamples provided for this feature apply only to Australia Change Telco Arm/Disarm SequenceTurning Telephone Monitor Mode On and Off Setting Stay Mode 2 ZonesSatellite Siren Service Mode Event Memory Playback Telephone Monitor Mode IndicationsEvent Memory Recall Mode Event SequenceChanging and Deleting User Codes Master Code FunctionsMaster Code Functions Arm or Disarm Both Areas at the Same TimeChanging Domestic Phone Numbers User Numbers Displayed by the Codepad IndicatorsChanging and Deleting Remote Radio User Codes Codepad Indicators When Changing Domestic Telephone Numbers Turning Outputs On/Off When you program a # in the telco arm sequence, enter STAY2Event Non-volatile Memory Recall Mode Setting the Date and TimeHold-Down Functions Arm the System in Away ModeArm the System in Stay Mode User Code FunctionsHorn Speaker Test Turning Day Alarm On and OffFault Analysis Mode Reset Latching OutputsProgramming with the Remote Codepad ICP-CC488 Installation Guide Remote Arming by TelephoneRemote Arming by Telephone ProgrammingProgramming with the Programming Key ICP-CC488 Installation Guide ProgrammingCodepad Indicators Programming Option Bits Installer’s Programming CommandsInstaller’s Programming Mode Commands Command 959 Test the Programming KeyCommand 963 Copy the Programming Key to the Control Panel Command 960 Exit from Installers Programming ModeCommand 965 Set Up Domestic Dialing Format Command 964 Erase the Programming KeyCommand 965 Defaults Disable Factory DefaultsExample Auto Step Enabled Example Auto Step DisabledRemote Connection with Customer Control Alarm Link SoftwareICP-CC488 Installation Guide Alarm Link Software Remote ConnectAlarm Link Options Domestic Dialing ICP-CC488 Installation Guide Domestic DialingEnable Alarm Link Call Back Terminate Alarm Link Connection on AlarmTransmission Formats Setting Up and Programming Domestic ReportingICP-CC488 Installation Guide Dialer Reporting Formats Dialer Reporting FormatsExample Reporting in 4 + 2 Format + 2 Reporting Format Contact ID Format BreakdownPoint ID Codes 10.1.4 4 + 2 Reporting FormatBasic Pager Reporting Format + 2 Transmission Code Descriptions14.3.2 Basic Pager Display Basic Pager Display Information ICP-CC488 Installation Guide Dialer InformationDialer Information Dialing Digits Primary Telephone Number for Receiver 1 and ReceiverSecondary Telephone Number for Receiver 1 and Receiver Handshake Tone for Receiver 1 and ReceiverTelco Arming Sequence Transmission Format for Receiver 1 and ReceiverSubscriber ID Number for Receiver 1 and Receiver Dialing FormatAnswering Machine Bypass Telco Disarming SequenceCall Back Telephone Number Ring CountDialer Options Telephone Line Fault OptionsICP-CC488 Installation Guide Dialer Options Dialer OptionsOpen/Close Reports for Stay Mode 1 and Stay Mode Answering Machine Bypass Only When ArmedUse Bell 103 for FSK Format Disabled=CCITT V21 Open/Close Reports Only if Previous AlarmUser Codes Access CodesInstaller Code ICP-CC488 Installation Guide Access CodesArm Only User Code PriorityPriority Levels Arm/DisarmEOL Resistor Value Day Alarm InformationICP-CC488 Installation Guide Zone Information Zone InformationTamper Zone 1 3K3 Zone 5 6K8 Zone Reporting Information Zone ProgrammingZone Operating Information Zone OptionsYou can program Zones 1 to 16 as any zone type Instant Zone Delay-1 ZoneDelay-2 Zone Keyswitch ZoneZone Pulse Count 13 24-Hour Fire ZoneChime Zone Zone Not UsedLatching Arm and Disarm in Away Mode Delay Alarm ReportingSilent Alarm Keyswitch Zone OptionsMomentary Arm in Away Mode Latching Arm in Stay ModeLatching Disarm from Stay Mode 1 or Stay Mode Momentary Arm and Disarm in Away ModeSwinger Shutdown Count for Dialer Swinger Shutdown Count for SirenZone Status Bypass Reports System Reporting InformationZone Status Zone Tamper Report Zone Status Walk Test ReportZone Status Reporting Options Zone Status Alarm Restore CodeRF Low Battery Report Zone