H71 Accel/Decel Time Scale

Range: 0 - 2

Default: 1

Access Tunable

See Also: P36, P41, P42, H70

This parameter is used to scale the time units for the accel/decel ramp. The display for the VS1MD is available up to 5-digits. Therefore, if time unit is set to 0.01 sec for example, maximum accel/decel time would be 600.00 seconds.

0

= Setting Unit: 0.01 sec

Range: 0.01 ~ 600.00

1

= Setting Unit: 0.1 sec

0.1 ~ 6000.0

2

= Setting Unit: 1 sec

1 ~ 60000

H72 Power-On Display

Range: 0 - 9

Default: 0

Access Configurable

See Also:

d0-d9, H74

This parameter selects the parameter to display on the keypad when power is applied.

0

= Frequency Command

1

= Motor RPM

2

= Output Current

3

= Output Voltage

4

= Output Power

5

= Output Torque

6

= DC Link Voltage

7

= Digital Input Status

8

= Digital Output Status

9

= Software Version

H74 Gain for Motor RPM Display

Range:

1-100 [%]

 

 

Default: 100

Access Configurable

See Also:

d1, H72

This parameter is used to change the motor rpm display to a scaled custom factor. When H40 = 0 (V/F Control) or 1 (PID Control), the inverter output frequency is displayed in RPM suing the formula below. Motor slip is not considered.

 

RPM =

120 f

H 74

 

 

 

 

 

P32

100

 

Parameter Descriptions

⎝⎜

 

⎠⎟

7-53