P40

Frequency Setting Method

 

Range:

1

= Digital Keypad

 

 

2

= Analog V1 1: -10 - +10V

 

 

3

= Analog V1 2: 0 ~ +10 V

 

 

4

= Analog Terminal I: 0 - 20mA

 

 

5

= Analog Terminal V1 Mode 1+ Terminal I

 

 

6

= Analog Terminal V1 Mode 1+ Terminal I

 

 

7

= Analog RS485

 

Default:

 

1

 

Access

 

Configurable

 

See Also:

 

t32-t33, F60

 

 

 

 

Sets the source of the speed reference to the drive.

1 = Keypad:Drive output frequency is set in the operation mode by pressing the up/down keys. The drive immediately responds to the new setting without pressing the enter key.

2 = Analog V1 Mode 1:Drive output frequency is set via a +/- 10V signal applied to analog input terminal V1.

3 = Analog V1 Mode 2:Drive output frequency is set via a 4~20mA signal applied to analog input terminal V1.

4 = Analog I:Drive output frequency is set via a 4~20mA signal applied to analog input terminal I.

5 = Analog V1 Mode 1 + I:Drive output frequency is set via the sum of a +/-10V signal applied to V1 and a 4~20mA signal applied to terminal I.

6 = Analog V1 Mode 2 + I:Drive output frequency is set via the sum of a 0~10V signal applied to V1 and a 4~20mA signal applied to terminal I.

7 = RS485:Drive output frequency is controlled via the RS485 communications port.

P41

Accel Time

 

P42

Decel Time

 

 

 

 

 

Range:

0 - 6,000 [sec]

 

Default:

P41 = 5.0, P42 = 10.0

 

Access

Tunable

 

See Also:

P42, P36, H70, H71

 

 

 

Sets the Accel/Decel time of the drive. When using the multiple accel/decel curves with preset speeds, this ramp serves as accel/decel time 0.

H71 can be used to scale the accel/decel units and H70 determines if the time to accel/decel is relative to P35 (Frequency High Limit) or the delta change of running frequency to set frequency.