t47 Frequency corresponding to t46

Range:

0 - 400 [Hz]

Default:

0

Access

Tunable

See Also:

t46

 

 

Sets the inverter output minimum frequency at minimum current of the I input.

t48

Analog Input 0-20mA (I) Max Current

 

Range:

4 - 20mA

 

Default:

20

 

Access

Tunable

 

See Also:

t47

 

 

 

Sets the maximum current of the Analog 0-20mA (I) Input.

t49 Frequency corresponding to t47

Range:

0 - 400 [Hz]

Default:

60

Access

Tunable

See Also:

t48

 

 

Sets the inverter output maximum frequency at maximum current of the I input.

t57 Keypad Error Output

Range:

0 - 3

 

 

 

Default:

0

 

 

 

Access

Tunable

 

 

 

 

 

Relay Output

 

Digital Output

 

 

 

0

 

Bit 2

 

Bit 0

 

-

 

-

 

1

 

-

 

￿

2

 

￿

 

-

 

3

 

￿

 

￿

 

 

 

 

Selects the Digital and/or Relay output when a keypad-inverter communication fails.

When communication error occurs for a certain time, will be displayed and the error signal can be sent to the Digital (MO) or Relay output.

0:

Not used

1:

Signal output to MO

2:

Signal output to 3A, 3B contacts

3:

Signal output to MO, 3A, 3B