Bosch Appliances ICP-CC488 manual Dialer Options, Telephone Line Fault Options

Page 52

ICP-CC488 Installation Guide 12.0

Dialer Options

 

 

EN 52

Program the Ring Count to 14 to enable Answering Machine Bypass in the secondary mode. In this case, call the control panel and allow the phone to ring no more than twice and hang up. Wait a minimum of 8 sec and call the control panel again. The control panel answers on the first ring. If you do not wait the 8 sec, the control panel does not answer the call. To enable Answering Machine Bypass only when the system is armed, select Option 2 in Location 177 (refer to Section 12.1 Dialer Options 1 on page 52).

Set the Ring Count for the answering machine or facsimile machine to a value greater than two rings. Four to six rings is preferred.

Program a 0 into this location to disable the control panel from answering an incoming call.

11.11 Telephone Line Fault Options

Location 176

Default 0

1Display FAULT indicator when telephone line fails

2 Sound alarm when system is armed

4 Sound alarm when system is disarmed

8 Reserved

This location has three options. You can select any combination of these options by programming a single value. Calculate this value by adding the option bit numbers together. Refer to Section 7.3 Programming Option Bits on page 36 for more information.

The control panel monitors the telephone line. If the telephone line is cut or disconnected for longer than 40 sec, the control panel lights the FAULT indicator on the codepad. The FAULT indicator is extinguished after the telephone line is restored for longer than 40 sec.

Options 2 and 4 do not operate unless you also enable Option 1.

1 – Display FAULT indicator When the Telephone Line Fails

When this options is selected, the FAULT indicator flashes and the codepad buzzer beeps once per min if the control panel detects that the telephone line is disconnected. Refer to Section 3.13 Fault Descriptions on page 18 for more information.

2 – Sound Alarm When System Is Armed

You must also select Option 1 to use this option. If the control panel detects that the telephone line is disconnected when the system is armed, the horn speaker, bell, and strobe outputs are activated. If only one audible alarm per arming cycle is required, select the Lockout Telephone Line Fail Alarm option (2) in Location 179 (refer to Section 12.3 Dialer Options 3 on page 53).

4 – Sound Alarm when System Is Disarmed

You must also select Option 1 to use this option. If the control panel detects that the telephone line is disconnected when the system is disarmed, the horn speaker, bell, and strobe outputs are activated. If only one audible alarm per arming cycle is required, select the Lockout Telephone Line Fail Alarm option (2) in Location 179 (refer to Section 12.3 Dialer Options 3 on page 53).

If you program 7 in this location, the horn speaker, bell, strobe, and EDMSAT outputs are all activated when the system is armed or disarmed.

12.0 Dialer Options

Locations 177, 178, 179, and 180 have up to four options per location available for programming. You can select any combination of the options by programming a single value. Calculate this value by adding the option bit numbers together. Refer to Section 7.3 Programming Option Bits on page 36 for more information.

12.1Dialer Options 1

Location 177

1Dialer reporting functions allowed

2Remote arming by telephone allowed

4Answering machine bypass only when armed

8Bell 103 used for FSK format (disabled = CCITT V21)

1 – Dialer Reporting Functions Allowed

If you select this option, the dialer operates for all functions.

If you do not select this option, the communication dialer does not operate.

