Page 36

ICP-CC488 Installation Guide 7.0

Programming

 

 

EN 36

If you do not enter Installer’s Programming Mode first, connecting the CC891 Programming Key to the control panel when the programming key memory is blank corrupts the control panel’s memory. If this occurs, you must return the control panel to Bosch Security Systems, Inc. to unlock the control panel’s memory. A service fee will be charged.

7.3Programming Option Bits

When programming these locations, each location has four options. You can select one, two, three, or all four options for each location, but you can program only one value for the location. Calculate this value by adding the option bit numbers together.

Example

If you want to select Options 1, 2, and 4 for Location 177, add the numbers and program the sum. In this example, program a 7 in the location (1 + 2 + 4 = 7).

Table 35: Programming Option Bits Example

Option Description

1Allow dialer reporting functions

2Enable remote arming by telephone

4Enable answering machine bypass only when armed

8Enabled = Use Bell 103 for FSK format Disabled = CCITT V21 format

7.4Installer’s Programming Commands

You can use ten commands in Installer’s Programming Mode. To issue the command, enter the command number and press [#].

Table 36: Installer’s Programming Mode Commands

Command Function

959Test the programming key Refer to Section 7.4.1.

960Exit from Installer’s Programming Mode Refer to Section 7.4.2.

961Reset the control panel to factory defaults Refer to Section 7.4.3.

962Copy the control panel memory to the programming key

Refer to Section 7.4.4.

963Copy the programming key data to the control panel memory

Refer to Section 7.4.5.

964Erase the programming key Refer to Section 7.4.6.

965Set up domestic dialing format Refer to Section 7.4.7.

966Enable/disable the automatic stepping of locations during programming

Refer to Section 7.4.8.

999Display the software version number or control panel type

Refer to Section 7.4.9.

7.4.1Command 959 – Test the Programming Key

This command initiates a test of the programming key. You can use the CC891 Programming Key only with the ICP-CC488 Control Panel.

The programming key test is non-destructive, and any data in the programming key remains after the test is completed. One long beep indicates that the programming key test failed. Two beeps indicates a successful test.

If you remove the programming key before the test is finished, the programming key data becomes corrupt. Do not remove the programming key while the activity LED is lit or pulsing rapidly.

To test the programming key:

1.Enter the Installer Code (the default is 1234) and press [#] to enter Installer’s Programming Mode. Two beeps sound and the STAY and AWAY indicators flash on the remote codepad to indicate you entered Installer’s Programming Mode. The remote codepad displays the data stored in Location 000.

