Baldor VS1MD instruction manual

Models: VS1MD

1 168
Download 168 pages 41.14 Kb
Page 100
Image 100

1 = Operation stops when cooling fan malfunctions

When cooling fan fault occurs, message is displayed on the LED and operation is stopped. If t32 and/or t33 is set to 17 (Fault Output), fault message is displayed.

H81 -

H90

Second Motor Parameters

Range:

See below

Default:

See below

Access

Configurable

See Also:

t1-t8

 

 

These parameters activate when a selected terminal is ON and one of the t1 thru t8 terminals is set for 12 (2nd Motor Select).

Param.

Description

Range

Factory Default

Adj. run

H81

Accel Time

0

~ 60000 Sec

1.0

 

H82

Decel Time

0

~ 60000 Sec

5.0

 

H83

Base Freq

30

~ 400 Hz

60.0

-

H84

V/F Pattern

0

~ 2

0

-

H85

FX Torque Boost

0

~ 15 %

5

-

H86

RX Torque Boost

0

~ 15 %

5

-

H87

Stall Level

30

~ 150 %

150

-

H88

1 Min Overload Level

50

~ 200 %

150

 

H89

Continuous Overload Level

50

~ 150 %

100

￿

H90

Motor Rated Current

0.1 ~ 50 Amps

26.3

-

Use these settings when an inverter operates two motors connected to two

different types of loads. 2nd motor operation does not drive two motors at the same time. When first selected motor operation is stopped, select a terminal for the second motor and define H81 thru H90 to run the second motor.

VS1MD

M 1

M 2

P8

Sets the V/F pattern for the second motor.

7-56

VS1MD AC Drive User Manual

Page 100
Image 100
Baldor VS1MD instruction manual