Bosch Appliances ICP-CC488 manual Codepad Fire Alarm, Codepad Medical Alarm, Isolating Zones

Page 17

ICP-CC488 Installation Guide 3.0

System Operations

 

 

EN 17

3.9Codepad Fire Alarm

An audible codepad Fire Alarm activates when a user presses [4] and [6] on the remote codepad simultaneously. A distinct fire sound emits through the horn speaker to indicate this type of alarm. The fire sound is different than the burglary sound.

Select Option 2 in Location 493 to program the codepad Fire Alarm as silent (refer to Section 18.2 System Options 2 on page 81). To disable the codepad Fire Alarm Report, program Locations 407 and 408 to 0 (refer to Section 15.17 Codepad Fire Report). A codepad Fire Alarm transmits a Contact ID Event Code 110 to a base station receiver.

3.10Codepad Medical Alarm

An audible codepad Medical Alarm activates when a user presses [7] and [9] simultaneously.

Select Option 4 in Location 493 to program codepad Medical Alarm as silent (refer to Section 18.2 System Options 2 on page 81). To disable reporting of the codepad Medical Alarm Report, program Locations 409 and 410 to 0 (refer to Section 15.18 Codepad Medical Report). A codepad Medical Alarm transmits a Contact ID Event Code 100 to a base station receiver.

3.11Isolating Zones

Isolating zones allows you to manually disable one or more zones before arming the system in AWAY Mode, STAY Mode 1, or STAY Mode 2. When a zone is isolated, access is allowed into that zone when the system is armed without activating an alarm.

For example, you might want to isolate a zone before arming the system because a zone passive infrared (PIR) detector is activating false alarms or because you need to leave a pet inside a particular zone while you are away.

You can isolate zones using one of two methods. One method requires a valid User Code and the other does not. The ability to isolate zones is determined by the priority level assigned to each User Code holder. Some User Code holders cannot isolate zones. Refer to Section 13.3 User Code Priority for more information. By default, the standard isolation method is used.

Zones that are manually isolated using this method transmit a Zone Bypass Report (Contact ID Event Code 570) for each isolated zone when the system is armed. A Zone Bypass Restore Report is transmitted when the system is disarmed.

When you select a 24-Hour Burglary Zone to be isolated, a Contact ID Event Code 572 is sent. If you select a 24-Hour Fire Zone to be isolated, a Contact ID Event Code 571 is sent.

3.11.1Standard Isolating

Standard isolating allows any operator to isolate zones because no code is required.

1.Press [STAY] twice.

Three beeps sound and the STAY indicator flashes.

2.Enter the number of the zone to be isolated and press [STAY].

The indicator for the zone flashes.

24-Hour zones are automatically isolated as soon as you press [STAY]. All other Burglary Zones are automatically isolated only after the system is armed.

3.Repeat Step 2 for each zone you want to isolate.

As each zone is selected to be isolated, the corresponding zone indicator flashes. If you make a mistake, enter the incorrect zone number and press [STAY]. This zone is no longer selected to be isolated and the zone indicator is extinguished.

4.Press [AWAY].

Two beeps sound and the system returns to the disarmed state.

The indicators for the selected zones continue to flash until the next time the system is disarmed.

Example

To manually isolate zones 1, 3, and 4, press:

[STAY][STAY][1][STAY][3][STAY][4][STAY]

[AWAY]

3.11.2Code to Isolate

The code to isolate method permits only those User Code holders with a priority level that includes Code to Isolate. The standard isolating method is disabled for any User Code with this priority level set.

1.Press [STAY].

2.Enter your code and press [STAY].

Three beeps sound and the STAY indicator flashes.

If you attempt to enter isolating mode with a User Code that is not set for Code to Isolate, the system ignores the attempt.

3.Enter the number of the zone to be isolated and press [STAY].

The indicator for the zone flashes.

24-Hour zones are automatically isolated as soon you press [STAY]. All other Burglary zones are automatically isolated only after the system is armed.

4.Repeat Step 3 for each zone you want to isolate.

