Installation & User Guide
Pressing the End delay button will terminate any delay time and all the sockets in the unit will be switched on. Reset Power button will bring the value of total power back to zero.
Voltage, current and the power readings are displayed on the LCD screen on the PDU. If you press button No.4 you’ll be able to view the Serial Number. Button No. 5 will display the channel status for all the sockets. The status of each channel is reported in the following way:
0Switched Off
1Switched On F Fuse Fault
¾ Mains present on the output but the relay is off.
Button No.6 displays the Hardware and the Firmware version inside the unit. In order to reset the PDU to its default settings press and hold buttons 1, 3, 4 and 6. After resetting the unit, the time interval between the sockets being switched on (in the
States to be indicated on PDU relay LED:
1.Normal: Power switched on, power sensed – LED on solid
2.Fault Feedback: Power switched off, power sensed – 0.5 sec on/off flash for 3 seconds, off 2 seconds
3.Fuse Fault: Power switched on, power not sensed – 80 ms seconds on/off flash
4.Socket Off: Power switched off, power not sensed – LED off.