Upload/Download using the CC816 Alarm Link Software and telephone remote arming remains operational regardless of this setting.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 52
Contents Installation Guide ICP-CC488Copyright Notice ICP-CC488 Installation Guide NoticesBosch Security Systems, Inc /08 F01U089457-02 Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Figures TablesUser Code Allocations Hexadecimal Values for Zone Nos ICP-CC488 Installation Guide Introduction ICP-CC488 FeaturesIntroduction ICP-CC488 Zone Defaults Zone Defaults for the ICP-CC488Quick Start Set the Date and TimeICP-CC488 Installation Guide Codepad Indicators Codepad IndicatorsICP-CP508W Eight Zone LED Codepad Mains Indicator Fault indicatorAudible Indicators ICP-CP508LW Eight Zone LCD CodepadICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads Arming the System in Away Mode Disarming the System from Away ModeArming the System in Stay Mode ICP-CC488 Installation Guide System OperationsDisarming the System from Stay Mode Codepad Duress Alarm Codepad Panic AlarmCodepad Fire Alarm Codepad Medical AlarmIsolating Zones Standard IsolatingFault Analysis Mode Fault DescriptionsSystem Fault indicators AC Mains FailureFault Analysis Conditions Remote Radio Transmitter OperationsRemote Radio User Code Priority Levels Indications from Remote Radio Transmitter OperationsChanging or Deleting Remote Radio User Codes Installer Code Functions ICP-CC488 Installation Guide System FunctionsInstaller Code Functions Add or Delete RF Wireless DevicesChange Domestic Phone Numbers Set the Number of Days until the First Test ReportDomestic Dialing Digits Codepad Indicators When Changing Phone Numbers Examples provided for this feature apply only to AustraliaChange Telco Arm/Disarm Sequence Telco Arm SequenceSatellite Siren Service Mode Setting Stay Mode 2 ZonesTurning Telephone Monitor Mode On and Off Telephone Monitor Mode Indications Event Memory Recall ModeEvent Sequence Event Memory PlaybackMaster Code Functions Master Code FunctionsArm or Disarm Both Areas at the Same Time Changing and Deleting User CodesChanging and Deleting Remote Radio User Codes User Numbers Displayed by the Codepad IndicatorsChanging Domestic Phone Numbers Codepad Indicators When Changing Domestic Telephone Numbers When you program a # in the telco arm sequence, enter STAY2 Turning Outputs On/OffSetting the Date and Time Event Non-volatile Memory Recall ModeArm the System in Away Mode Arm the System in Stay ModeUser Code Functions Hold-Down FunctionsTurning Day Alarm On and Off Fault Analysis ModeReset Latching Outputs Horn Speaker TestICP-CC488 Installation Guide Remote Arming by Telephone Remote Arming by TelephoneProgramming Programming with the Remote CodepadCodepad Indicators ICP-CC488 Installation Guide ProgrammingProgramming with the Programming Key Installer’s Programming Commands Installer’s Programming Mode CommandsCommand 959 Test the Programming Key Programming Option BitsCommand 960 Exit from Installers Programming Mode Command 963 Copy the Programming Key to the Control PanelCommand 964 Erase the Programming Key Command 965 Set Up Domestic Dialing FormatDisable Factory Defaults Example Auto Step EnabledExample Auto Step Disabled Command 965 DefaultsAlarm Link Software ICP-CC488 Installation Guide Alarm Link SoftwareRemote Connect Remote Connection with Customer ControlAlarm Link Options ICP-CC488 Installation Guide Domestic Dialing Enable Alarm Link Call BackTerminate Alarm Link Connection on Alarm Domestic DialingSetting Up and Programming Domestic Reporting ICP-CC488 Installation Guide Dialer Reporting FormatsDialer Reporting Formats Transmission FormatsContact ID Format Breakdown Point ID Codes10.1.4 4 + 2 Reporting Format Example Reporting in 4 + 2 Format + 2 Reporting Format+ 2 Transmission Code Descriptions Basic Pager Reporting Format14.3.2 Basic Pager Display Dialer Information ICP-CC488 Installation Guide Dialer InformationBasic Pager Display Information Primary Telephone Number for Receiver 1 and Receiver Secondary Telephone Number for Receiver 1 and ReceiverHandshake Tone for Receiver 1 and Receiver Dialing DigitsTransmission Format for Receiver 1 and Receiver Subscriber ID Number for Receiver 1 and ReceiverDialing Format Telco Arming SequenceTelco Disarming Sequence Call Back Telephone NumberRing Count Answering Machine BypassTelephone Line Fault Options ICP-CC488 Installation Guide Dialer OptionsDialer Options Dialer OptionsAnswering Machine Bypass Only When Armed Use Bell 103 for FSK Format Disabled=CCITT V21Open/Close Reports Only if Previous Alarm Open/Close Reports for Stay Mode 1 and Stay ModeAccess Codes Installer CodeICP-CC488 Installation Guide Access Codes User CodesUser Code Priority Priority LevelsArm/Disarm Arm OnlyDay Alarm Information ICP-CC488 Installation Guide Zone InformationZone Information EOL Resistor