Page 27

ICP-CC488 Installation Guide 5.0

System Functions

 

 

EN 27

5.2Master Code Functions

Master Code functions allow those users that have the appropriate priority level to perform certain supervisory level functions. You can use these functions only when the system is disarmed.

The default Master Code (User Code 1) is 2580. It is possible to program multiple Master Codes. Refer to Section 13.3 User Code Priority for more information.

To access a Master Code function, enter the Master Code and press the corresponding function digit and the [AWAY] button. The Master Code functions are listed in Table 26.

Table 26: Master Code Functions

Function Description

0Arm or disarm both areas at the same time (Refer to Section 5.2.1)

1Add, change, and delete User Codes/Remote Radio User Codes (Sections 5.2.2 and 5.2.3)

2Change domestic phone numbers (Section 5.2.4)

3Change Telco Arm/Disarm Sequence (Section 5.2.5)

4Set zones for STAY Mode 2 (Section 5.2.6)

5Turn outputs on and off (Section 5.2.7)

6Set the date and time (Section 5.2.8)

7Walk Test Mode (Section 5.2.9)

8Event Memory Recall Mode (Section 5.2.10)

5.2.1Arm or Disarm Both Areas at the Same Time

This Master Code function only operates with partitioned ICP-CC488 systems and allows Master Codes allocated to both Area 1 and Area 2 to arm or disarm both areas at the same time.

This feature allows a Master Code holder to arm or disarm the system by pressing one extra button rather than entering a code twice. You can use either the CP5 Area Addressable Codepad (CP500A) or the Master Partitioned Codepad (CP500P) with this function. To enable this feature, select Option 2 in Location 501 (refer to Section 19.3.2 Partitioning Options 2).

To arm or disarm both areas at the same time: Enter your Master Code and press [0][AWAY]. Two beeps sound and both areas are armed or disarmed from AWAY Mode.

5.2.2Changing and Deleting User Codes

This function allows a Master Code holder to change or delete a User Code.

When using a partitioned ICP-CC488 Control Panel, the Master Code holder cannot add, change, or delete User Codes unless the User Code is allocated to the same area as the Master Code. Refer to Section

13.3User Code Priority for more information.

1.Enter your Master Code and press [1][AWAY]. Three beeps sound and the STAY and AWAY indicators flash.

2.Enter the number of the code (1 to 8) you want to change and press [AWAY].

Two beeps sound and the corresponding zone indicator lights. Refer to Table 27 on page 28.

3.Enter the new code and press [AWAY]. Two beeps sound and the STAY and AWAY indicators are extinguished.

4.Repeat this procedure to change other User Codes.

This function is automatically terminated if you do not press a button within 60 sec or if you press [AWAY].

One long beep indicates that the code already exists or you entered an incorrect user number.

Example

To program User Code number 2 as 4627, enter:

[2 5 8 0 1][AWAY][2][AWAY][4 6 2 7][AWAY]

To delete a User Code:

1.Enter your Master Code and press [1][AWAY]. Three beeps sound and the STAY and AWAY indicators flash.

2.Enter the number of the code (1 to 8) you want to delete and press [AWAY].

Two beeps sound and the corresponding zone indicator lights. Refer to Table 27.

3.Press [STAY] to delete the User Code.

Two beeps sound and the STAY and AWAY indicators are extinguished.

4.Repeat this procedure to delete other User Codes.

This function terminates automatically if you do not press a button within 60 sec or if you press [AWAY].

