Baldor VS1MD instruction manual 120, H7 Dwell Frequency Range

Models: VS1MD

1 168
Download 168 pages 41.14 Kb
Page 85
Image 85

H7 Dwell Frequency

Range:

0.1-400 [Hz]

Default:

5.00

Access

Configurable

See also:

P35, P36, H8

 

 

When run frequency is issued, the motor will accelerate after the Dwell Frequency is applied for the Dwell Time – H8. Dwell frequency can be set within Frequency High and Low Limits (P35 and P36).

Dwell frequency is used to output torque in an intended direction. It is useful in hoisting applications to apply torque before releasing a mechanical brake. Rated slip frequency is calculated by the formula shown below:

fs

= fr

 

rpm P

 

 

120

 

 

 

 

 

Where,

f s = Rated slip frequency

f r = Rated frequency rpm = = Motor nameplate RPM

P = Number of

Motor poles

H8

 

 

 

 

Example:

Rated frequency = 60Hz; Rated RPM = 1740rpm;

Number of motor poles= 4

 

 

 

 

 

fs = 60

1740 4

= 2Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dwell freq.

 

 

 

 

 

 

 

 

 

 

 

 

 

Start freq.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

 

 

 

 

 

Dwell time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dwell Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range:

 

0-10 [sec]

 

 

 

 

 

 

 

 

 

 

Default:

 

0.0

 

 

 

 

 

 

 

 

 

 

 

 

Access

 

Configurable

 

 

 

 

 

 

 

 

 

 

See also:

 

H7

 

 

 

 

 

 

 

 

 

 

 

 

dwell operation.

 

 

 

 

Sets the time for

 

 

 

 

 

 

 

 

 

 

 

 

Parameter Descriptions

7-41

Page 85
Image 85
Baldor VS1MD instruction manual 120, H7 Dwell Frequency Range