ValueTamper Zone 1 3K3 Zone 5 6K8 Zone Programming Zone Operating InformationZone Options Zone Reporting InformationYou can program Zones 1 to 16 as any zone type Delay-1 Zone Delay-2 ZoneKeyswitch Zone Instant Zone13 24-Hour Fire Zone Chime ZoneZone Not Used Zone Pulse CountDelay Alarm Reporting Silent AlarmKeyswitch Zone Options Latching Arm and Disarm in Away ModeLatching Arm in Stay Mode Latching Disarm from Stay Mode 1 or Stay ModeMomentary Arm and Disarm in Away Mode Momentary Arm in Away ModeSwinger Shutdown Count for Siren Swinger Shutdown Count for DialerSystem Reporting Information Zone Status Zone Tamper ReportZone Status Walk Test Report Zone Status Bypass ReportsZone Status Alarm Restore Code RF Low Battery ReportZone Status Sensor Watch Reports Zone Status Reporting OptionsRF Receiver Trouble Restore Report RF Dialer OptionsOpen/Close Reports Open/Close Reporting OptionsSystem Status AUX Power Supply Fail Report System Status AUX Power Supply Fail Restore ReportSystem Status AC Fail Restore Report Codepad Fire ReportSystem Status Low Battery Report System Status Low Battery Restore ReportSystem Status Access Denied System Status Reporting OptionsProgrammable Outputs ICP-CC488 Installation Guide Programmable OutputsTest Reporting Dialer Options Redirecting Outputs to the Codepad Buzzer Output Event TypesEntry Warning + Day Alarm Resetting Exit Warning + Entry Warning + Day Alarm ResettingDay Alarm Enabled AUX Power Supply FailSensor Watch Alarm Codepad Medical AlarmCodepad Fire Alarm Codepad Panic AlarmFire Alarm Verification Remote ControlRadio Control Output 1 Not in Away Mode Radio Control Output 2 Not in Away ModeArea 1 in Alarm Area 2 in Alarm Mimic ZoneGlobal Chime Zone Not SealedOutput Polarity System Event Timers ICP-CC488 Installation Guide System Event TimersOutput Timing Pulsing PolaritiesProgramming Entry/Exit Timers Entry TimerExit Timer Entry Guard Timer for Stay ModeAuto Arming Pre-Alert Timer Codepad Lockout TimeSiren Run Time Siren Sound RateSystem and Consumer Options Assign Button 4 To Operate Stay Mode Access Denied Code Retries To Be SilentStrobe Indications for Radio Arm/Disarm Codepad Panic To Be SilentConsumer Options Radio Input Options Using Codepads in a Partitioned System ICP-CC488 Installation Guide PartitioningPartitioning 19.1 CP500 Master Partitioned LED CodepadZone Allocations Setting Up and Programming Codepads for Partitioning User Code AllocationsZone Allocations for Areas 1 Detailed ExampleSetting Up an Area 1 Codepad as the Main Codepad Setting Up an Area 1 CodepadSetting Up an Area 2 Codepad Codepad Connections For Partitioning ExamplesRF Information ICP-CC488 Installation Guide RF InformationRF Option Bit Default RF Device Mapping Devices 1 to Default RF Device Mapping Devices 9 toUsing Hexadecimal Values for RF Device Mapping Enable RF Jamming MonitorRF Device Signal Strength Devices 1 to 8 Read Only RF Device Signal Strength Devices 9 to 16 Read OnlyICP-CC488 Installation Guide Optional Equipment Optional Equipment21.5 CC816 Alarm Link Software 21.3 SS914 Edmsat Satellite Siren21.4 CC891 Programming Key ICP-CP500AW Eight Zone Area Addressable CodepadTerminals and Descriptions ICP-CC488 Installation Guide Terminals and DescriptionsTerminal Descriptions Glossary Of Terms Domestic alarm reports That an alarm was sent outStay Mode This mode. Only the installer can program these zonesDiagrams ICP-CC488 Wiring DiagramICP-CC488 Installation Guide Terminals and Descriptions Wiring and Power Up Operation Telecom Connection Diagram for AustraliaYellow wire Green wire Appendix B Test Reports Only When Armed ICP-CC488 Installation Guide AppendicesAppendices Appendix a Telephone Anti JammingSpecifications Warranty StatementSpecifications Software Version NumberICP-CC488 Installation Guide Programming Sheets Programming SheetsTick ICP-CC488 Programming SheetsTelephone Line Fault Options Alarm Link OptionsDialing Format ReservedInstaller Code Day Alarm ZonesUser Code Priority Levels EOL Resistor ValueZone Pulse Count Settings ZonesRF Low Battery Report RF Receiver Trouble Restore ReportZone Descriptions Swinger Shutdown Count for SirenSystem Status AUX Power Supply Fail Report System Status AUX Power Supply Fail Restore ReportSystem Status AC Fail Restore Report System Status Low Battery ReportEntry Guard Time for Stay Mode Delay Alarm Reporting TimeSpeaker Beep Volume Sensor Watch TimeZone Allocations Enabled for Area 1 and Area Radio Input OptionsZone Allocations for Area 1 and Area Domestic Telephone NumbersRF Device Signal Strength Devices 1 to RF Device Signal Strength Devices 9 toRF Options RF Device Mapping OptionDisable Factory Default Country CodesSystem Time System DateICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Index Remote Connect Without Call Back Verification41Telephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02