One long beep indicates that the code already exists or that you entered an incorrect user number.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 27
Contents ICP-CC488 Installation GuideICP-CC488 Installation Guide Notices Copyright NoticeBosch Security Systems, Inc /08 F01U089457-02 Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Tables FiguresUser Code Allocations Hexadecimal Values for Zone Nos ICP-CC488 Features ICP-CC488 Installation Guide IntroductionIntroduction Set the Date and Time ICP-CC488 Zone DefaultsZone Defaults for the ICP-CC488 Quick StartCodepad Indicators ICP-CC488 Installation Guide Codepad IndicatorsICP-CP508W Eight Zone LED Codepad ICP-CP508LW Eight Zone LCD Codepad Mains IndicatorFault indicator Audible IndicatorsICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads ICP-CC488 Installation Guide System Operations Arming the System in Away ModeDisarming the System from Away Mode Arming the System in Stay ModeDisarming the System from Stay Mode Codepad Panic Alarm Codepad Duress AlarmStandard Isolating Codepad Fire AlarmCodepad Medical Alarm Isolating ZonesFault Descriptions Fault Analysis ModeAC Mains Failure System Fault indicatorsRemote Radio Transmitter Operations Fault Analysis ConditionsIndications from Remote Radio Transmitter Operations Remote Radio User Code Priority LevelsChanging or Deleting Remote Radio User Codes Add or Delete RF Wireless Devices Installer Code FunctionsICP-CC488 Installation Guide System Functions Installer Code FunctionsSet the Number of Days until the First Test Report Change Domestic Phone NumbersDomestic Dialing Digits Telco Arm Sequence Codepad Indicators When Changing Phone NumbersExamples provided for this feature apply only to Australia Change Telco Arm/Disarm SequenceSetting Stay Mode 2 Zones Satellite Siren Service ModeTurning Telephone Monitor Mode On and Off Event Memory Playback Telephone Monitor Mode IndicationsEvent Memory Recall Mode Event SequenceChanging and Deleting User Codes Master Code FunctionsMaster Code Functions Arm or Disarm Both Areas at the Same TimeUser Numbers Displayed by the Codepad Indicators Changing and Deleting Remote Radio User CodesChanging Domestic Phone Numbers Codepad Indicators When Changing Domestic Telephone Numbers Turning Outputs On/Off When you program a # in the telco arm sequence, enter STAY2Event Non-volatile Memory Recall Mode Setting the Date and TimeHold-Down Functions Arm the System in Away ModeArm the System in Stay Mode User Code FunctionsHorn Speaker Test Turning Day Alarm On and OffFault Analysis Mode Reset Latching OutputsProgramming with the Remote Codepad ICP-CC488 Installation Guide Remote Arming by TelephoneRemote Arming by Telephone ProgrammingICP-CC488 Installation Guide Programming Codepad IndicatorsProgramming with the Programming Key Programming Option Bits Installer’s Programming CommandsInstaller’s Programming Mode Commands Command 959 Test the Programming KeyCommand 963 Copy the Programming Key to the Control Panel Command 960 Exit from Installers Programming ModeCommand 965 Set Up Domestic Dialing Format Command 964 Erase the Programming KeyCommand 965 Defaults Disable Factory DefaultsExample Auto Step Enabled Example Auto Step DisabledRemote Connection with Customer Control Alarm Link SoftwareICP-CC488 Installation Guide Alarm Link Software Remote ConnectAlarm Link Options Domestic Dialing ICP-CC488 Installation Guide Domestic DialingEnable Alarm Link Call Back Terminate Alarm Link Connection on AlarmTransmission Formats Setting Up and Programming Domestic ReportingICP-CC488 Installation Guide Dialer Reporting Formats Dialer Reporting FormatsExample Reporting in 4 + 2 Format + 2 Reporting Format Contact ID Format BreakdownPoint ID Codes 10.1.4 4 + 2 Reporting FormatBasic Pager Reporting Format + 2 Transmission Code Descriptions14.3.2 Basic Pager Display ICP-CC488 Installation Guide Dialer Information Dialer InformationBasic Pager Display Information Dialing Digits Primary Telephone Number for Receiver 1 and ReceiverSecondary Telephone Number for Receiver 1 and Receiver Handshake Tone for Receiver 1 and ReceiverTelco Arming Sequence Transmission Format for Receiver 1 and ReceiverSubscriber ID Number for Receiver 1 and Receiver Dialing FormatAnswering Machine Bypass Telco Disarming SequenceCall Back Telephone Number Ring CountDialer Options Telephone Line Fault OptionsICP-CC488 Installation Guide Dialer Options Dialer OptionsOpen/Close Reports for Stay Mode 1 and Stay Mode Answering Machine Bypass Only When ArmedUse Bell 103 for FSK Format Disabled=CCITT V21 Open/Close Reports Only if Previous AlarmUser Codes Access CodesInstaller Code ICP-CC488 Installation Guide Access CodesArm Only User Code PriorityPriority Levels Arm/DisarmEOL Resistor Value Day Alarm InformationICP-CC488 Installation Guide