ICP-CC488 Installation Guide 15.0

System Reporting Information

 

 

EN 65

When the Swinger Shutdown Count is reached, all zones that were activated are locked out according to their individual lockout settings.

If Lockout Dialer is enabled for any zone, the last restore signal is not transmitted until the system is disarmed.

If the ICP-CC488 Control Panel is partitioned, the Swinger Shutdown Count for Dialer applies to both Area 1 and Area 2.

Example

All eight zones are programmed for lockout dialer with a Swinger Shutdown Count of 6. If Zone 1 activates an alarm, the Swinger Shutdown Count decrements to 5 when the control panel calls.

If Zone 1 reactivates the dialer, the Swinger Shutdown Count is decremented by to 4. If Zone 1 reactivates the dialer three more times, the Swinger Shutdown Count is 1.

If Zone 2 activates an alarm, the Swinger Shutdown Count is decremented to 0, which locks out Zone 2 from activating the dialer until the system is reset. At this point, the Swinger Shutdown Count for the Dialer is reset to 6 and the process of swinger shutdown for the remaining zones, including Zone 1, begins again until all zones are locked out.

15.0 System Reporting

Information

This section covers features that are involved with basic housekeeping of the system. These include monitoring of the zones, whether they are isolated from the system or are actually operating, the status of the AC MAINS and DC power to the system, and codepad-generated alarms activated by the user.

15.1Zone Status – Zone Tamper Report

Location 381 to 382

 

Location

Default

Zone Tamper Report

381

0

Zone Tamper Restore Report

382

0

A Zone Tamper Report (Contact ID Event Code

144)is sent when Option 14 is programmed in Location 266 (refer to Section 14.2 EOL Resistor Value on page 56) and the zone loop using split EOL resistors (3K3/6K8) with tamper (1K) becomes open circuit.

To enable Zone Tamper and Zone Tamper Restore Reports, program the two locations with any digit from 1 to 15.

15.2Zone Status – Walk Test Report

Location 383 to 384

 

Location

Default

Walk Test Report

383

0

Walk Test Restore Report

384

0

A Walk Test Report (Contact ID Event Code 607) is sent when either the Installer or Master Code holder activates Walk Test Mode (refer to Section 5.1.8 on page 26 or Section 5.2.9 on page 31 for more information).

To enable Walk Test and Walk Test Restore Reports, program the two locations with any digit from 1 to 15.

15.3Zone Status – Bypass Reports

Location 385 to 386

 

Location

Default

Zone Bypass Report

385

9

Zone Bypass Restore Report

386

8

A zone is bypassed when it is manually isolated. Refer to Section 3.11 Isolating Zones on page 17 for information on isolating zones. A Zone Bypass Report (Contact ID Event Code 573) is sent at the end of Exit Time for any zone that was manually isolated. A 24-Hour Zone sends a Zone Bypass Report when the zone is selected to be isolated.

A Zone Bypass Restore Report is sent when the system is disarmed. All bypassed zones are automatically cleared when the system is disarmed.

The Bypass code parameter has no effect on Contact ID Format because a Zone Bypass is always reported as Event Code 570.

If Zone Bypass Reports are not required, program Locations 385 and 386 as 0.

A24-Hour Burglary Zone that is manually bypassed reports as Contact ID Event Code 572.

A24-Hour Fire Zone that is manually bypassed reports as Contact ID Event Code 571.

15.4Zone Status – Trouble Reports

Location 387 to 388

 

Location

Default

Zone Trouble Report

387

2

Zone Trouble Restore Report

388

3

A zone is in trouble when it is unsealed at the end of Exit Time. A Sensor Trouble Report (Contact ID Event Code 380) is sent to indicate that one or more zones were automatically isolated by the system. 24- Hour Zones that are unsealed at the end of Exit Time do not transmit a Sensor Trouble Report because the restoral for that zone is still outstanding.

