VS1MD ERRATA SHEET

1.1Change from Main Source to 2nd Source

The function of parameters P46 and P47 has been changed. A digital input can now select between the main control and speed setting selected in parameters P38 and P40 and the secondary source set in parameters P46 and P47. A digital input programmed in t1 to t8 must be set to “22” Exchange between second source and drive.

1.2Parameters

P46 Drive Start/Stop Source 2

Range: 0 to 3 (see table for P38)

Default:

0 = Keypad

Access: Configurable

See Also: P38, P47, t1 to t8

This parameter serves as an alternate control mode. It is selectable by a digital input (t1 to t8) = “22” Exchange between second source and drive.

P47 Frequency Setting Mode 2

Range: 1 to 7 (See table for P40)

Default:

1 = Keypad

Access: Configurable

See Also: P40, P47, t1 to t8

This parameter serves as an alternate speed reference mode. It is selectable by a digital input (t1 to t8) = “22” Exchange between second source and drive.

NOTE: Parameters P46 and P47 are only viewable when one of the t1 to t8 terminals is set equal to “22”.

t1-t8 Digital Input 1 define (I/O Terminal P1) to Digital Input 8 define (I/O Terminal P8)

Range:

0 to 25

Default: t1 = 0, t2 = 1, t3 = 2, t4 = 3, t5 = 4, t6 = 5, t7 = 6, t8 = 7

Access: Configurable

See Also:

n/a

Errata Sheet for the VS1MD Drive Installation & Operating Manual