As each zone is selected to be isolated, the corresponding zone indicator flashes. If you make a mistake, enter the incorrect zone number and press [STAY]. This zone is no longer selected to be isolated and the zone indicator is extinguished.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 17
Contents ICP-CC488 Installation GuideBosch Security Systems, Inc /08 F01U089457-02 ICP-CC488 Installation Guide NoticesCopyright Notice Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Tables FiguresUser Code Allocations Hexadecimal Values for Zone Nos Introduction ICP-CC488 FeaturesICP-CC488 Installation Guide Introduction Zone Defaults for the ICP-CC488 ICP-CC488 Zone DefaultsQuick Start Set the Date and TimeICP-CP508W Eight Zone LED Codepad Codepad IndicatorsICP-CC488 Installation Guide Codepad Indicators Fault indicator Mains IndicatorAudible Indicators ICP-CP508LW Eight Zone LCD CodepadICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads Disarming the System from Away Mode Arming the System in Away ModeArming the System in Stay Mode ICP-CC488 Installation Guide System OperationsDisarming the System from Stay Mode Codepad Panic Alarm Codepad Duress AlarmCodepad Medical Alarm Codepad Fire AlarmIsolating Zones Standard IsolatingFault Descriptions Fault Analysis ModeAC Mains Failure System Fault indicatorsRemote Radio Transmitter Operations Fault Analysis ConditionsChanging or Deleting Remote Radio User Codes Indications from Remote Radio Transmitter OperationsRemote Radio User Code Priority Levels ICP-CC488 Installation Guide System Functions Installer Code FunctionsInstaller Code Functions Add or Delete RF Wireless DevicesDomestic Dialing Digits Set the Number of Days until the First Test ReportChange Domestic Phone Numbers Examples provided for this feature apply only to Australia Codepad Indicators When Changing Phone NumbersChange Telco Arm/Disarm Sequence Telco Arm SequenceTurning Telephone Monitor Mode On and Off Setting Stay Mode 2 ZonesSatellite Siren Service Mode Event Memory Recall Mode Telephone Monitor Mode IndicationsEvent Sequence Event Memory PlaybackMaster Code Functions Master Code FunctionsArm or Disarm Both Areas at the Same Time Changing and Deleting User CodesChanging Domestic Phone Numbers User Numbers Displayed by the Codepad IndicatorsChanging and Deleting Remote Radio User Codes Codepad Indicators When Changing Domestic Telephone Numbers Turning Outputs On/Off When you program a # in the telco arm sequence, enter STAY2Event Non-volatile Memory Recall Mode Setting the Date and TimeArm the System in Stay Mode Arm the System in Away ModeUser Code Functions Hold-Down FunctionsFault Analysis Mode Turning Day Alarm On and OffReset Latching Outputs Horn Speaker TestRemote Arming by Telephone ICP-CC488 Installation Guide Remote Arming by TelephoneProgramming Programming with the Remote CodepadProgramming with the Programming Key ICP-CC488 Installation Guide ProgrammingCodepad Indicators Installer’s Programming Mode Commands Installer’s Programming CommandsCommand 959 Test the Programming Key Programming Option BitsCommand 963 Copy the Programming Key to the Control Panel Command 960 Exit from Installers Programming ModeCommand 965 Set Up Domestic Dialing Format Command 964 Erase the Programming KeyExample Auto Step Enabled Disable Factory DefaultsExample Auto Step Disabled Command 965 DefaultsICP-CC488 Installation Guide Alarm Link Software Alarm Link SoftwareRemote Connect Remote Connection with Customer ControlAlarm Link Options Enable Alarm Link Call Back ICP-CC488 Installation Guide Domestic DialingTerminate Alarm Link Connection on Alarm Domestic DialingICP-CC488 Installation Guide Dialer Reporting Formats Setting Up and Programming Domestic ReportingDialer Reporting Formats Transmission FormatsPoint ID Codes Contact ID Format Breakdown10.1.4 4 + 2 Reporting Format Example Reporting in 4 + 2 Format + 2 Reporting FormatBasic Pager Reporting Format + 2 Transmission Code Descriptions14.3.2 Basic Pager Display Basic Pager Display Information ICP-CC488 Installation Guide Dialer InformationDialer Information Secondary Telephone Number for Receiver 1 and Receiver Primary Telephone Number for Receiver 1 and ReceiverHandshake Tone for Receiver 1 and Receiver Dialing DigitsSubscriber ID Number for Receiver 1 and Receiver Transmission Format for Receiver 1 and ReceiverDialing Format Telco Arming SequenceCall Back Telephone Number Telco Disarming SequenceRing Count Answering Machine BypassICP-CC488 Installation Guide Dialer Options Telephone Line Fault OptionsDialer Options Dialer OptionsUse Bell 103 for FSK Format Disabled=CCITT V21 Answering Machine Bypass Only When ArmedOpen/Close Reports Only if Previous Alarm Open/Close Reports for Stay Mode 1 and Stay ModeInstaller Code Access CodesICP-CC488 Installation Guide Access Codes User CodesPriority Levels User Code PriorityArm/Disarm Arm OnlyICP-CC488 