Baldor VS1MD instruction manual H41 Auto-Tuning Range 0 Default, See also H40, H42, H44

Models: VS1MD

1 168
Download 168 pages 41.14 Kb
Page 93
Image 93

Volts per Hertz: Basic Operation of the Drive, set standard motor parameters:

P30 – Motor Hp

P32 – Motor Rated Current

P33 – Motor PolesF30 – V/F Pattern

Slip

Compensation: This function enables the motor to run in constant speed by compensating inherent slip in an induction motor. Set parameters:

P30 – Motor Hp

P32 – Motor Rated Current

P33 – Motor Poles

H32 – Rated Slip Freq

H34 – Motor No Load Current

H36 – Motor Efficiency

H37 – Load Inertia

PID Feedback: H50 thru H56 (see chapter 8 for advanced PID features)

Sensorless

Vector: Open Loop Speed Regulated drive control. Set parameters:

P30 – Motor Hp

P32 – Motor Rated Current

H32 – Rated Slip Freq

H34 – Motor No Load Current

H41 – Auto tuning

H42 – Stator resistance

H44 – Leakage inductance

F14 – Time for magnetizing

H41 Auto-Tuning

Range: 0 - 1

Default: 0

Access Configurable

See also:

H40, H42, H44

If this parameter is set to a 1, it automatically measures the values to assign for parameters H42 – Stator Resistance and H44 – Leakage Inductance.

H42 Stator Resistance (Rs)

Range:

0-28 [Ω]

Default:

n/a

Access

Configurable

See also:

H40, H41, H44

 

 

This is the value of the motor stator resistance.

Parameter Descriptions

7-49

Page 93
Image 93
Baldor VS1MD instruction manual H41 Auto-Tuning Range 0 Default, See also H40, H42, H44, H42 Stator Resistance Rs Range