2.Connect the programming key to the PROGRAMMING KEY pins (next to the Auxiliary Module socket) at the top of the control panel printed circuit board.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 36
Contents Installation Guide ICP-CC488ICP-CC488 Installation Guide Notices Copyright NoticeBosch Security Systems, Inc /08 F01U089457-02 Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Figures TablesUser Code Allocations Hexadecimal Values for Zone Nos ICP-CC488 Features ICP-CC488 Installation Guide IntroductionIntroduction ICP-CC488 Zone Defaults Zone Defaults for the ICP-CC488Quick Start Set the Date and TimeCodepad Indicators ICP-CC488 Installation Guide Codepad IndicatorsICP-CP508W Eight Zone LED Codepad Mains Indicator Fault indicatorAudible Indicators ICP-CP508LW Eight Zone LCD CodepadICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads Arming the System in Away Mode Disarming the System from Away ModeArming the System in Stay Mode ICP-CC488 Installation Guide System OperationsDisarming the System from Stay Mode Codepad Duress Alarm Codepad Panic AlarmCodepad Fire Alarm Codepad Medical AlarmIsolating Zones Standard IsolatingFault Analysis Mode Fault DescriptionsSystem Fault indicators AC Mains FailureFault Analysis Conditions Remote Radio Transmitter OperationsIndications from Remote Radio Transmitter Operations Remote Radio User Code Priority LevelsChanging or Deleting Remote Radio User Codes Installer Code Functions ICP-CC488 Installation Guide System FunctionsInstaller Code Functions Add or Delete RF Wireless DevicesSet the Number of Days until the First Test Report Change Domestic Phone NumbersDomestic Dialing Digits Codepad Indicators When Changing Phone Numbers Examples provided for this feature apply only to AustraliaChange Telco Arm/Disarm Sequence Telco Arm SequenceSetting Stay Mode 2 Zones Satellite Siren Service ModeTurning Telephone Monitor Mode On and Off Telephone Monitor Mode Indications Event Memory Recall ModeEvent Sequence Event Memory PlaybackMaster Code Functions Master Code FunctionsArm or Disarm Both Areas at the Same Time Changing and Deleting User CodesUser Numbers Displayed by the Codepad Indicators Changing and Deleting Remote Radio User CodesChanging Domestic Phone Numbers Codepad Indicators When Changing Domestic Telephone Numbers When you program a # in the telco arm sequence, enter STAY2 Turning Outputs On/OffSetting the Date and Time Event Non-volatile Memory Recall ModeArm the System in Away Mode Arm the System in Stay ModeUser Code Functions Hold-Down FunctionsTurning Day Alarm On and Off Fault Analysis ModeReset Latching Outputs Horn Speaker TestICP-CC488 Installation Guide Remote Arming by Telephone Remote Arming by TelephoneProgramming Programming with the Remote CodepadICP-CC488 Installation Guide Programming Codepad IndicatorsProgramming with the Programming Key Installer’s Programming Commands Installer’s Programming Mode CommandsCommand 959 Test the Programming Key Programming Option BitsCommand 960 Exit from Installers Programming Mode Command 963 Copy the Programming Key to the Control PanelCommand 964 Erase the Programming Key Command 965 Set Up Domestic Dialing FormatDisable Factory Defaults Example Auto Step EnabledExample Auto Step Disabled Command 965 DefaultsAlarm Link Software ICP-CC488 Installation Guide Alarm Link SoftwareRemote Connect Remote Connection with Customer ControlAlarm Link Options ICP-CC488 Installation Guide Domestic Dialing Enable Alarm Link Call BackTerminate Alarm Link Connection on Alarm Domestic DialingSetting Up and Programming Domestic Reporting ICP-CC488 Installation Guide Dialer Reporting FormatsDialer Reporting Formats Transmission FormatsContact ID Format Breakdown Point ID Codes10.1.4 4 + 2 Reporting Format Example Reporting in 4 + 2 Format + 2 Reporting Format+ 2 Transmission Code Descriptions Basic Pager Reporting Format14.3.2 Basic Pager Display ICP-CC488 Installation Guide Dialer Information Dialer InformationBasic Pager Display Information Primary Telephone Number for Receiver 1 and Receiver Secondary Telephone Number for Receiver 1 and ReceiverHandshake Tone for Receiver 1 and Receiver Dialing DigitsTransmission Format for Receiver 1 and Receiver Subscriber ID Number for Receiver 1 and ReceiverDialing Format Telco Arming SequenceTelco Disarming Sequence Call Back Telephone NumberRing Count Answering Machine BypassTelephone Line Fault Options ICP-CC488 Installation Guide Dialer OptionsDialer Options Dialer OptionsAnswering Machine Bypass Only When Armed Use Bell 103 for FSK Format Disabled=CCITT V21Open/Close Reports Only if Previous Alarm Open/Close Reports for Stay Mode 1 and Stay ModeAccess Codes Installer CodeICP-CC488 Installation Guide Access Codes User CodesUser Code Priority Priority LevelsArm/Disarm Arm OnlyDay Alarm Information ICP-CC488 Installation Guide Zone InformationZone Information