Bosch Security Systems, Inc. 12/08 F01U089457-02

Image 65
Contents ICP-CC488 Installation GuideBosch Security Systems, Inc /08 F01U089457-02 ICP-CC488 Installation Guide NoticesCopyright Notice Contents 15.4 Zone Status Trouble Reports 15.5 ICP-CC488 Installation Guide Contents Tables FiguresUser Code Allocations Hexadecimal Values for Zone Nos Introduction ICP-CC488 FeaturesICP-CC488 Installation Guide Introduction Zone Defaults for the ICP-CC488 ICP-CC488 Zone DefaultsQuick Start Set the Date and TimeICP-CP508W Eight Zone LED Codepad Codepad IndicatorsICP-CC488 Installation Guide Codepad Indicators Fault indicator Mains IndicatorAudible Indicators ICP-CP508LW Eight Zone LCD CodepadICP-CP500PW Master Partitioned LED Codepad ICP-CP516 Sixteen Zone Codepads Disarming the System from Away Mode Arming the System in Away ModeArming the System in Stay Mode ICP-CC488 Installation Guide System OperationsDisarming the System from Stay Mode Codepad Panic Alarm Codepad Duress AlarmCodepad Medical Alarm Codepad Fire AlarmIsolating Zones Standard IsolatingFault Descriptions Fault Analysis ModeAC Mains Failure System Fault indicatorsRemote Radio Transmitter Operations Fault Analysis ConditionsChanging or Deleting Remote Radio User Codes Indications from Remote Radio Transmitter OperationsRemote Radio User Code Priority Levels ICP-CC488 Installation Guide System Functions Installer Code FunctionsInstaller Code Functions Add or Delete RF Wireless DevicesDomestic Dialing Digits Set the Number of Days until the First Test ReportChange Domestic Phone Numbers Examples provided for this feature apply only to Australia Codepad Indicators When Changing Phone NumbersChange Telco Arm/Disarm Sequence Telco Arm SequenceTurning Telephone Monitor Mode On and Off Setting Stay Mode 2 ZonesSatellite Siren Service Mode Event Memory Recall Mode Telephone Monitor Mode IndicationsEvent Sequence Event Memory PlaybackMaster Code Functions Master Code FunctionsArm or Disarm Both Areas at the Same Time Changing and Deleting User CodesChanging Domestic Phone Numbers User Numbers Displayed by the Codepad IndicatorsChanging and Deleting Remote Radio User Codes Codepad Indicators When Changing Domestic Telephone Numbers Turning Outputs On/Off When you program a # in the telco arm sequence, enter STAY2Event Non-volatile Memory Recall Mode Setting the Date and TimeArm the System in Stay Mode Arm the System in Away ModeUser Code Functions Hold-Down FunctionsFault Analysis Mode Turning Day Alarm On and OffReset Latching Outputs Horn Speaker TestRemote Arming by Telephone ICP-CC488 Installation Guide Remote Arming by TelephoneProgramming Programming with the Remote CodepadProgramming with the Programming Key ICP-CC488 Installation Guide ProgrammingCodepad Indicators Installer’s Programming Mode Commands Installer’s Programming CommandsCommand 959 Test the Programming Key Programming Option BitsCommand 963 Copy the Programming Key to the Control Panel Command 960 Exit from Installers Programming ModeCommand 965 Set Up Domestic Dialing Format Command 964 Erase the Programming KeyExample Auto Step Enabled Disable Factory DefaultsExample Auto Step Disabled Command 965 DefaultsICP-CC488 Installation Guide Alarm Link Software Alarm Link SoftwareRemote Connect Remote Connection with Customer ControlAlarm Link Options Enable Alarm Link Call Back ICP-CC488 Installation Guide Domestic DialingTerminate Alarm Link Connection on Alarm Domestic DialingICP-CC488 Installation Guide Dialer Reporting Formats Setting Up and Programming Domestic ReportingDialer Reporting Formats Transmission FormatsPoint ID Codes Contact ID Format Breakdown10.1.4 4 + 2 Reporting Format Example Reporting in 4 + 2 Format + 2 Reporting FormatBasic Pager Reporting Format + 2 Transmission Code Descriptions14.3.2 Basic Pager Display Basic Pager Display Information ICP-CC488 Installation Guide Dialer InformationDialer Information Secondary Telephone Number for Receiver 1 and Receiver Primary Telephone Number for Receiver 1 and ReceiverHandshake Tone for Receiver 1 and Receiver Dialing DigitsSubscriber ID Number for Receiver 1 and Receiver Transmission Format for Receiver 1 and ReceiverDialing Format Telco Arming SequenceCall Back Telephone Number Telco Disarming SequenceRing Count Answering Machine BypassICP-CC488 Installation Guide Dialer Options Telephone Line Fault OptionsDialer Options Dialer OptionsUse Bell 103 for FSK Format Disabled=CCITT V21 Answering Machine Bypass Only When ArmedOpen/Close Reports Only if Previous Alarm Open/Close Reports for Stay Mode 1 and Stay ModeInstaller Code Access CodesICP-CC488 Installation Guide Access Codes User CodesPriority Levels User Code PriorityArm/Disarm Arm OnlyICP-CC488 Installation Guide Zone Information Day Alarm InformationZone Information EOL Resistor ValueTamper Zone 1 3K3 Zone 5 6K8 Zone Operating Information Zone ProgrammingZone Options Zone