Installation Guide Zone Information Day Alarm InformationZone Information EOL Resistor ValueTamper Zone 1 3K3 Zone 5 6K8 Zone Operating Information Zone ProgrammingZone Options Zone Reporting InformationYou can program Zones 1 to 16 as any zone type Delay-2 Zone Delay-1 ZoneKeyswitch Zone Instant ZoneChime Zone 13 24-Hour Fire ZoneZone Not Used Zone Pulse CountSilent Alarm Delay Alarm ReportingKeyswitch Zone Options Latching Arm and Disarm in Away ModeLatching Disarm from Stay Mode 1 or Stay Mode Latching Arm in Stay ModeMomentary Arm and Disarm in Away Mode Momentary Arm in Away ModeSwinger Shutdown Count for Dialer Swinger Shutdown Count for SirenZone Status Zone Tamper Report System Reporting InformationZone Status Walk Test Report Zone Status Bypass ReportsRF Low Battery Report Zone Status Alarm Restore CodeZone Status Sensor Watch Reports Zone Status Reporting OptionsRF Dialer Options RF Receiver Trouble Restore ReportOpen/Close Reports Open/Close Reporting OptionsSystem Status AUX Power Supply Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AC Fail Restore Report Codepad Fire ReportSystem Status Low Battery Restore Report System Status Low Battery ReportSystem Status Access Denied System Status Reporting OptionsTest Reporting Dialer Options ICP-CC488 Installation Guide Programmable OutputsProgrammable Outputs Output Event Types Redirecting Outputs to the Codepad BuzzerExit Warning + Entry Warning + Day Alarm Resetting Entry Warning + Day Alarm ResettingDay Alarm Enabled AUX Power Supply FailCodepad Medical Alarm Sensor Watch AlarmCodepad Fire Alarm Codepad Panic AlarmRemote Control Fire Alarm VerificationRadio Control Output 1 Not in Away Mode Radio Control Output 2 Not in Away ModeMimic Zone Area 1 in Alarm Area 2 in AlarmGlobal Chime Zone Not SealedOutput Polarity ICP-CC488 Installation Guide System Event Timers System Event TimersOutput Timing Pulsing PolaritiesEntry Timer Programming Entry/Exit TimersExit Timer Entry Guard Timer for Stay ModeCodepad Lockout Time Auto Arming Pre-Alert TimerSiren Run Time Siren Sound RateSystem and Consumer Options Access Denied Code Retries To Be Silent Assign Button 4 To Operate Stay ModeStrobe Indications for Radio Arm/Disarm Codepad Panic To Be SilentConsumer Options Radio Input Options ICP-CC488 Installation Guide Partitioning Using Codepads in a Partitioned SystemPartitioning 19.1 CP500 Master Partitioned LED CodepadZone Allocations User Code Allocations Setting Up and Programming Codepads for PartitioningZone Allocations for Areas 1 Detailed ExampleSetting Up an Area 1 Codepad Setting Up an Area 1 Codepad as the Main CodepadSetting Up an Area 2 Codepad Codepad Connections For Partitioning ExamplesRF Option Bit ICP-CC488 Installation Guide RF InformationRF Information Default RF Device Mapping Devices 9 to Default RF Device Mapping Devices 1 toUsing Hexadecimal Values for RF Device Mapping Enable RF Jamming MonitorRF Device Signal Strength Devices 9 to 16 Read Only RF Device Signal Strength Devices 1 to 8 Read OnlyICP-CC488 Installation Guide Optional Equipment Optional Equipment21.3 SS914 Edmsat Satellite Siren 21.5 CC816 Alarm Link Software21.4 CC891 Programming Key ICP-CP500AW Eight Zone Area Addressable CodepadTerminal Descriptions ICP-CC488 Installation Guide Terminals and DescriptionsTerminals and Descriptions Glossary Of Terms That an alarm was sent out Domestic alarm reportsStay Mode This mode. Only the installer can program these zonesICP-CC488 Wiring Diagram DiagramsICP-CC488 Installation Guide Terminals and Descriptions Telecom Connection Diagram for Australia Wiring and Power Up OperationYellow wire Green wire ICP-CC488 Installation Guide Appendices Appendix B Test Reports Only When ArmedAppendices Appendix a Telephone Anti JammingWarranty Statement SpecificationsSpecifications Software Version NumberProgramming Sheets ICP-CC488 Installation Guide Programming SheetsTick ICP-CC488 Programming SheetsAlarm Link Options Telephone Line Fault OptionsDialing Format ReservedDay Alarm Zones Installer CodeUser Code Priority Levels EOL Resistor ValueZones Zone Pulse Count SettingsRF Receiver Trouble Restore Report RF Low Battery ReportZone Descriptions Swinger Shutdown Count for SirenSystem Status AUX Power Supply Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AC Fail Restore Report System Status Low Battery ReportDelay Alarm Reporting Time Entry Guard Time for Stay ModeSpeaker Beep Volume Sensor Watch TimeRadio Input Options Zone Allocations Enabled for Area 1 and AreaZone Allocations for Area 1 and Area Domestic Telephone NumbersRF Device Signal Strength Devices 9 to RF Device Signal Strength Devices 1 toRF Options RF Device Mapping OptionCountry Codes Disable Factory DefaultSystem Time System DateICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Remote Connect Without Call Back Verification41 IndexTelephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02