Baldor VS1MD instruction manual Parameter Descriptions

Models: VS1MD

1 168
Download 168 pages 41.14 Kb
Page 81
Image 81

F58

Overload trip time

 

 

 

 

Range:

0-60 [sec]

 

Default:

60

 

Access

Tunable

 

See Also:

F56, F57

 

The inverter output is turned off if the current level set in F57 is exceeded

 

for the time set in F58 – Overload trip time.

 

 

 

 

F59

Stall Prevention select

 

 

 

 

Range:

0 - 7

 

Default:

0

 

Access

Configurable

 

See Also:

t32, t33, F60

 

 

 

0

1

2

3

4

5

6

7

 

During Decel

 

During Constant Run

During Accel

 

Bit 2

 

Bit 1

Bit 0

 

-

 

-

-

-

 

-

-

-

 

 

-

 

-

-

 

 

 

 

 

 

-

-￿

 

 

 

 

 

￿

 

￿

 

During:

 

 

 

Function Description:

 

Acceleration

Motor starts deceleration when current exceeds the value

 

 

set in F60.

 

Constant run

Motor decelerates when current exceeds the value set in

 

 

F6.

 

Deceleration

Motor deceleration is stopped when inverter DC link

 

 

voltage rises above a certain voltage level.

 

t32 and t33:

The drive outputs signals through either the digital (MO) or

 

 

relay output (3A~C) terminals when set = 7 Motor Stall.

 

 

Motor stall status can be monitored in the above codes

 

 

even if F59 is not active.

 

Example:

F59 = 3; stall prevention active during acceleration and

 

 

constant run. When stall prevention is executed during

 

 

acceleration or deceleration, accel/decel times may take

 

 

longer than the user-setting time to prevent a stall

 

 

condition. When stall prevention is activated during

constant run, t1, t2 executed in accordance with the value set in P41 – Accel Time and P42 – Decel Time.

Parameter Descriptions

7-37

Page 81
Image 81
Baldor VS1MD instruction manual Parameter Descriptions