Status Sensor Watch ReportsOpen/Close Reporting Options RF Receiver Trouble Restore ReportRF Dialer Options Open/Close ReportsCodepad Fire Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportSystem Status Reporting Options System Status Low Battery ReportSystem Status Low Battery Restore Report System Status Access DeniedTest Reporting Dialer Options ICP-CC488 Installation Guide Programmable OutputsProgrammable Outputs Output Event Types Redirecting Outputs to the Codepad BuzzerAUX Power Supply Fail Entry Warning + Day Alarm ResettingExit Warning + Entry Warning + Day Alarm Resetting Day Alarm EnabledCodepad Panic Alarm Sensor Watch AlarmCodepad Medical Alarm Codepad Fire AlarmRadio Control Output 2 Not in Away Mode Fire Alarm VerificationRemote Control Radio Control Output 1 Not in Away ModeZone Not Sealed Area 1 in Alarm Area 2 in AlarmMimic Zone Global ChimeOutput Polarity Pulsing Polarities System Event TimersICP-CC488 Installation Guide System Event Timers Output TimingEntry Guard Timer for Stay Mode Programming Entry/Exit TimersEntry Timer Exit TimerSiren Sound Rate Auto Arming Pre-Alert TimerCodepad Lockout Time Siren Run TimeSystem and Consumer Options Codepad Panic To Be Silent Assign Button 4 To Operate Stay ModeAccess Denied Code Retries To Be Silent Strobe Indications for Radio Arm/DisarmConsumer Options Radio Input Options 19.1 CP500 Master Partitioned LED Codepad Using Codepads in a Partitioned SystemICP-CC488 Installation Guide Partitioning PartitioningZone Allocations Detailed Example Setting Up and Programming Codepads for PartitioningUser Code Allocations Zone Allocations for Areas 1Codepad Connections For Partitioning Examples Setting Up an Area 1 Codepad as the Main CodepadSetting Up an Area 1 Codepad Setting Up an Area 2 CodepadRF Option Bit ICP-CC488 Installation Guide RF InformationRF Information Enable RF Jamming Monitor Default RF Device Mapping Devices 1 toDefault RF Device Mapping Devices 9 to Using Hexadecimal Values for RF Device MappingOptional Equipment RF Device Signal Strength Devices 1 to 8 Read OnlyRF Device Signal Strength Devices 9 to 16 Read Only ICP-CC488 Installation Guide Optional EquipmentICP-CP500AW Eight Zone Area Addressable Codepad 21.5 CC816 Alarm Link Software21.3 SS914 Edmsat Satellite Siren 21.4 CC891 Programming KeyTerminal Descriptions ICP-CC488 Installation Guide Terminals and DescriptionsTerminals and Descriptions Glossary Of Terms This mode. Only the installer can program these zones Domestic alarm reportsThat an alarm was sent out Stay ModeICP-CC488 Wiring Diagram DiagramsICP-CC488 Installation Guide Terminals and Descriptions Telecom Connection Diagram for Australia Wiring and Power Up OperationYellow wire Green wire Appendix a Telephone Anti Jamming Appendix B Test Reports Only When ArmedICP-CC488 Installation Guide Appendices AppendicesSoftware Version Number SpecificationsWarranty Statement SpecificationsICP-CC488 Programming Sheets ICP-CC488 Installation Guide Programming SheetsProgramming Sheets TickReserved Telephone Line Fault OptionsAlarm Link Options Dialing FormatEOL Resistor Value Installer CodeDay Alarm Zones User Code Priority LevelsZones Zone Pulse Count SettingsSwinger Shutdown Count for Siren RF Low Battery ReportRF Receiver Trouble Restore Report Zone DescriptionsSystem Status Low Battery Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportSensor Watch Time Entry Guard Time for Stay ModeDelay Alarm Reporting Time Speaker Beep VolumeDomestic Telephone Numbers Zone Allocations Enabled for Area 1 and AreaRadio Input Options Zone Allocations for Area 1 and AreaRF Device Mapping Option RF Device Signal Strength Devices 1 toRF Device Signal Strength Devices 9 to RF OptionsSystem Date Disable Factory DefaultCountry Codes System TimeICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Remote Connect Without Call Back Verification41 IndexTelephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02