EOL Resistor ValueTamper Zone 1 3K3 Zone 5 6K8 Zone Programming Zone Operating InformationZone Options Zone Reporting InformationYou can program Zones 1 to 16 as any zone type Delay-1 Zone Delay-2 ZoneKeyswitch Zone Instant Zone13 24-Hour Fire Zone Chime ZoneZone Not Used Zone Pulse CountDelay Alarm Reporting Silent AlarmKeyswitch Zone Options Latching Arm and Disarm in Away ModeLatching Arm in Stay Mode Latching Disarm from Stay Mode 1 or Stay ModeMomentary Arm and Disarm in Away Mode Momentary Arm in Away ModeSwinger Shutdown Count for Siren Swinger Shutdown Count for DialerSystem Reporting Information Zone Status Zone Tamper ReportZone Status Walk Test Report Zone Status Bypass ReportsZone Status Alarm Restore Code RF Low Battery ReportZone Status Sensor Watch Reports Zone Status Reporting OptionsRF Receiver Trouble Restore Report RF Dialer OptionsOpen/Close Reports Open/Close Reporting OptionsSystem Status AUX Power Supply Fail Report System Status AUX Power Supply Fail Restore ReportSystem Status AC Fail Restore Report Codepad Fire ReportSystem Status Low Battery Report System Status Low Battery Restore ReportSystem Status Access Denied System Status Reporting OptionsICP-CC488 Installation Guide Programmable Outputs Programmable OutputsTest Reporting Dialer Options Redirecting Outputs to the Codepad Buzzer Output Event TypesEntry Warning + Day Alarm Resetting Exit Warning + Entry Warning + Day Alarm ResettingDay Alarm Enabled AUX Power Supply FailSensor Watch Alarm Codepad Medical AlarmCodepad Fire Alarm Codepad Panic AlarmFire Alarm Verification Remote ControlRadio Control Output 1 Not in Away Mode Radio Control Output 2 Not in Away ModeArea 1 in Alarm Area 2 in Alarm Mimic ZoneGlobal Chime Zone Not SealedOutput Polarity System Event Timers ICP-CC488 Installation Guide System Event TimersOutput Timing Pulsing PolaritiesProgramming Entry/Exit Timers Entry TimerExit Timer Entry Guard Timer for Stay ModeAuto Arming Pre-Alert Timer Codepad Lockout TimeSiren Run Time Siren Sound RateSystem and Consumer Options Assign Button 4 To Operate Stay Mode Access Denied Code Retries To Be SilentStrobe Indications for Radio Arm/Disarm Codepad Panic To Be SilentConsumer Options Radio Input Options Using Codepads in a Partitioned System ICP-CC488 Installation Guide PartitioningPartitioning 19.1 CP500 Master Partitioned LED CodepadZone Allocations Setting Up and Programming Codepads for Partitioning User Code AllocationsZone Allocations for Areas 1 Detailed ExampleSetting Up an Area 1 Codepad as the Main Codepad Setting Up an Area 1 CodepadSetting Up an Area 2 Codepad Codepad Connections For Partitioning ExamplesICP-CC488 Installation Guide RF Information RF InformationRF Option Bit Default RF Device Mapping Devices 1 to Default RF Device Mapping Devices 9 toUsing Hexadecimal Values for RF Device Mapping Enable RF Jamming MonitorRF Device Signal Strength Devices 1 to 8 Read Only RF Device Signal Strength Devices 9 to 16 Read OnlyICP-CC488 Installation Guide Optional Equipment Optional Equipment21.5 CC816 Alarm Link Software 21.3 SS914 Edmsat Satellite Siren21.4 CC891 Programming Key ICP-CP500AW Eight Zone Area Addressable CodepadICP-CC488 Installation Guide Terminals and Descriptions Terminals and DescriptionsTerminal Descriptions Glossary Of Terms Domestic alarm reports That an alarm was sent outStay Mode This mode. Only the installer can program these zonesDiagrams ICP-CC488 Wiring DiagramICP-CC488 Installation Guide Terminals and Descriptions Wiring and Power Up Operation Telecom Connection Diagram for AustraliaYellow wire Green wire Appendix B Test Reports Only When Armed ICP-CC488 Installation Guide AppendicesAppendices Appendix a Telephone Anti JammingSpecifications Warranty StatementSpecifications Software Version NumberICP-CC488 Installation Guide Programming Sheets Programming SheetsTick ICP-CC488 Programming SheetsTelephone Line Fault Options Alarm Link OptionsDialing Format ReservedInstaller Code Day Alarm ZonesUser Code Priority Levels EOL Resistor ValueZone Pulse Count Settings ZonesRF Low Battery Report RF Receiver Trouble Restore ReportZone Descriptions Swinger Shutdown Count for SirenSystem Status AUX Power Supply Fail Report System Status AUX Power Supply Fail Restore ReportSystem Status AC Fail Restore Report System Status Low Battery ReportEntry Guard Time for Stay Mode Delay Alarm Reporting TimeSpeaker Beep Volume Sensor Watch TimeZone Allocations Enabled for Area 1 and Area Radio Input OptionsZone Allocations for Area 1 and Area Domestic Telephone NumbersRF Device Signal Strength Devices 1 to RF Device Signal Strength Devices 9 toRF Options RF Device Mapping OptionDisable Factory Default Country CodesSystem Time System DateICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Index Remote Connect Without Call Back Verification41Telephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02