Reporting InformationYou can program Zones 1 to 16 as any zone type Delay-2 Zone Delay-1 ZoneKeyswitch Zone Instant ZoneChime Zone 13 24-Hour Fire ZoneZone Not Used Zone Pulse CountSilent Alarm Delay Alarm ReportingKeyswitch Zone Options Latching Arm and Disarm in Away ModeLatching Disarm from Stay Mode 1 or Stay Mode Latching Arm in Stay ModeMomentary Arm and Disarm in Away Mode Momentary Arm in Away ModeSwinger Shutdown Count for Dialer Swinger Shutdown Count for SirenZone Status Zone Tamper Report System Reporting InformationZone Status Walk Test Report Zone Status Bypass ReportsRF Low Battery Report Zone Status Alarm Restore CodeZone Status Sensor Watch Reports Zone Status Reporting OptionsRF Dialer Options RF Receiver Trouble Restore ReportOpen/Close Reports Open/Close Reporting OptionsSystem Status AUX Power Supply Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AC Fail Restore Report Codepad Fire ReportSystem Status Low Battery Restore Report System Status Low Battery ReportSystem Status Access Denied System Status Reporting OptionsTest Reporting Dialer Options ICP-CC488 Installation Guide Programmable OutputsProgrammable Outputs Output Event Types Redirecting Outputs to the Codepad BuzzerExit Warning + Entry Warning + Day Alarm Resetting Entry Warning + Day Alarm ResettingDay Alarm Enabled AUX Power Supply FailCodepad Medical Alarm Sensor Watch AlarmCodepad Fire Alarm Codepad Panic AlarmRemote Control Fire Alarm VerificationRadio Control Output 1 Not in Away Mode Radio Control Output 2 Not in Away ModeMimic Zone Area 1 in Alarm Area 2 in AlarmGlobal Chime Zone Not SealedOutput Polarity ICP-CC488 Installation Guide System Event Timers System Event TimersOutput Timing Pulsing PolaritiesEntry Timer Programming Entry/Exit TimersExit Timer Entry Guard Timer for Stay ModeCodepad Lockout Time Auto Arming Pre-Alert TimerSiren Run Time Siren Sound RateSystem and Consumer Options Access Denied Code Retries To Be Silent Assign Button 4 To Operate Stay ModeStrobe Indications for Radio Arm/Disarm Codepad Panic To Be SilentConsumer Options Radio Input Options ICP-CC488 Installation Guide Partitioning Using Codepads in a Partitioned SystemPartitioning 19.1 CP500 Master Partitioned LED CodepadZone Allocations User Code Allocations Setting Up and Programming Codepads for PartitioningZone Allocations for Areas 1 Detailed ExampleSetting Up an Area 1 Codepad Setting Up an Area 1 Codepad as the Main CodepadSetting Up an Area 2 Codepad Codepad Connections For Partitioning ExamplesRF Option Bit ICP-CC488 Installation Guide RF InformationRF Information Default RF Device Mapping Devices 9 to Default RF Device Mapping Devices 1 toUsing Hexadecimal Values for RF Device Mapping Enable RF Jamming MonitorRF Device Signal Strength Devices 9 to 16 Read Only RF Device Signal Strength Devices 1 to 8 Read OnlyICP-CC488 Installation Guide Optional Equipment Optional Equipment21.3 SS914 Edmsat Satellite Siren 21.5 CC816 Alarm Link Software21.4 CC891 Programming Key ICP-CP500AW Eight Zone Area Addressable CodepadTerminal Descriptions ICP-CC488 Installation Guide Terminals and DescriptionsTerminals and Descriptions Glossary Of Terms That an alarm was sent out Domestic alarm reportsStay Mode This mode. Only the installer can program these zonesICP-CC488 Wiring Diagram DiagramsICP-CC488 Installation Guide Terminals and Descriptions Telecom Connection Diagram for Australia Wiring and Power Up OperationYellow wire Green wire ICP-CC488 Installation Guide Appendices Appendix B Test Reports Only When ArmedAppendices Appendix a Telephone Anti JammingWarranty Statement SpecificationsSpecifications Software Version NumberProgramming Sheets ICP-CC488 Installation Guide Programming SheetsTick ICP-CC488 Programming SheetsAlarm Link Options Telephone Line Fault OptionsDialing Format ReservedDay Alarm Zones Installer CodeUser Code Priority Levels EOL Resistor ValueZones Zone Pulse Count SettingsRF Receiver Trouble Restore Report RF Low Battery ReportZone Descriptions Swinger Shutdown Count for SirenSystem Status AUX Power Supply Fail Restore Report System Status AUX Power Supply Fail ReportSystem Status AC Fail Restore Report System Status Low Battery ReportDelay Alarm Reporting Time Entry Guard Time for Stay ModeSpeaker Beep Volume Sensor Watch TimeRadio Input Options Zone Allocations Enabled for Area 1 and AreaZone Allocations for Area 1 and Area Domestic Telephone NumbersRF Device Signal Strength Devices 9 to RF Device Signal Strength Devices 1 toRF Options RF Device Mapping OptionCountry Codes Disable Factory DefaultSystem Time System DateICP-CC488 Installation Guide Programming Sheets ICP-CC488 Installation Guide Index Remote Connect Without Call Back Verification41 IndexTelephone Line Fault Options 52, 80 Disarming ICP-CC488 Installation Guide Index Enable User Code + 0 + Away To Arm/Disarm Zone Restore Code Bosch Security Systems, Inc. F01U089457-02