Baldor VS1MD instruction manual F11 DC Brake Time Range, F12 DC Brake start voltage Range

Models: VS1MD

1 168
Download 168 pages 41.14 Kb
Page 74
Image 74

F11

DC Brake Time

 

 

Range:

0-60 [sec]

 

Default:

1.0

 

Access

Configurable

 

See Also:

P35, P39, F8-F11

 

Note:

Only viewable when P39 – Stop mode select is set to DC

 

 

Brake.

 

 

 

Sets the time for F10 – DC Brake Voltage to be applied to the motor after F9

DC Brake wait time. Setting F10 or F11 to zero will disable the DC Brake function. In case of DC Brake at high load inertia and frequency, change the DC brake controller gain according to H37 set value.

F12 DC Brake start voltage

Range:

0-200 [%]

 

 

Default: 50

Access Configurable

See Also:

F12, t1-t8

This parameter sets the amount of DC voltage before a motor starts to run. It is set as percentage of P33 – Motor rated current.

F13 DC Brake start time

Range:

0-60 [sec]

 

 

Default: 0

Access Configurable

See Also:

F12, t1-t8

DC voltage is applied to the motor for DC Brake start time before motor accelerates.

Freq.

 

F13

t

Voltage

F12

Run

 

command

 

Setting F12 or F13 to 0 will disable the Starting DC brake. After F13 – DC Brake start time, the frequency is increased. If a digital input (t1~t8) is set for 11 – DC brake during start, the voltage is not released until the input is opened. The drive will accelerate with dc voltage applied until the input is open.

7-30

VS1MD AC Drive User Manual

Page 74
Image 74
Baldor VS1MD instruction manual F11 DC Brake Time Range, F12 DC Brake start voltage Range, F13 DC Brake start time Range