Zone Information Zone InformationTamper Zone 1 3K3 Zone 5 6K8 Zone Reporting Information Zone ProgrammingZone Operating Information Zone OptionsYou can program Zones 1 to 16 as any zone type Instant Zone Delay-1 ZoneDelay-2 Zone Keyswitch ZoneZone Pulse Count 13 24-Hour Fire ZoneChime Zone Zone Not UsedLatching Arm and Disarm in Away Mode Delay Alarm ReportingSilent Alarm Keyswitch Zone OptionsMomentary Arm in Away Mode Latching Arm in Stay ModeLatching Disarm from Stay Mode 1 or Stay Mode Momentary Arm and Disarm in Away ModeSwinger Shutdown Count for Dialer Swinger Shutdown Count for SirenZone Status Bypass Reports System Reporting InformationZone Status Zone Tamper Report Zone Status Walk Test ReportZone Status Reporting Options Zone Status Alarm Restore CodeRF Low Battery Report Zone Status Sensor Watch ReportsOpen/Close Reporting Options RF Receiver Trouble Restore ReportRF Dialer Options Open/Close ReportsCodepad Fire Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportSystem Status Reporting Options System Status Low Battery ReportSystem Status Low Battery Restore Report System Status Access DeniedICP-CC488 Installation Guide Programmable Outputs Programmable OutputsTest Reporting Dialer Options Output Event Types Redirecting Outputs to the Codepad BuzzerAUX Power Supply Fail Entry Warning + Day Alarm ResettingExit Warning + Entry Warning + Day Alarm Resetting Day Alarm EnabledCodepad Panic Alarm Sensor Watch AlarmCodepad Medical Alarm Codepad Fire AlarmRadio Control Output 2 Not in Away Mode Fire Alarm VerificationRemote Control Radio Control Output 1 Not in Away ModeZone Not Sealed Area 1 in Alarm Area 2 in AlarmMimic Zone Global ChimeOutput Polarity Pulsing Polarities System Event TimersICP-CC488 Installation Guide System Event Timers Output TimingEntry Guard Timer for Stay Mode Programming Entry/Exit TimersEntry Timer Exit TimerSiren Sound Rate Auto Arming Pre-Alert TimerCodepad Lockout Time Siren Run TimeSystem and Consumer Options Codepad Panic To Be Silent Assign Button 4 To Operate Stay ModeAccess Denied Code Retries To Be Silent Strobe Indications for Radio Arm/DisarmConsumer Options Radio Input Options 19.1 CP500 Master Partitioned LED Codepad Using Codepads in a Partitioned SystemICP-CC488 Installation Guide Partitioning PartitioningZone Allocations Detailed Example Setting Up and Programming Codepads for PartitioningUser Code Allocations Zone Allocations for Areas 1Codepad Connections For Partitioning Examples Setting Up an Area 1 Codepad as the Main CodepadSetting Up an Area 1 Codepad Setting Up an Area 2 CodepadICP-CC488 Installation Guide RF Information RF InformationRF Option Bit Enable RF Jamming Monitor Default RF Device Mapping Devices 1 toDefault RF Device Mapping Devices 9 to Using Hexadecimal Values for RF Device MappingOptional Equipment RF Device Signal Strength Devices 1 to 8 Read OnlyRF Device Signal Strength Devices 9 to 16 Read Only ICP-CC488 Installation Guide Optional EquipmentICP-CP500AW Eight Zone Area Addressable Codepad 21.5 CC816 Alarm Link Software21.3 SS914 Edmsat Satellite Siren 21.4 CC891 Programming KeyICP-CC488 Installation Guide Terminals and Descriptions Terminals and DescriptionsTerminal Descriptions Glossary Of Terms This mode. Only the installer can program these zones Domestic alarm reportsThat an alarm was sent out Stay ModeICP-CC488 Wiring Diagram DiagramsICP-CC488 Installation Guide Terminals and Descriptions Telecom Connection Diagram for Australia Wiring and Power Up OperationYellow wire Green wire Appendix a Telephone Anti Jamming Appendix B Test Reports Only When ArmedICP-CC488 Installation Guide Appendices AppendicesSoftware Version Number SpecificationsWarranty Statement SpecificationsICP-CC488 Programming Sheets ICP-CC488 Installation Guide Programming SheetsProgramming Sheets TickReserved Telephone Line Fault OptionsAlarm Link Options Dialing FormatEOL Resistor Value Installer CodeDay Alarm Zones User Code Priority LevelsZones Zone Pulse Count SettingsSwinger Shutdown Count for Siren RF Low Battery ReportRF Receiver Trouble Restore Report Zone DescriptionsSystem Status Low Battery Report System Status AUX Power Supply Fail ReportSystem Status AUX Power Supply Fail Restore Report System Status AC Fail Restore ReportSensor Watch Time Entry Guard Time for Stay ModeDelay Alarm Reporting Time Speaker Beep VolumeDomestic Telephone Numbers Zone Allocations Enabled for Area 1 and AreaRadio Input Options Zone Allocations for Area 1 and AreaRF Device Mapping Option RF Device Signal Strength Devices 1 toRF Device Signal Strength Devices 9 to RF OptionsSystem Date Disable Factory DefaultCountry Codes System TimeICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Remote Connect Without Call Back Verification41 IndexTelephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02