Criteria for Analog Input Signal Loss

 

Range:

0

= Disabled

 

 

1

= Activated below half of set value

 

 

2

= Activated below set value

 

Default:

0

 

 

Access

Tunable

 

See Also:

t32-t33, t36, t41, t46, t62-t63

 

 

 

 

Selects the drive mode when frequency reference set by the Analog (V1, I) input terminal or communication option is lost.

t35 [Criteria for analog input signal loss]

0

1

2

Disabled (Does not check the analog input signal loss)

When half the value set in t36, t41, t46 is entered

When less than the value set in t36, t41, t46 is entered

Example 1) The inverter determines the freq reference is lost when P40 – Freq set method is set to 3 (Analog V1 input), t16 to 1 and analog input signal is less than half the value set in t36.

Example 2)The inverter determines the freq reference is lost when P40 – Freq set method is set to 6 (V1+I), t16 to 2 and V1 input signal is either below the value set in t36 or I input value is less than the t46 value.

Example diagram when t35 is set to 2, I62 to 2, I63 to 5.0 sec and t32 to 11:

t36

Analog Input 0 to -10V (NV) Min voltage

 

 

Range:

0 to -10V

 

 

Default:

0

 

 

Access

Tunable

 

 

See Also:

P40, t37

 

 

Sets the￿￿￿￿￿￿￿minimum

voltage of the NV (-10 to￿￿￿￿￿0V) input.

 