5.3Terminal Wiring (Control I/O)

T/M

Description

MO

Multi-function open collector output

 

MG

MO Common

 

 

24

24V output

 

 

P1

MF input terminal

FX: Forward run

 

P2

(factory setting)

RX: Reverse run

 

CM

Input signal common

 

 

P3

MF input terminal

BX: Stop

 

P4

RST: Trip reset

 

(factory setting)

 

P5

JOG: Jog operation

 

CM

Input signal common

 

 

P6

MF input terminal

Preset Speed Input 1

P7

 

 

(factory setting)

Preset Speed Input 2

P8

 

 

 

Preset Speed Input 3

 

 

VR

10V power supply for potentiometer

 

V1

Freq. Setting Voltage signal input: -0~10V

I

Freq. Setting Current signal input: 0~20mA

AM

Multi-function analog output signal: 0~10V

3A

Multi-function relay

A contact output

N.O.

3B

output terminal

B contact output

N.C.

3C

 

A/B contact common

S+

RS485 communication terminal

 

S-

 

 

 

 

#For connection to Remote Option or parameter copying