2 = User V/F is a custom volts per hertz pattern established using parameters F31~F38.

Voltage

 

 

 

 

 

100%

 

 

 

 

 

F38

 

 

 

 

 

F36

 

 

 

 

 

F34

 

 

Linear

 

 

 

 

V/F

 

F32

 

 

 

 

 

 

 

 

 

 

Freq.

Start

F31

F33

F35

F37

Base

freq.

 

 

 

 

freq.

F31 User V/F frequency 1

F33 User V/F frequency 2

F35 User V/F frequency 3

F37 User V/F frequency 4

Range:

0 - 400 [Hz]

 

 

Default: F31=15, F33=30, F35=45, F37=60

Access Configurable

See Also: P34, P35, F31-F38, H40

When F30 = 2, selects the frequency for each point in a custom volts per hertz pattern.

F32 User V/F voltage 1

F34 User V/F voltage 2

F36 User V/F voltage 3

F38 User V/F voltage 4

Range:

0-100 [%]

 

 

Default: F32=25,F34=5-, F36=75, F38=100

Access Configurable

See Also: P34, P35, F31-F38, H40

When F30 = 2, selects the voltage for each point in a custom volts per hertz pattern.